DVM CHILLER [Basic, Advanced]
DVM CHILLER [Basic, Advanced]
Single DVM CHILLER Unit has following point list.
Instance
Object
Number
1
Chilled Water Temperature
2
Set temperature
3
Demand limit setting
The number of hours usage of an
4
indoor unit after the basic date
The number of hours usage of an
5
indoor unit within peirod
6
Power On/Off operation
7
Water Law
8
Quiet
9
Forced Fan
10
Operation mode status
11
Remote controller limit status
12
Integrated error code
13
DVM CHILLER Notify
BACnet Device Object does not support master function of
DVM CHILLER.
Demand control setting range is as follows:
50,55,60,65,70,75,80,85,90,95,100(%)
SIM/PIM [Basic, Advanced]
SIM/PIM [Basic, Advanced]
Single SIM/PIM has following point list.
Instance
Object
Number
1
SIM/PIM error code
2
SIM/PIM Notify
Centralized Controller (OnOff Controller) [Basic, Advanced]
Centralized Controller (OnOff Controller) [Basic, Advanced]
Single Centralized Controller (OnOff Controller) has following point list.
Instance
Object
Number
Centralized Controller
1
(OnOff Controller) error code
Centralized Controller
2
(OnOff Controller) notify
Object
Object Name
Type
AI
MC_WaterTemp_xx_xxxxxx
AV MC_WaterTemp_Set_xx_xxxxxx
AV MC_Demand_Set_xx_xxxxxx
AI
MC_Baseline_Minute_xx_xxxxxx
AI
MC_Period_Minute_xx_xxxxxx
BV
MC_Power_xx_xxxxxx
BO MC_Water_Law_xx_xxxxxx
BV
MC_Quiet_xx_xxxxxx
BV
MC_Forced_Fan_xx_xxxxxx
MV MC_Operation_Mode_xx_xxxxxx
MV MC_Remocon_Limit_xx_xxxxxx
AI
MC_Error_Code_xx_xxxxxx
NC MC_Notify_xx_xxxxxx
Object
Object Name
Type
AI
SIM_Error_Code_xx_xx
NC
SIM_Notify_xx_xx
Object
Object Name
Type
AI
Central_Error_Code_xx_xx
NC
Central_Notify_xx_xx
Unit
Status value
Inactive Active
Text-1 Text-2
Text-3
Text-4 Text-5
°C/F
°C/F
%
Minute
Minute
Off
On
False
True
Off
On
Off
On
Cool
Hot
Cool
Heat
Storage
Water
Enable
Disable
Conditional
RC
RC
RC
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
Status value
Refer to list of error code
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
Status value
Refer to the list of the integrated
error code
When the error occurred, send event to
list of destination in the recipient_list.
(Max : 8)
71