Summary of Contents for Samsung DMS2.5 MIM-D01ANDZ
Page 1
DMS2.5 MIM-D01ANDZ BACnet Gateway MIM-B17BNDZ • Thank you for purchasing this Samsung Product. • Before operating this unit, please read this manual carefully and retain it for future reference. • For more information on using the product, download the user manual from the product and refer...
Safety Precautions Cautions for operation • Before using the DMS2.5, BACnet Gateway, read carefully these instructions. • After reading the instructions, keep this user's manual in a handy and safe place. If a user is changed, you must hand over the manuals. •...
Page 3
Cautions for installation • This user & installation manual describes how to install the DMS2.5, BACnet Gateway. For installation of other optional accessories, refer to the appropriate installation manual. Read carefully this user & installation manual before installation and WARNING check if the product is installed correctly after installation.
A static IP from an internet service provider must be used if xDSL (ADSL, VDSL) is supported. Use this product only in a separate dedicated network. Samsung electronics is not liable for any problems caused by connecting it to the Internet or an intranet.
Accessories Make sure you have each item. Supplied items may vary depending on your country or service provider. Item DMS2.5 Adapter Power cable M4 x16 Screw Quantity Shape User & Installation Cable tie manual The DMS2.5 must be installed by a trained installer. ...
Viewing the Parts Main Parts DMS2.5 Exterior DMS2.5 Exterior LCD Display Shows current time and IP address. Various messages will be displayed depending on button input. LCD operation button There are 4 buttons(Menu, ▼(Down), ▲(Up), Set) and you can access menu and move, check the menu.
Page 8
Viewing the Parts (Continued) DMS2.5 Cable Connection Part DMS2.5 Cable Connection Part RS485 Communication Terminal DI Terminal1 DI Terminal2 DO Terminal3 DO Terminal4 Reserved Cable tie groove Power Terminal SD Card Socket Ethernet Terminal Reset Button Name Description DI Terminal1 Digital Input connection terminal, Channel1~Channel5 DI Terminal2 Digital Input connection terminal, Channel6~Channel10...
Main Parts DMS2.5 Interior DMS2.5 Interior Display Board 20-pin Cable Main Board 40-pin Cable Sub Board Note Note If you need external circuit configuration, consult with the manufacturer. Refer to page 18 for DI contact input operation. Product Dimensions (Unit : mm) 64.80...
System Architecture S-NET 3 Web Client TCP/IP Internet DMS2.5 Touch OnOff PM 05:45 Centralized Controller controller R5 485 SIM/PIM Outdoor Unit Power Meter Max 256 Indoor units (DVM Series) Connecting outdoor unit and DMS2.5. - You can control up to 80 outdoor units and 256 indoor units by using DMS2.5. ...
( Please consult Samsung for compatible power meters) Watt-hour Meter Connected with PIM Pulse type Pulse Width: 20~400(ms) Pulse: 1~10000(Wh/Pulse) Products with ‘* ’ are not Samsung products and must be purchased separately. (Only selected power meters may be used for protocol compatibility issues.)
Page 12
Compatible Devices (Continued) Maximum Devices Attachable Devices Max. Note Tracking error occurs if exceeded The maximum number of indoor units Indoor Unit (including ERV and MCU) that can be connected to each DMS communication channel is 128. OnOff controller/ Must not exceed 15 units per each RS485 communication terminal Touch Centralized controller Must not exceed 16 units per each...
Installing the DMS2.5 Separate the installation plate on the rear side of DMS2.5. Fix the installation plate on the wall using 4 screws. Hang the DMS2.5 on the groove which is on the top of the installation plate. Installation plate Fix the installation plate and DMS2.5 using 2 screws.
Page 14
Installing the DMS2.5 (Continued) Connecting Outdoor Unit Unfasten the 2 screws on the bottom of the DMS2.5 front cover. Hold the bottom 2 sides of the DMS2.5 and push downwards to slide open the cover. Connect the adapter to the power terminal. ...
Page 15
Connecting SIM Unfasten the 2 screws on the bottom of the DMS2.5 front cover. Hold the bottom 2 sides of the DMS2.5 and push downwards to slide open the cover. Connect the adapter to the power terminal. Arrange the adapter as the right figure. Adapter Separate 1 terminal block from 5 terminal blocks which are attached to RS485 communication terminal.
Page 16
Installing the DMS2.5 (Continued) Using the DI External Contact Control (Optional) Setting the External Contact Control Pattern Setting the External Contact Control Pattern You can set the system settings through contact control pattern. Select [System Settings] menu and click [System environment setting]. Click [Edit] from ‘Select the contact control pattern’...
Page 17
Contact control Pattern Contact control Pattern Pattern Control ▶ No external input (Factory default setting) Pattern1 When you input contact control signal in port 1, there will be no response. ▶ Level input (Emergency stop) 1. If the contact control signal is changed to ON, emergency stop status and all the indoor units are given ‘Stop’...
Page 18
Installing the DMS2.5 (Continued) DI(Digital Input) Circuitry according to Contact DI(Digital Input) Circuitry according to Contact control Pattern control Pattern Pattern 2 (May be used for connection with a fire sensor) DMS2.5 Emergency Stop/Resume Operation No Connection Pattern 3 (External contact signal control) ...
Setting the Computer Environment Device related to network (Purchase separately) Computer with a LAN Card HUB or network cable(Cross·Direct cable) Computer web browser specification Chrome 86 or later version Note Note A cross cable is used when connecting to PC directly. It is produced as transmission and reception cables are crossed.
Page 20
Setting the Computer Environment (Continued) Computer Settings for DMS2.5 Connection All settings of DMS2.5 will be arranged in web page which built in DMS2.5. You should access to DMS2.5 IP to use DMS2.5 web page. Set your computer settings as follows. DMS2.5 Factory default setting ...
Setting the DMS2.5 DMS2.5 Connection and Login From the computer desktop, double-click the Chrome icon. When the Chrome window appears, enter IP (https://192.168.0.100) in the address input field and press [ENTER]. When you access DMS2.5 for the first from the Chrome browser on your computer, a security certificate warning screen appears.
Page 22
Setting the DMS2.5 (Continued) If the screen above appears again although you have registered the DMS2.5 certifi- cate, stop accessing the solution. There is a risk that a security issue may occur.
How to register the DMS2.5 certificate to a web browser At the top right of the Chrome browser, click the three-dot button and select ‘Settings’ to access the Settings page. B. From the Settings page, access the ‘Privacy and security’ menu and click Security. C.
Page 24
Setting the DMS2.5 (Continued) In the Certificates dialogue box, select the ‘Trusted Root Certification Authorities’ tab and then the ‘Import’ button. Load the saved certificate and click ‘Next’ . The DMS2.5 certificate can be downloaded from [System environment setting]...
Page 25
Select the ‘Place all certificates in the following store’ option, set Certificate store to ‘Trusted Root Certification Authorities’ and then click ‘Next’ . Read the details, and click ‘Finish’ to complete certificate registration.
Page 26
Setting the DMS2.5 (Continued) When the initial screen of the DMS2.5 website appears, enter your ID and password and click [LOGIN]. Access to some functions may be restricted, depending on the user authorisation setting configured by the administrator. To change your user authorization setting, select System settings > User authorization management.
Page 27
DMS2.5 System Environment Setting (Network settings) You can set and check information about DMS2.5 installation operation. DMS2.5 Network Information Setting DMS2.5 Network Information Setting Select [System Settings] menu and click [System environment setting]. Click [Edit] from DMS2.5 network information window. When text boxes of IP address, subnet mask address, default gateway and DNS server are enabled, enter values for each item.
Page 28
(ex: an office LAN), it could be a risk of illegal approach. Also, this may change it to a harmful connection for other network devices. This is not the responsibility of Samsung Electronics and not included in compensation for the damage.
Page 29
System Time Setting System Time Setting Select [System Settings] menu and click [System environment setting]. Click [Edit] from system time setting. Enter system time(year/month/day/hour/minute/second). You can enter only numbers. Year: You can enter from 1980 to 2035. Month: You can enter from 1 to 12. ...
Page 30
Setting the DMS2.5 (Continued) DMS2.5 Name Setting DMS2.5 Name Setting Select [System Settings] menu and click [System environment setting]. Click [Edit] from DMS2.5 name setting window. Enter name of DMS2.5 when DMS2.5 name field enabled. You can use maximum 30 letters including English alphabets and special symbols.
Page 31
Error Mail Forwarding Setting Error Mail Forwarding Setting Select [System Settings] menu and click [System environment setting]. Click [Edit] from error mail forwarding setting. Set all the items as the value you want when all items fields are enabled. If you select ‘Apply’ , you should enter e-mail address, SMTP server ID, password, and SMTP server address.
Page 32
Setting the DMS2.5 (Continued) Setting Enable public IP Setting Enable public IP Select [System Settings] menu and click [System environment setting]. Click [Edit] on Enable public IP section. Select whether to use Public IP or not. When you select ‘Enable’ , you must register the Public IP of PCs or network devices to access DMS2.5 from the PCs or network devices.
Page 33
System setting initialization 192.168.0.100 06:12:13(AM) Press [Menu], [], [] or [Set] on LCD if IP and current time are displayed on LCD screen. Main menu screen appears. Initialization is not possible in the screen which time information is displayed.
Tracking What is tracking? Tracking is an operation that finds devices which are connected to DMS2.5. Through tracking operation, devices which are connected to DMS2.5 can recognize if they are connecting to DMS2.5. To supervise and control system air conditioner using DMS2.5, tracking should be done first. ...
Page 35
Setting Communication Mode for Each Channel Setting Communication Mode for Each Channel Select [System Settings] menu and click [Tracking]. Click [Edit] from communication mode for each channel setting. [Edit] will change to [Cancel]. Selection buttons are enabled. However, the channels which have searched device maintains its selection button disabled.
Page 36
Tracking (Continued) DVM Tracking DVM Tracking Select [System Settings] menu and click [Tracking]. Click [DVM Tracking]. Enter administrator’s password and then click [OK]. Tracking information window pops up. Check it and click [OK] to continue. Execute tracking depending on the communication mode set by communication mode setting for each channel.
Page 37
Tracking completed message will appear. Select Zone initialization mode you want. No initialization: No zone information initialization will be made. Individual initialization: Initialize zone information as individual mode. - Individual mode: Arrange by indoor unit main address on monitoring page. ...
Page 38
Tracking (Continued) Disconnect All Devices Function Function Initialize searched device status in DMS2.5. Monitoring and controlling of all the connected devices to DMS2.5 will be stopped when you use this function. Connect searched device to the other channel and execute tracking. If the other device is searched in the channel you want to use, use ‘Disconnect all devices’...
Page 39
Renaming the Device Renaming the Device Select [System Settings] menu and click [Tracking]. Click [Edit] on the bottom of tracking device list. [Edit] will change to [Cancel]. When the type of the device is displayed, NEW communication address will be shown with it.
Page 40
Tracking (Continued) DMS DI•DO Port Setting DMS DI•DO Port Setting Select [System Settings] and then click [Tracking]. Click [Setting] which is next to DMS DI•DO of device list. Click [Edit] which is on the bottom of DMS DI•DO setting page. ...
Page 41
PIM Setting System Settings ] [ Tracking ] when DMS2.5 web Click [ page menu screen appears. Setting ] which is next to PIM of device list. Click [ Enter administrator’s password and then click [ OK ]. Edit ] which is on the bottom of PIM setting page.
Setting the Power Distribution When doing power distribution, set SIM/PIM channel for each indoor unit. Channel Setting by Indoor Unit Click [EHP Power Consumption Inspection] [Channel setting by indoor unit] when DMS2.5 web page menu screen appears. Click [Edit] when the setting channel by indoor unit screen appears.
Page 43
Check the virtual channel information of indoor/outdoor unit. To execute power distribution without SIM/PIM, you should set virtual channel. When bringing indoor unit’s power from outdoor unit, set the ‘Outdoor unit virtual channel’ information only. ( ‘Outdoor unit virtual channel’ is referring to watt-hour meter which is connected to outdoor unit.) ...
Appendix IP Terminology DMS2.5 needs IP address to contact other computers. 1. Public IP Static IP 1-1. Dynamic IP 1-2. 2. Private IP Static IP 2-1. Dynamic IP 2-2. : Ordinary IP used to connect internet is called 1. Public IP public IP.
Page 45
Examples of DMS2.5 Installation with DSL Local Management without External Control : Use Private IP Local Management without External Control : Use Private IP Direct connection between DMS2.5 and computer or controller Computer DMS2.5 Cross cable Private IP : 192.168.0.100 Private IP : 192.168.0.1 (Mount separate LAN card) ...
Page 46
Appendix (Continued) Initial Connection Error (for Private IP) Several DMS2.5s are Connected to the Same Network Several DMS2.5s are Connected to the Same Network Computer DMS2.5 ① Initial IP : 192.168.0.100 Computer cannot distinguish which DMS2.5 DMS2.5 ② has 192.168.0.100 IP. Initial IP : 192.168.0.100 DMS2.5 ③...
BACnet Gateway setting System Architecture BMS system BMS Engineering Internet SAMSUNG Engineering BACnet Gateway Touch OnOff PM 05:45 Touch Centralized Controller Centralized controller Control & Schedule Settings Monitoring controller RS 485 Outdoor Unit Max 256 Indoor units (DVM Series) Connecting outdoor units and BACnet Gateway - You can control up to 80 outdoor units and 256 indoor units using BACnet Gateway.
Page 48
Pulse Width: 20~400(ms) Pulse: 1~10000(Wh/Pulse) Products with ‘* ’ are not Samsung products and must be purchased separately. (Only selected power meters may be used for protocol compatibility issues.) Samsung is not responsible for BMS engineering which creates each device and objects.
Page 49
Maximum Devices Attachable Maximum Devices Attachable Devices Max. Note Tracking error occurs if exceeded The maximum number of indoor units (including Indoor Unit ERV and MCU) that can be connected to each communication channel is 128. OnOff controller/ Must not exceed 15 units per each RS485 Touch communication terminal Centralized...
Page 50
BACnet Gateway setting (Continued) Setting the BACnet Gateway BACnet Gateway Connection and Login BACnet Gateway Connection and Login Click web browser (chrome) twice on your computer. When web browser window appears, enter IP address (https://192.168.0.100) on the address bar then press [ENTER].
Page 51
If you use accounts with authorization level lower than management group or accounts with general authorization level, you cannot access BACnet Gateway settings. If you cannot access BACnet Gateway, consult the manager. If you login successfully, 'Control and Monitoring' screen will appear.
Page 52
BACnet Gateway setting (Continued) Reading EHP Watt-hour Meter Setting and checking watt-hour meter Setting and checking watt-hour meter Click [System and Checking Watt-hour meter]. You can change settings on watt-hour meter only when SIM/PIM interface module is connected. Click [Edit] from the 'Setting and checking Watt-hour meter' screen. ...
Page 53
Monthly baseline setting Monthly baseline setting Click [System and Checking Watt-hour meter]. Click [Edit] from the ‘Monthly baseline setting’ screen. You can make changes when list box enables. Set the Monthly baseline setting. You can select from 1 ~ 31. ...
Page 54
BACnet Gateway setting (Continued) System Settings You can set and check information about BACnet Gateway installation and operation. BACnet Gateway network information BACnet Gateway network information Click [System Settings]. Click [Edit] from the ‘BACnet network information’ section. When text boxes of IP, Subnet mask, Default gateway, DNS server, BBMD IP, BBMD PORT, Network No., and BACnet PORT are enabled, enter the address values for each item.
Page 55
BACnet gateway information and initialization BACnet gateway information and initialization Click [System Settings]. You can check the basic BACnet gateway information from 'BACnet gateway information' section. Click [Edit] from the ‘BACnet gateway information’ section. If you want to initialize ‘Recipient_list’ , Check and click [Save].
Page 56
BACnet Gateway setting (Continued) Device Configuration Checking device information Checking device information Click one of the Object ID from 'Object ID' column. Detail information of the selected device will be displayed in device information. Analog data of the selected device will be displayed in Analog data. ...
Page 57
BACnet Protocol Implementation Conformance Statement Date: 2017. 08. 31 Vendor Name: Samsung Electronics Co., Ltd. Product Name: DMS BACnet Gateway Product Model Number: MIM-B17BN, MIM-B17BNDZ Application Software Version: 1.20 Firmware Revision: 1.35 BACnet Protocol Revision: 12 Product Description: This product supports BACnet/IP and provide functions to monitor and control status of air conditionerss.
Page 60
If this product is a communication gateway, describe the types of non-BACnet equipment/ networks(s) that the gateway supports: This gateway switches SAMSUNG air conditioner protocol to BACnet protocol to make RS-485 communication possible with the air conditioners connected to gateway.
Page 61
Detail Description of Object Device Device Following table shows regulation of device ID and they are created automatically. DNET – Range CPP – Range INDOOR – Range Item [Digit 2] [Digit 3] [Digit 2] Centralized Controller 1~40 000~015 (OnOff Controller) SIM/PIM 1~40 100~115...
Page 62
BACnet Gateway setting (Continued) BACnet Point List The BACnet point list varies depending on which [BACnet point provision type] is selected in the [System Settings] menu. There are two BACnet point provision types: (1) Basic: Reflects the default points. (2) Advanced: Reflects updated points. For details, refer to the point list below.
Page 63
Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 * 24 °C(°F) Discharge current temperature AC_DisCurrentTemp_xx_xxxxxx When the error occurred, send event to list of ** 25 AC Indoor Notify AC_Notify_xx_xxxxxx destination in the recipient_list. (Max : 8) ...
Page 64
BACnet Gateway setting (Continued) Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Integrated error code of both indoor ** 19 Refer to list of error code AC_Error_Code_xx_xxxxxx unit and outdoor unit * 20 False True...
Page 65
AHU Kit [Basic] AHU Kit [Basic] Single AHU unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Indoor Temperature AHU_RoomTemp_xx_xxxxxx °C Set temperature AV AHU_Temp_Set_xx_xxxxxx °C Setting lower temperature AV AHU_Cool_LimitTemp_xx_xxxxxx °C limit...
Page 66
BACnet Gateway setting (Continued) AHU Kit [Advanced] AHU Kit [Advanced] Single AHU unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Indoor Temperature AHU_RoomTemp_xx_xxxxxx °C Set temperature AV AHU_Temp_Set_xx_xxxxxx °C Setting lower temperature...
Page 67
Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Cooling temperature upper AV AHU_Cool_Upper_LimitTemp_xx_xxxxx °C(°F) limit Heating temperature lower AV AHU_Heat_Lower_LimitTemp_xx_xxxxx °C(°F) limit Use of cooling temperature BV AHU_Cool_Upper_Limit_set_xx_xxxxx False True upper limit Use of heating temperature BV AHU_Heat_Lower_Limit_set_xx_xxxxx False True lower limit...
Page 68
BACnet Gateway setting (Continued) EHS [Basic] EHS [Basic] Single EHS Unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 °C Room temperature EHS_RoomTemp_xx_xxxxxx Use when displayed temperature type °C Set temperature EHS_Temp_Set_xx_xxxxxx...
Page 69
EHS [Advanced] EHS [Advanced] Single EHS Unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Room temperature EHS_RoomTemp_xx_xxxxxx °C Use when displayed temperature type Set temperature EHS_Temp_Set_xx_xxxxxx °C is set to 'Room' .
Page 70
BACnet Gateway setting (Continued) Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Used when the room temperature is used Heating temperature lower limit EHS_Heat_Lower_LimitTemp_xx_xxxxx °C(°F) as the temperature display reference Cooling temperature upper limit, Used when the water out temperature is EHS_WO_Cool_Upper_LimitTemp_xx_xxxxx °C(°F)
Page 71
DVM CHILLER [Basic, Advanced] DVM CHILLER [Basic, Advanced] Single DVM CHILLER Unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Chilled Water Temperature MC_WaterTemp_xx_xxxxxx °C/F Set temperature AV MC_WaterTemp_Set_xx_xxxxxx °C/F Demand limit setting AV MC_Demand_Set_xx_xxxxxx...
Page 72
BACnet Gateway setting (Continued) Interface Module (Outdoor Unit) [Basic] Interface Module (Outdoor Unit) [Basic] Single Interface Module (Outdoor Unit) has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Outside temperature ODU_Outside_Temp_xx_xxxx °C...
Page 73
BACnet Gateway [Basic, Advanced] BACnet Gateway [Basic, Advanced] BACnet Gateway has following point list. Instance Control and Object Object Name Status Value Number Monitoring Type All device OFF ALL_OFF_xx Inactive : All devices Off 0: Normal, 8: Emergency stop, 105 : Tracking in progress, DMS2.5 Status DMS2.5_Status_xx 108 : Tracking failed...
Page 74
BACnet Gateway setting (Continued) Other Information Object setting when there is communication error Object setting when there is communication error If any communication error occurs between the air conditioner devices, the property will be set as below. 1. Reliability property will be set as COMMUNICATION_FAILURE. 2.
Specifications Items Description Exterior Size 240 X 255 X 64.8 mm ( Width X Length X Height ) Weight 1.48 Kg Source DC ADAPTOR Power INPUT Voltage 100-240V 50/60Hz 1.0A OUTPUT Voltage 12V 3A RS-485 5 Channels Ethernet 10/100Mbps 1 Port Inter- SD CARD Option (Purchase SD card separately)
The software included in this product contains open source software. You may obtain the complete corresponding source code for a period of three years after the last shipment of this product by contacting our support team via http://opensource.samsung.com (Please use the “Inquiry” menu.) It is also possible to obtain the complete corresponding source code in a physical medium such as a CD-ROM;...
Page 78
Correct Disposal of This Product (Waste Electrical & Electronic Equipment) (Applicable in countries with separate collection systems) This marking on the product, accessories or literature indicates that the product and its electronic accessories (e.g. charger, headset, USB cable) should not be disposed of with other household waste at the end of their working life.