BACnet Gateway setting (Continued)
AHU Kit [Advanced]
AHU Kit [Advanced]
Single AHU unit has following point list.
Instance
Number
1
Indoor Temperature
2
Set temperature
Setting lower temperature
3
limit
Setting upper temperature
4
limit
The power value of an indoor
5
unit after the basic date
The number of hours usage of
6
an indoor unit after the basic
date
7
Power value within period
The number of hours usage of
8
an indoor unit within period
9
Power On/Off
Applying lower temperature
10
limit setting
Applying upper temperature
11
limit setting
12
Filter sign status
13
Filter sign reset
14
Operation mode status
15
Operation mode limit status
16
Remote controller limit status
Integrated error code of both
17
indoor unit and outdoor unit
Discharge cooling set
* 18
temperature
Discharge heating set
* 19
temperature
* 20
Discharge current temperature
* 21
Humidification setting
* 22
Outdoor air intake setting
* 23
Outdoor cooling setting
* 24
Fan speed status
* 25
Set humidity status
* 26
Current humidity status
66
E-
Object
Object
Type
AI
AHU_RoomTemp_xx_xxxxxx
AV AHU_Temp_Set_xx_xxxxxx
AV AHU_Cool_LimitTemp_xx_xxxxxx
AV AHU_Heat_LimitTemp_xx_xxxxxx
AI
AHU_Baseline_kWh_xx_xxxxxx
AI
AHU_Baseline_Minute_xx_xxxxxx Minute
AI
AHU_Period_kWh_xx_xxxxxx
AI
AHU_Period_Minute_xx_xxxxxx
BV AHU_Power_xx_xxxxxx
BV AHU_Cool_Limit_set_xx_xxxxxx
BV AHU_Heat_Limit_set_xx_xxxxxx
BI
AHU_FilterSign_xx_xxxxxx
BO AHU_FilterSign_Reset_xx_xxxxxx
MV AHU_Operation_Mode_xx_xxxxxx Auto Cool
MV AHU_Mode_Limit_xx_xxxxxx
MV AHU_Remocon_Limit_xx_xxxxxx
AI
AHU_Error_Code_xx_xxxxxx
AV AHU_DisCoolSetTemp_xx_xxxxxx
AV AHU_DisHeatSetTemp_xx_xxxxxx
AI
AHU_Dis_CurrentTemp_xx_xxxxxx
BV AHU_Humidification_xx_xxxxxx
BV AHU_OAIntake_xx_xxxxxx
BV AHU_OutdoorCool_xx_xxxxxx
MV
AHU_FanSpeed_xx_xxxxxx
MV AHU_SetHumidity_xx_xxxxxx
MI AHU_CurrentHumidity_xx_xxxxxx
Unit
Object Name
Inactive Active
Text-1 Text-2
°C
°C
°C
°C
kWh
kWh
Minute
Off
False
False
False
False
No
Limit
Enable
RC
Refer to list of error code
°C
°C
°C
Off
Off
Off
Low
Low
Low
Status value
Text-3 Text-4 Text-5
On
True
True
True
True
Heat
Fan Dry
Cool
Heat
Only
Only
Disable
Conditional
RC
RC
On
On
On
Mid
High
Mid
High
Mid
High