Samsung AM AN4PKH Series Installation Manual
Samsung AM AN4PKH Series Installation Manual

Samsung AM AN4PKH Series Installation Manual

Hide thumbs Also See for AM AN4PKH Series:

Advertisement

Quick Links

Air conditioner
Installation manual
AM***AN4PKH
• Thank you for purchasing this Samsung air conditioner.
• Before operating this unit, please read this manual carefully and retain it for future reference.

Advertisement

Table of Contents
loading

Summary of Contents for Samsung AM AN4PKH Series

  • Page 1 Air conditioner Installation manual AM***AN4PKH • Thank you for purchasing this Samsung air conditioner. • Before operating this unit, please read this manual carefully and retain it for future reference.
  • Page 2: Table Of Contents

    Contents Safety Information Safety Information Installation Procedure Installation Procedure Step 1 Checking and preparing accessories Step 2 Choosing the installation location Step 3 Optional: Insulating the body of the indoor unit Step 4 Installing the indoor unit Step 5 Purging inert gas from the indoor unit Step 6 Cutting and flaring the pipes Step 7 Connecting the assembly pipes to the refrigerant pipes Step 8 Performing the gas leak test...
  • Page 3: Safety Information

    • This manual explains how to install an indoor unit with a IMPORTANT: When installing the unit, always remember split system with two SAMSUNG units. The use of other to connect first the refrigerant tubes, then the electrical types of units with different control systems may damage lines.
  • Page 4 Safety Information Safety Information • After completing the installation, always carry out a • Devices disconnected from the power supply should be functional test and provide the instructions on how to completely disconnected in the condition of overvoltage category. operate the air conditioner to the user. •...
  • Page 5: Installation Procedure

    Installation Procedure Step 1 Checking and preparing Step 2 Choosing the installation accessories location The following accessories are supplied with the indoor unit. The type and quantity may differ, depending on the Installation location requirements specifications. • There must be no obstacles near the air inlet and outlet.
  • Page 6 Installation Procedure (Unit: mm) 890~910 (Celling opening) 735 (Space of suspension bolts) The sub duct hole is not applicable to the Wind-Free models. Model AM028AN4PKH* AM036AN4PKH* AM045AN4PKH* AM056AN4PKH* AM071AN4PKH* AM090AN4PKH* AM112AN4PKH* AM128AN4PKH* AM140AN4PKH* Chassis Small Medium Large dimension mm 840 X 840 X 204 840 X 840 X 204 840 X 840 X 204 840 X 840 X 204 840 X 840 X 204 840 X 840 X 246 840 X 840 X 288 (W ×...
  • Page 7: Step 3 Optional: Insulating The Body Of The Indoor Unit

    Spacing requirements 1500 mm or more 17 mm 2500 mm or more 20 mm Obstruction Step 3 Optional: Insulating the body of the indoor unit (Unit: mm) If you install a cassette type indoor unit on the ceiling when AM028AN4PKH temperature is over 27°C and humidity is over 80%, you AM036AN4PKH AM090AN4PKH...
  • Page 8: Step 4 Installing The Indoor Unit

    Installation Procedure Step 4 Installing the indoor unit CAUTION When deciding on the location of the air conditioner the • Make sure that the ceiling is strong enough to support following restrictions must be taken into account. the weight of the indoor unit. Before hanging the unit, test the strength of each attached suspension bolt.
  • Page 9: Step 5 Purging Inert Gas From The Indoor Unit

    7 Adjust the unit to the appropriate position, taking into Step 6 Cutting and flaring the pipes account the installation area for the front panel. 1 Make sure that you have the required tools available: • Place the pattern sheet on the indoor unit. pipe cutter, reamer, flaring tool, and pipe holder.
  • Page 10: Step 7 Connecting The Assembly Pipes To The Refrigerant Pipes

    Installation Procedure 5 Check that the flaring is correct, referring to the Outer Diameter (mm) Torque (N•m) illustrations below for examples of incorrect flaring. Ø6.35 14 to 18 Ø9.52 34 to 42 Ø12.70 49 to 61 Ø15.88 68 to 82 Ø19.05 100 to 120 (1 N•m=10 kgf•cm)
  • Page 11: Step 8 Performing The Gas Leak Test

    Step 8 Performing the gas leak test 2 Wind insulating tape around the pipes and drain hose avoiding compressing the insulation too much. To identify potential gas leaks on the indoor unit, inspect the connection area of each refrigerant pipe using a leak Insulation cover pipe detector for R-410A.
  • Page 12: Step 10 Installing The Drain Hose And Drain Pipe

    Installation Procedure 5 Select the insulation of the refrigerant pipe. • Refrigerant pipe before EEV kit and MCU or without • Insulate the gas side and liquid side pipe, noting EEV kit and MCU the insulation thickness that must differ according –...
  • Page 13 • Do not apply force to the piping on the unit side when PVC Tube Joint + connecting the drain hose. The hose should not be Drain hose VP25 (OD: 32 mm, ID: 25 mm) allowed to hang loose from its connection to the unit. Fasten the hose to a wall, frame or other support as close to the unit as possible.
  • Page 14: Step 11 Performing The Drainage Test

    Installation Procedure Hanger 1~1.5m Main air vent Individual air vent 200 mm or more 300 to 550 mm Centralized horizontal drainpipe Main drainpipe (more than 1/100 slope) • If 3 or more units are installed, install the main air vent CAUTION at the front of the farthest indoor unit from the main drain pipe.
  • Page 15: Step 12 Connecting The Power And Communication Cables

    • Tighten the electric wires with a proper tool within the CAUTION torque limit to connect and fix them firmly, and then organize the wires to prevent outside pressure being • When the float switch is not detected due to exerted on the covers and other parts.
  • Page 16 Installation Procedure Outdoor Unit Wired Remote Control 220~240V~ MCCB EEV kit Indoor Unit 1 Indoor Unit 2 Indoor Unit 3 Indoor Unit 4 Indoor Unit 5 Indoor Unit 6 Selecting the crimping terminal lug 1 Select the crimping terminal lug based on the norminal dimension of the power cable. 2 Cover the connection part of the power cable and crimping terminal lug to insulate it.
  • Page 17 Specifications of the terminal blocks Rated currents Model Rating current(A) (Unit: mm) AM028AN4PKH* 0.25 AC power: M4 screw Communication: M3.5 screw AM036AN4PKH* 0.27 AM045AN4PKH* 0.30 AM056AN4PKH* 0.32 AM071AN4PKH* 0.35 AM090AN4PKH* 0.45 AM112AN4PKH* 0.60 Power supply MCCB (single phase) AM128AN4PKH* 0.75 Min : 198V XA, 30 mA AM140AN4PKH*...
  • Page 18: Step 13 Optional: Extending The Power Cable

    Installation Procedure Example of Installation Total power cable length L = 100(m), Initial pull-in current = 10[A], Running current of each units = 1[A], Total 10 indoor units were installed 10 [A] 9 [A] 1 [A] MCCB+ELB ELCB Indoor unit 1 Indoor unit 2 Indoor unit 10 0[m]...
  • Page 19 2 As shown in the figure, peel off the shields from the 4 Using a crimping tool, compress the two points and rubber and wire of the power cable. flip it over and compress another two points in the same location. •...
  • Page 20: Step 14 Setting The Indoor Unit Addresses And The Installation Options

    Installation Procedure CAUTION NOTE • The remote control display and buttons may vary • Make sure that the connection parts are not exposed depending on the model. to outside. 1 Enter the mode for setting the options: • Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials a Remove the batteries from the remote control, that have the same level of withstand voltage with...
  • Page 21 Take the steps presented in the following table: Steps Remote control display 1 Set the SEG2 and SEG3 values: a Set the SEG2 value by pressing the (Low Fan) button repeatedly until the value you want to set appears on the remote control display. SEG2 b Set the SEG3 value by pressing the (High Fan) button repeatedly until the...
  • Page 22 Installation Procedure Steps Remote control display 6 Press the (Mode) button. Fan and On appear on the remote control display. 7 Set the SEG9 and SEG10 values: a Set the SEG9 value by pressing the (Low Fan) button repeatedly until the value you want to set appears on the remote control display.
  • Page 23 Steps Remote control display 11 Set the SEG14 and SEG15 values: a Set the SEG14 value by pressing the (Low Fan) button repeatedly until the value you want to set appears on the remote control display. SEG14 b Set the SEG15 value by pressing the (High Fan) button repeatedly until the value you want to set appears on the remote control display.
  • Page 24 Installation Procedure Steps Remote control display 16 Press the (Mode) button. Fan and Off appear on the remote control display. 17 Set the SEG21 and SEG22 values: a Set the SEG21 value by pressing the (Low Fan) button repeatedly until the value you want to set appears on the remote control display.
  • Page 25 3 Check whether the option values that you have set are correct by pressing the (Mode) button repeatedly [SEG2, SEG3] [SEG4, SEG5] [SEG6, SEG8] [SEG9, SEG10] [SEG11, SEG12] [SEG14, SEG15] [SEG16, SEG17] [SEG18, SEG20] [SEG21, SEG22] [SEG23, SEG24] 4 Save the option values into the indoor unit: Point the remote control to the remote control sensor on the indoor unit and then press the (Power) button on the remote control twice.
  • Page 26 Installation Procedure Setting the indoor unit addresses (MAIN/RMC/ 3 Set an address (MAIN/RMC/MCU port) for each indoor unit using the remote control, according to your air MCU) conditioning system plan. 1 Make sure that the power is supplied to the indoor •...
  • Page 27 Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Setting MCU PORT Function Page 10-digit of MCU address 1-digit of MCU MCU PORT address address Indication Details Indication Details Indication Details Indication Details Indication Details No MCU PORT Indication and PORT details MCU PORT 10-digit 1-digit...
  • Page 28 Installation Procedure Installation options for the 02 series SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Use of external room temperature FAN RPM Evaporator Drying sensor / Minimizing Use of central control compensation fan operation when thermostat is off SEG7 SEG8 SEG9 SEG10 SEG11 SEG12...
  • Page 29 02 series installation option (Detailed) Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Use of external room temperature sensor / Use of central Explanation PAGE MODE Evaporator Drying Minimizing fan operation when thermostat FAN RPM compensation control is off Details Use of...
  • Page 30 Installation Procedure Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Setting the output of external control / External Explanation PAGE Use of external control heater signal / Cooling S-Plasma ion Buzzer control Hours of filter usage operation signal / Free Cooling control signal Indication Details Indication Details Indication Details...
  • Page 31 (*3) 1: Fan is turned on continually when the hot water heater is turned on, 3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as cool mode.
  • Page 32 Installation Procedure 05 series installation option (Detailed) Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Use of Auto Change (When setting SEG3) Over for HR only in (When setting SEG3) (When setting SEG3) Standard for mode Explanation PAGE MODE Auto mode / Use of...
  • Page 33 Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation Control variables when using hot water / external heater (*4) Details Indication Details Indication Set temp. for heater Delay time for heater On On/Off At the same time as No delay thermo on At the same time as 10 minutes thermo on...
  • Page 34 Installation Procedure (*1) Height difference : The difference of the height between the corresponding indoor unit and the indoor unit installed at the lowest place. For example, When the indoor unit is installed 40m higher than the indoor unit installed at the lowest place, select the option “1”.
  • Page 35 Changing the addresses and options individually When you want to change the value of a specific option, refer to the following table and follow the steps in Common steps for setting the addresses and options on page 20. Option SEG1 SEG2 SEG3 SEG4...
  • Page 36 Installation Procedure Performing final check and trial operation To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly. 1 Check the followings. • Strength of the installation site • Tightness of pipe connection to detect a gas leak •...
  • Page 37: Appendix

    Troubleshooting LED Display Operation Defrost Timer Filter Abnormal condition Error code Error on indoor temperature sensor (Short or Open) E121 1. Error on Eva-in sensor (Short or Open) E122 2. Error on Eva-out sensor (Short or Open) E123 3. Discharge sensor error (Short or Open) E126 Indoor fan error E154...
  • Page 38 Troubleshooting LED Display Operation Defrost Timer Filter Abnormal condition Error code 10. Low pressure sensor is detached E306 11. Outdoor unit Compression ratio error E428 12. Outdoor sump down_1 prevetion control E413 13. Compressor down due to low pressure sensor prevention E410 control_1 14.
  • Page 39 Memo English...
  • Page 40 DB68-09967A-00...