Indoor unit installation

AA
1. Determine the position of the pipe and drain hose hole as seen in the
picture and drill the hole with an inner diameter of 65mm so that it slants
slightly downwards.
Since the diagram is made of paper, it may shrink or stretch slightly
due to temperature or humidity. For this reason, before drilling the
holes maintain the correct dimensions between the markings.
2. Insert bolt anchors, use existing ceiling supports or construct a suitable
support as shown in figure.
3. Install the suspension bolts depending on the ceiling type.
indoor unit. Before hanging the unit,
test the strength of each attached suspension bolt.
plate
4. Screw eight nuts to the suspension bolts making space for hanging the
indoor unit.
access for maintenance or repairs to the drainage pipe connection,
5. Hang the indoor unit to the suspension bolts between two nuts.
suspending the unit. If the ceiling is already constructed, lay the
piping into position for connection to the unit before placing the unit
inside the ceiling.
6. Screw the nuts to suspend the unit. Cut a pad stopper and place it on the
bracket at this time.
7. Adjust the unit to the appropriate position considering the installation area
for the front panel.
of dimensions.
panel.
between indoor pipe and hanger
Concrete
Hole in anchor
Hole in plug
Ceiling support
Pad stopper
Bracket
20mm
Indoor unit
17mm
Dimensions
Insert
Ceiling
7