Contents 11. Precautions 1-1 Installing the air conditioner 1-2 Power supply and circuit breaker 1-3 During operation 1-4 Disposing of the unit 1-5 Others 12. Product Spe 2-1 The Feature of Product 2-2 Product S cations 2-3 The Comparative of Product 2-14 2-4 Accessory and Option Speci cations 2-22...
An all pole disconnection from the power supply must be incorporated in the fixed wiring with a contact opening of >3mm. Do not extend an electric cord to the air conditioner. The air conditioner must be plugged in after you complete the installation. No Tapping and No Extension Cords Samsung Electronics...
- Release the valve caps on High and Low pressure side. - Use L wrench to close the valve on the high pressure side. - Approximately 2 minutes after, close the valve on the low pressure side. - Stop operation of the air conditioner.- Disconnect the pipes. Samsung Electronics...
■ Space saving & Environmental Friendly ■ Reliability ■ Smart & Low Noise outdoor units in any condition Double layered felt structure absorbs noise by two times and felt is also covering top of the compressor to reduce the noise even more. Samsung Electronics...
Page 6
2 5 . 2 5 . 2 5 . 2 5 . Type Cross Fan Cross Fan Cross Fan Cross Fan Cross Fan Blower Type Motor Rated Output Heat Exchanger 2ROWx14STEP 2ROWx14STEP 2ROWx14STEP 2ROWx14STEP 2ROWx14STEP Refrigerant Control Device Samsung Electronics...
Page 7
2 5 . 2 5 . 2 5 . 2 5 . Type Cross Fan Cross Fan Cross Fan Cross Fan Cross Fan Blower Type Motor Rated Output Heat Exchanger 2ROWx14STEP 2ROWx10STEP 2ROWx10STEP 2ROWx14STEP 2ROWx14STEP Refrigerant Control Device Samsung Electronics...
Page 8
8 8 . 2 5 . 2 5 . 2 5 . Type Cross Fan Cross Fan Cross Fan Cross Fan Cross Fan Blower Type Motor Rated Output Heat Exchanger 2ROWx10STEP 2ROWx10STEP 2ROWx14STEP 2ROWx14STEP 2ROWx14STEP Refrigerant Control Device Samsung Electronics...
Page 9
8 8 . 2 5 . 2 5 . 2 5 . Type Cross Fan Cross Fan Cross Fan Cross Fan Cross Fan Blower Type Motor Rated Output Heat Exchanger 2ROWx10STEP 2ROWx10STEP 2ROWx10STEP 2ROWx10STEP 2ROWx10STEP Refrigerant Control Device Samsung Electronics...
Page 10
Outer Dimension Net Size W*H*D(mm) 1065*298*243 1065*298*243 1065*301*294 1065*301*294 Refrigerant Pipe Size 12.70 15.88 12.70 15.88 Type Cross Fan Cross Fan Cross Fan Cross Fan Blower Type Motor Rated Output Heat Exchanger 2ROWx10STEP 2ROWx10STEP 2ROWx10STEP 2ROWx10STEP Refrigerant Control Device Samsung Electronics...
Page 15
Protection Device Type r e l l r e l l r e l l Blower Size Fan Motor & Blower Rated Output Motor Capacitor uFx VAC Heat Exchanger 2Row×24Step 2Row×24Step 2Row×28Step Refrigerant Control Device Charging Refrigerant (R410A) Samsung Electronics 2-11...
Page 16
Protection Device Type r e l r e l r e l Blower Size Fan Motor & Blower Rated Output Motor Capacitor uFx VAC Heat Exchanger 2Row×36Step 2Row×36Step 2Row×36Step Refrigerant Control Device Charging Refrigerant (R410A) 2-12 Samsung Electronics...
Page 17
BLDC Permanent Magnetic Motor Type Compressor Type Lubricant Oil y t i 1200 Protection Device Type r e l Blower Size Fan Motor & Blower Rated Output Motor Capacitor uFx VAC Heat Exchanger 2Row×46Step Refrigerant Control Device Charging Refrigerant (R410A) Samsung Electronics 2-13...
Page 18
2-3 The Comparative Spe ations of Product ITEM Indoor Unit Design Outdoor Unit AR07KSPDBWKNEU AR09/12KSWSBWKNET 9.5Kg AR07KSPDBWKNEU AR09/12KSWSBWKNET 9.5Kg Indoor Unit Net Weight MH026/035FSEA NJ026/035LHXEA 10.5Kg AJN016/020/026/035NDEHA/EU 11.4Kg AJN052NDEHA/EU 13.4Kg Outdoor Unit 2-14 Samsung Electronics...
Page 19
41/42dB MH052FUEA 37dB MH026/035/FJEA 28/39dB Outdoor AJ040MCJ2EH/EU AJ050MCJ2EH/EU 55 dB 56 dB Unit Free Joint Multi (Varibale Indoor Unit) Free Joint Multi (Varibale Indoor Unit) BLDC INVERTER COMPRESSOR BLDC INVERTER COMPRESSOR UG9AJ1090FJR UG9TK3150FE4 The Feature of Product Samsung Electronics 2-15...
Page 21
MH026/035FSEA NJ026/035LHXEA 36/38 dB 38/39dB AJN016/020/026/035NDEHA/EU 38/39dB AJN016/020/026/035NDEHA/EU AJN052NDEHA/EU 41/42dB 41/42dB MH052FUEA 37dB MH052FUEA 37dB MH026/035/FJEA 28/39dB MH026/035/052FJEA 28/39/41dB Outdoor AJ052MCJ3EH/EU 56 dB AJ068MCJ3EH/EU 57 dB Unit ) t i ) t i The Feature of Product Samsung Electronics 2-17...
Page 23
MH026/035FSEA NJ026/035LHXEA 36/38 dB AJN016/020/026/035NDEHA/EU 38/39dB AJN016/020/026/035NDEHA/EU 38/39dB AJN052NDEHA/EU 41/42dB AJN052NDEHA/EU 41/42dB MH052FUEA 37dB MH052FUEA 37dB MH026/035/052FJEA 28/39/41dB MH026/035/052FJEA 28/39/41dB Outdoor AJ070MCJ4EH/EU 57 dB AJ080MCJ4EH/EU 57 dB Unit ) t i ) t i The Feature of Product Samsung Electronics 2-19...
Page 24
The Comparative Spe ations of Product(cont.) ITEM Indoor Unit Design Outdoor Unit AR07KSPDBWKNEU AR09/12KSWSBWKNET 9.5Kg AR07MSFPEWQNEU AR07MSFHBWKNEU 8.2Kg Indoor Unit Net Weight AR09/12MSFPEWQN AR09/12MSFHBWKN 8.0Kg MH026/035FSEA NJ026/035LHXEA 10.5Kg AJN016/020/026/035NDEHA/EU 11.4Kg AJN052NDEHA/EU 13.4Kg Outdoor Unit 2-20 Samsung Electronics...
Page 25
Unit Noise AR09/12MSFPEWQN AR09/12MSFHBWKN 42 dB AR18MSFPEWQNEU 46dB AR18MSFHBWKNEU 46dB AR18MSPDBWKNEU 46dB MH026/035FSEA NJ026/035LHXEA 36/38 dB 38/39dB AJN016/020/026/035NDEHA/EU AJN052NDEHA/EU 41/42dB MH052FUEA 37dB MH026/035/052FJEA 28/39/41dB Outdoor AJ100MCJ5EH/EU 57 dB Unit ) t i UG8T300FUBJU The Feature of Product Samsung Electronics 2-21...
Page 26
2-4 Accessory and Option Spe 2-4-1 Indoor Unit Accessories 2-22 Samsung Electronics...
(Use +Screw Driver.) 3) Loosen each 7 screws(CCW)on cabi front. (Use +Screw Driver.) 4) Loosen 2 screw(CCW)fixed to assemble Plate Control Out with Cabinet-Side RH. (Use +Screw Driver.) 5) Loosen 2 fixing screws(CCW)on Cabinet-Side RH. (Use +Screw Driver.) Samsung Electronics...
Page 39
Parts Procedure Remark 6) Loosen 4 screws(CCW)fixed to assemble Bracket Valve with Cabinet-Side RH. (Use +Screw Driver.) 7) Loosen 3 fixing screws(CCW)of Cabinet Side LF. (Use +Screw Driver.) Samsung Electronics...
Page 40
Ass’y Ass'y Control Out. Control Out 2) Detach several connectors from the PCB of Ass'y Control Out. 3) Detach 2 Connect Wires from Reactor. 4) Loosen 1 screw(CCW)fixed to assemble Ass'y Control Out with Partition. (Use +Screw Driver.) Samsung Electronics...
Page 41
2) Detach the Terminal Cover and detach the Connect Comp Wire from Compressor. 3) Disassemble the Felt Comp Sound. 4) Loosen the 3 bolts(CCW)at the bottom of Compressor like the picture on the right side. (Use Monkey Spanner.) Samsung Electronics...
Page 42
Cover-Valve. (Use +Screw Driver.) 2) Loosen each 9 screws(CCW)on cabi top. (Use +Screw Driver.) 3) Loosen 2 screw(CCW)fixed to assemble Plate Control Out with Cabinet-Side RH. (Use +Screw Driver.) 4) Loosen 10 fixing screws(CCW)on Cabinet-Side RH. (Use +Screw Driver.) Samsung Electronics...
Page 43
1) Detach the Motor Wire from the PCB of Ass’y Ass'y Control Out. Control Out 2) Detach the comp wire from the PCB of Ass'y Control Out. 3) Detach several connectors from the PCB of Ass'y Control Out. Samsung Electronics...
Page 44
2) Loosen the fixing nut and detach the Fan. Motor (Use +Screw Driver.) 3) Loosen 4 fixing bolts and detach the Motor. (Use +Screw Driver.) 4) Loosen 4 fixing bolts and detach the Bracket Motor. (Use +Screw Driver.) Samsung Electronics...
Page 45
2) Detach the Terminal Cover and detach the Connect Comp Wire from Compressor. 3) Disassemble the Felt Comp Sound. 4) Loosen the 3 bolts(CCW)at the bottom of Compressor like the picture on the right side. (Use Monkey Spanner.) Samsung Electronics...
Page 46
3) Loosen 2 fixing screws of the Ass'y Control Out. (Use +Screw Driver.) 4) Loosen 6 fixing screws and detach the Cabinet Upper. (Use +Screw Driver.) 5) Loosen 2 fixing screws, 7 bolts and detach the Cabinet Front. (Use +Screw Driver.) 3-10 Samsung Electronics...
Page 47
Parts Procedure Remark 6) Loosen 2 fixing screw and pull up the Control Box. (Use +Screw Driver.) 7) Pull the felt and detach it. 8) Detach the Terminal Cover and detach the comp lead wire. Samsung Electronics 3-11...
Page 48
2) Disassemble the Inlet and Outlet Pipe by & Compressor welding. 3) Loosen the fixing screw of the Heat Exchanger. (Use +Screw Driver.) 4) Detach the Heat Exchanger. 5) Loosen 3 nuts of the Compressor. (Use Monkey Spanner.) 6) Detach the Compressor. 3-12 Samsung Electronics...
4. Troubleshooting 4-1 Display Error and Check Method 4-1-1 Indoor unit AR** Samsung Electronics...
Page 58
Error of float switch Error of setting option switches for optional accessories EEPROM error EEPROM option error : On : Flickering : Off If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 59
Error of outdoor unit Detection of the float switch water. EEPROM error nent. EEPROM option error door machine models -.Check the wire connection Motion detect sensor error -. Check the MDS-KIT -.Check the indoor PBA Mixed operation error Samsung Electronics...
Page 60
Setting the outdoor unit capacity option error EEPROM error EEPROM option error MPI no feedback Error : On : Flickering : Off If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 61
: Flickering : Off If you turn off the air conditioner when the LED is flickering, the LED is also turned off. If you re-operate the air conditioner, it operates normally at first, then detect an error again. Samsung Electronics...
Page 62
Outdoor unit high discharge temperature - Safety control (Compressor stop) check pipe lenght, refrigerantleakage/charge u l i E462 Compressor trip by input current control mode (PFC over current) n i l / t r / t r / t r / t r . t i Samsung Electronics...
Page 63
If fails, the red LED of the A part turns on. - This work takes approximately 3 to 5 minutes. LED (RED, GRN / RED, GRN, YEL) 1) T e switch 1 of the DIP switch, and then turn on the outdoor unit. Reset 4-10 Samsung Electronics...
Push the button to set the display panel to ➡ ➡ Every time you push the button, the display panel reads ➡ ➡ . . . ➡ ➡ ➡ ➡ ➡ ➡ repeatedly. Samsung Electronics 4-11...
Page 65
If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. 4-12 Samsung Electronics...
Page 66
Push the button to set the display panel to Setting is not required if you must Every time you push the button, the display panel reads a value which has a default..repeatedly. Samsung Electronics 4-13...
Page 67
If all lamps of indoor unit are flickering, plug out, plug in power plug again and press the ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. 4-14 Samsung Electronics...
Page 68
Every time you push the button, the display panel reads ..repeatedly. Push the button to Push the button to set the display panel to Every time you push the button, the display panel reads ..repeatedly. Samsung Electronics 4-15...
Page 69
If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. 4-16 Samsung Electronics...
Page 72
2. Insert batteries and enter the option setting mode while pressing High Temp button and Low Temp button. Check if you have entered the option setting status. Step 2. The procedure of option setting After entering the option setting status, select the option as listed below. were used at the previous other remocons. Samsung Electronics 4-19...
Page 73
10. Setting Auto mode Press Mode button to be changed to AUTO mode in the OFF status. Press Low Fan button( ∨ Press High Fan button( ∧ Each time you press the button, will be selected in rotation. 4-20 Samsung Electronics...
Page 74
Step 5. Check operation 1. Reset the indoor unit by pressing the RESET button of indoor unit or outdoor unit. 2. Take the batteries out of the remote controller and insert them again and then press the operation button. Samsung Electronics 4-21...
Page 75
No RMC address Indication and Details RMC1 RMC2 RMC address setting mode Example) If you want to set as "MAIN : 3, CHANNEL : 1, RMC : B", assign option codes except SEG 1, 7 which are page options. 4-22 Samsung Electronics...
Page 76
Mixed operation Thermo Disuse Disuse 1000 Hour control 1/Use buzzer ON/OFF Mixed operation Control Indication control 1/Disuse of buzzer Control Details Operation 2000 Mixed operation control 2/Use Hour buzzer WINDOR Mixed operation ON/OFF control 2/Disuse of buzzer Samsung Electronics 4-23...
Page 77
Ex) When setting the 'buzzer control' into disuse status. Option The option The tens’ digit of The unit digit of The changed Explanation MODE mode you want value to change you will change you will change Indication 4-24 Samsung Electronics...
Page 79
020000 020000 S E G 31~36 100000 100000 100000 100000 100000 S E G 37~42 200000 200000 200000 200000 200000 S E G 43~48 300000 300000 300000 300000 300000 S E G 49~54 S E G 55~60 4-26 Samsung Electronics...
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables. Otherwise the air conditioner may not operate properly. When a problem occurs due to the contents illustrated in the table below it is a symptom not related to the malfunction of the air conditioner. Samsung Electronics 4-27...
Page 83
Display Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details No RMC address Indication and Details RMC1 RMC2 address setting mode You must set RMC address setting mode when using the centralized Control . 4-30 Samsung Electronics...
Page 93
4-6-2 Outdoor unit is not powered on – Initial diagnosis(1phase) Turn off the main power switch 4-40 Samsung Electronics...
Page 94
Caution! When you remove PBA, you have to check DC link Voltage. After Power off, DC link Voltage is so high! Measuring point Normal value Resistance R - S over the hundreds Samsung Electronics 4-41...
Page 95
4-6-4 Outdoor unit fan error 4-42 Samsung Electronics...
Page 97
4-6-6 IPM Over current error AJ040MCJ2EH/EU AJ050MCJ2EH/EU AJ052MCJ3EH/EU AJ068MCJ3EH/EU AJ070MCJ4EH/EU AJ080MCJ4EH/EU AJ100MCJ5EH/EU Turn off the power and reconnect the table. Turn off the power and correct or replace the temperature sensor location 4-44 Samsung Electronics...
Page 98
4-6-7 Checking Temperature sensor 4-6-7-1 Outdoor discharge/OLP temperature sensor error Samsung Electronics 4-45...
Page 100
11. When connected to an outdoor unit manufactured after June, 2011, a new option code is not needed. Samsung Electronics 4-47...
Page 101
#2 : N.C #1 : DC 5V #1 : DC 310V~340V #9 : GND #2 : GND #2,#3 : N.C #10 : DC 12V #3 : DC 12V #4 : DC 19V~27V #5 : AGND CN31 - DOWNLOAD DOWNLOAD Samsung Electronics...
Page 102
#1,4,5,6: Download Signal #1: EVA_TEMP #1: 12V Signal #1 : SPI Signal #2: GND #2 : VCC #2 : GND #3: GND #3 : DC 12V CN75 - SMPS IN CNS21-COMM #1 : Signal 1 #2 : Signal 2 Samsung Electronics...
Page 103
External Signal MAIN PCB Connection Samsung Electronics...
Page 104
CN41-Temp. sensor CN51-FLOAT S/W CN61, CN62-Slide Panel CN83- External Control #1:ROOM Temp. Sensor #1:GND #1:On/off Contact point input #1,#6:DC12V #2:GND #2:Float S/W #2~#5:Motor Control #2:GND #3:EVA IN Temp. sensor #7~#10:Not used #4:GND CN42-Temp. sensor #1:EVA OUT Temp. Sensor #2:GND Samsung Electronics...
Page 105
CN01 : Connect the Main PBA of the Indoor Unit #1~#5:Control Display LED #6:Not used connection #7:Receive signals from wireless remote controller Connector #8:GND #9:VCC (DC5V) Samsung Electronics...
Page 106
6:REMOCON signal out 5:EVA discharge 7,8:Not used 9:REMOCON_INT 10:GND 11:Vcc a l f 2:VENT_OUT 2-5: Louver control signal 3:SPI CONTROL 2:DRAOM_PUMP_OUT 7-10:Louver control signal (13) Human Sensor (14) External (15) External (16) COM1,COM2,V1,V2 3-F4: Com2 3:Com4_RXD 4:Human sensor reset 5:GND Samsung Electronics...
Page 107
Panel PCB ① CN01-DISPLAY #6 : Remocon signal out #9 : Remocon signal IN Samsung Electronics...
Page 108
#2~#5. Control SIGNAL #2~#5.Communication Signal #1. Communication Signal F1 #1.Communication Signal F1 #2. Communication Signal F2 #2.Communication Signal F2 CN20-MICOM Download2 CN10-MICOM Download1 > For Developer,Not for field >For Developer, Not for field > 7pin Downloader >10pin Downloader Samsung Electronics...
Page 109
EVA out Temperature Address Switch Heater Temperature Option Switch Wired Remote Controller Power(12V) Fan (Tap Control) Control Signal Ventilator Drain Pump Display Hot Coil Operating Check Signal Fan (SSR) HALL IC Trans In Download Main Power COM 1 Trans out Samsung Electronics...
Page 110
#5 : FAN RPM #6 : FAN FEEDBACK CN002 - POWER-L CN003 - EARTH CN150 - SMPS AC CN402 - COMP #1 : W #1 : L #1 : EARTH #1,#3 : AC220~240V #2 : V #3 : U 5-10 Samsung Electronics...
Page 111
#1 : DC310 #1-#9 : DOWNLOAD SIGNAL #2 : GND #2 : NC #14 : DOWNLOAD SIGNAL #3 : SIGNAL #3 : GND #18-#20 : DOWNLOAD SIGNAL #4 : DC15V #10 : VCC #5,#6 : SIGNAL #17 l GND Samsung Electronics 5-11...
Page 112
#3 : GND #4 : VCC #3 : VCC #5 : 12V #4 - #7 : SIGNAL #6 : SIGNAL CN303 - 485 COMM CN103 - EARTH OWNLOAD #1 : SIGNAL #1 : EARTH #2 : SIGNAL 5-12 Samsung Electronics...
Page 114
AJ100MCJ5EH EMI PCB ② ③ ① L1 - AC POWER L phase N1 - AC POWER N phase CN01 - AC POWER #L1 : BRN #N1 : SKY - BLU #1 - #3 : AC 220~240V 5-14 Samsung Electronics...
7. Schematic Diagram 7-1 INDOOR UNIT AR**SP**/AR**SW** SAMSUNG PROPRIETARY THIS DOCUMENT CONTAINS CONFIDENTIAL, PROPRIETARY INFORMATION THAT IS SAMSUNG ELECTRONICS CO'S PROPERTY. DO NOT DISCLOSE TO OR DUPLICATE THIS DOCUMENT EEPROM EXTERIOR_OPTION WIFI BLOCK STEP MOTOR BLOCK C534 100n GRILLE1 GRILLE2...
Page 133
330 J 1/16W R463 PIPE_OUT_2 MAIN 1/16W R464 MM74HC86M PIPE_OUT_3 330 J 1/16W R465 SMW200-H05G PIPE_OUT_4 1/16W WB25B-008-132 CN331 C454 C455 C456 C457 CE330 100n 100n 100n 100n 100u SC52130-024A(BL) This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 134
Output Output micom receive the input signal CN003 YW396-02V CN204 DA38-362M INRUSH DRED HIGH Micom Input Output Input Input SWITCH GP881205 Q151 D002 CN151 RY_MAIN OPTION 1N4148WS 150mA 75V This Document can not be used without Samsung's authorization. Samsung Electronics...
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice. Samsung Electronics...
2. Make sure that you put the remote control unit in an area not exposed to direct sunlight, and where there is no source of heat. 3. Make sure thatyou use the remote control unit in an area awa y from TVs, audio units, cordlessphones, fluorescent li g htin g Samsung Electronics...
You should purge the air in the indoor unit and in the pipe. Refrigerant for air purging is not charged in the outdoor unit. to the packed valve having a service port . Valve Valve stem Model Name Service port counter clockwise. Valve stem Service port Samsung Electronics...
Page 142
8-3 Refrigerant Re ll Samsung Electronics...
INVERTER HP INVERTER CO BEST RAC RAC Maldive 1ST MODEL Project Color Name Division Component Sinkeolreo code DA White Deco PM Gray Deco Maldives Midnight Blue Deco Urban silver Deco Cipria Gold Deco UNITED KINGDOM UNITED KINGDOM (XEU) Samsung Electronics...
Page 147
Derivation model (NASA) PREMIUM (except EHS) DELUXE <- Basic STANDARD Product Type Code Type CAC (USD) ASD(Air Side Unit) PAK (Packaged System) ※ "/" can be removed from the buyer card if there are not enough digits. 8-10 Samsung Electronics...
Heat exchanger; A device, used to transfer heat from a fluid on one side of a barrier to a fluid ASS’Y EVAP/ASS’Y COND on the other side without bringing the fluids into direct contact. (Full name : assemble evaporator / assemble condenser) 8-16 Samsung Electronics...
It occurs when the drain pump is plugged out or it is out of order. Check the power of the drain pump and the position of the drain hose, and when the pump is faulty, contact the drain pump manufacturer. Samsung Electronics do not manufacture drain pumps. So, we are not able to correct the drain pump problems.
Page 154
Set up a sun blind over the outdoor unit and clear the neighboring obstacles from the outdoor unit to provide good ventilation. When it goes off frequently during a heat wave, it would prevent the turn-off and increase the cooling capacity cleaning the outdoor unit or spraying some water to the heat exchanger. 8-18 Samsung Electronics...
Page 155
There is a cost table. But, our service engineer needs to visit to total up the cost correctly. When you move in, make sure to contact Samsung Electronics Service Center or Authorized Service Agent in advance to streamline the process.
But generally the value of fresh indoor temperature is that below 0.2(m/s) of indoor air circulation, the temperature is 21~28 C when the wall temperature is the same as the indoor's and relative humidity is 30~31% in summer, the winter temperature is 20~24 C and relative humidity is 30~60% in winter. 8-20 Samsung Electronics...