Summary of Contents for Samsung SINGLE AF50MS3MCEENHC
Page 1
SINGLE Technical Data Book SINGLE PAC for IRAN (R410A, 50Hz, HP/CO) Model : AF50MS3MCEENHC, AF50MV3MCEENHC (Indoor Unit) AF50MS3MCEEXHC, AF50MV3MCEEXHC (Outdoor Unit)
Page 2
History Version Modification Date Remark Ver.1.0 Release Single PAC TDB for Iran ‘17. 02. 07 Ver.1.1 Revised Compressor Oil type of outdoor unit ‘18. 10. 30...
Page 3
Nomenclature Indoor Unit Model Name Buyer (1) Classification (5) Feature 1Ф, 220V FAC/PAC 3Ф, 220V 3Ф, 380V 3Ф, 380V+ Virus doctor (2) Capacity (6) Series X 1000 Btu/h Mirage (3) Version (7) Color 2014 Santorini beige 2015 2016 2017 (8) Mode Indoor unit Outdoor unit (4) Product Type...
Page 4
Nomenclature Outdoor Unit Model Name Buyer (1) Classification (5) Feature 1Ф, 220V FAC/PAC 3Ф, 220V 3Ф, 380V 3Ф, 380V+ Virus doctor (2) Capacity (6) Series X 1000 Btu/h Mirage (3) Version (7) Color 2014 Santorini beige 2015 2016 2017 (8) Mode Indoor unit Outdoor unit (4) Product Type...
Page 5
Features & Benefits Long Distance Air Flow Full HD Filter (MAX60%) The full high density filter collects up t0 60% of dust and As a result of the horizontal and vertical flaps that move allergy causing bacteria independently of one another, a greater diversity of air- flow is available depending upon your needs: direct air Auto shutter flow in one direction, long-range cooling, broad left-right...
2. Specification Type PAC( for Iran) PAC( for Iran) Indoor Unit AF50MV3MCEENHC AF50MS3MCEENHC Model Name Outdoor Unit AF50MV3MCEEXHC AF50MS3MCEEXHC Mode Cooling Only HEAT PUMP Performance Capacity Cooling 4.2 / 13.4 / 16.7 4.2 / 13.4 / 16.7 (Min/Std/Max) Btu/h 14,300 / 45,700 / 57,000 14,300 / 45,700 / 57,000 US RT 1.19 / 3.81 / 4.75...
Page 9
2. Specification Type PAC( for Iran) PAC( for Iran) Indoor Unit AF50MV3MCEENHC AF50MS3MCEENHC Model Name Outdoor Unit AF50MV3MCEEXHC AF50MS3MCEEXHC Casing Material Drain Pump Drain Pump Max. lifting Height / Displacement mm / Liter/h Additional Drain Pump External Model Accessories Indoor Unit Internal Model Max.
7. Center of Gravity Indoor unit AF50MS3MCEENHC, AF50MV3MCEENHC Units : mm [inches]...
Page 18
7. Center of Gravity Outdoor unit AF50MS3MCEEXHC, AF50MV3MCEEXHC Units : mm [inches] [8-1/4] 620[24-3/8] 328[12-7/8] Hold location of foundation bolt Hold location of foundation bolt...
8. Electrical Wiring Diagram Indoor unit ASSY PCB MAIN Print circuit board(MAIN) M-BLDC BLDC Motor EVA-IN TEMP Thermistor EVAPORATE ASSY PCB POWER Print circuit board(POWER) U/D STEP MOTOR Up/Down louver DC Motor ROOM-TEMP Thermistor AMBIENT ASSY PCB DISPLAY Print circuit board(DISPLAY) L/R STEP MOTOR Left/Right louver DC Motor NOTE...
10. Temperature and air flow distribution AF50MS3MCEENHC (1) Cooling air velocity distribution (2) Cooling temperature distribution (3) Heating Air Velocity distribution (4) Heating temperature distribution...
Page 24
10. Temperature and air flow distribution AF50MV3MCEENHC (1) Cooling air velocity distribution (2) Cooling temperature distribution...
12. Piping Diagram AF50MV3MCEENHC+AF50MV3MCEEXHC AJ026MCJ3EC/SP OUTDOOR UNIT INDOOR UNIT Thermistor- Heat Exchanger (T_II) Service Valve- Heat Exchanger - Gas Pipe Indoor unit (SV_G) (HX_ID) Thermistor- Indoor Room (T_IR) Outdoor Fan Motor1 (OFM1) Outdoor Fan Motor2 (OFM2) Electronic Expansion Valve- Main Indoor Fan Motor (E_M) (IFM)
Page 27
12. Piping Diagram AF50MS3MCEENHC+AF50MS3MCEEXHC AJ026MCJ3EC/SP OUTDOOR UNIT INDOOR UNIT Thermistor- Heat Exchanger (T_II) Service Valve- Heat Exchanger - Gas Pipe Indoor unit (SV_G) (HX_ID) Thermistor- Indoor Room (T_IR) Outdoor Fan Motor1 (OFM1) Outdoor Fan Motor2 (OFM2) Electronic Expansion Valve- Main Indoor Fan Motor (E_M) (IFM)
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Selection of installation place Indoor unit f Install the unit at a place close to the wall facing the outside as it is necessary to perform piping connection with the outdoor unit. - It is effective to install the unit at a window side to ensure uniform distribution of indoor temperature. f Install the unit at a place where there is no obstacle against the wind around the air intake and air outlet.
Page 29
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Single installation (Unit : mm) ❋ When the air outlet is opposite the wall ❋ When the air outlet is towards the wall 2000 or more 300 or more 600 or more ❋ When 3 sides of the outdoor unit are blocked by the ❋...
Page 30
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC When installing more than 1 outdoor unit (Unit : mm) ❋ When the air outlet is towards the wall 300 or more 600 or more 600 or more 600 or more ❋ When 3 sides of the outdoor unit are blocked by the wall 300 or more 300 or more 600 or more...
Page 31
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC • Should adopt bar type louver. Don’t use a type of rain resistance louver. WARNING [Bar type louver] [Rain resistance louver] • Louver specifications. - Angle criteria : less than 20˚ - Opening ratio criteria : greater than 80% Outdoor unit base mount and anchor bolt position Fix the outdoor unit with anchor bolts.
Page 32
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Preparing the installation Selecting appropriate location for installation Decide the installation location based on the following condition and obtain the user’s approval. f Avoid a place that may disturb your neighbor. Noise may occur from the outdoor unit and the discharged air may run into the neighborhood.
Page 33
If you install several outdoor units at the same place, observe the space for ventilation and free airflow. f If the space for ventilation is insufficient, the air conditioner may not generate performance designed. Keep in mind that SAMSUNG logo is located on the front side of outdoor unit.
Page 34
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Installing the air conditioner Refrigerant pipe work Insulating the pipes f Make sure to insulated the refrigerant pipes with an insulation tape. If the Pipe insulator pipe is not insulated, condensate may form and drop into the indoor. Vinyl tape Indoor/outdoor unit f Wind the refrigerant pipes and the drain hose with vinyl tapes.
Page 35
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Refrigerant piping work 1. Cut the pipe with a pipe cutter ensuring that the cut edge remains flat and then remove all the burrs. 2. Make sure that the flared pipe doesn’t have uneven thickness, damaged and cracked surfaces, or any other defects. 3.
Page 36
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Electrical work Wiring work must be done by the certified expert. f Wiring work should be performed in accordance with related laws such as technical specification on electric installation or installation guide. f You must install exclusive power supply. - If you use multi-outlet, there is a risk of electric shock or fire.
Page 37
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC • Please use rated wires or products (with heat resistance over 105 °C) of all the wires and the switches or fuses in the cabinet panel. (Retailer and installer is responsible for the use of parts that does not CAUTION meet the wire standards or capacity requirements) •...
Page 38
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Connecting the power terminal f Connect the cables to the terminal board with solderless ring terminals. f Only sue the certified and rated cables and make sure to firmly connect them without applying any external force to the terminal.
Page 39
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Order of electrical connection f Entire system diagram Power supply cable Communication cable Electrical panel Outdoor unit Communication cable NFB 3 phase 4 wires 380- 415V, 50Hz Ground wire Ground wire Indoor/Outdoor unit connection cable Indoor unit f Power wiring diagram Cable Indoor/outdoor Communication...
Page 40
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC How to connect your extended power cables 1. Prepare the following tools. Tools Crimping pliers Connection sleeve (mm) Insulation tape Contraction tube (mm) MH-14 20xØ6.5(HxOD) Width 19 mm 70xØ8.0 (LxOD) Spec Shape 2. As shown in the figure, peel off the shields from the rubber and wire of the Power cable power cable.
Page 41
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC 5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape. Three or more layers of insulation are required. f Method 1 f Method 2 Insulation tape Insulation tape 40 mm...
Page 42
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Checking the earthing If the power distribution circuit does not have a earthing or the earthing does not comply with specifications, an earthing electrode must be installed. The corresponding accessories are not supplied with the air conditioner. 1.
Page 43
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Vacuuming, gas leak test and charging additional refrigerant Air tightness test and vacuuming Use Nitrogen gas for air tightness test as shown in the illustration. Manifold gage Low pressure side High pressure side Vacuum pump 1. Execute air tightness test with nitrogen gas at pressure over 0.2 MPa and below 4.1 MPa. If you apply pressure at over 4.1 MPa, pipes may get damaged.
Page 44
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Charging the refrigerant and preventing refrigerant leakage 1. Measure the quantity of the refrigerant according to the Manifold gage Outdoor length of the liquid side pipe. Then, Add fixed quantity of the High unit refrigerant using a scale. (When the pipe length exceeds the pressure Gas side pressure...
Page 45
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Pressure table for temperatures If you need extra refrigerant charging due to leakage or relocating the product, refer to below table before charging refrigerant. ❋ Cooling operation Unit : [kPa, G] Indoor temperature (°C) (Dry bulb / Wet bulb) 32/23 27/19 21/15...
Page 46
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC • Cut the middle part of the pipe outlet protection rubber before connecting the pipe. WARNING Pipe outlet protection rubber Connecting drain hose of indoor and outdoor unit 1. To prevent condensation from forming on the drain hose, insulated Drain hose the drain hose with a supplied insulator.
Page 47
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC 4. After connecting the drain hose, use a water bottle to pour water into the air outlet of the indoor unit to check the drainage. (To prevent water from flowing all over the place, insert the water bottle deeply into the first blade on the left side of the air outlet and slowly pour water.
Page 48
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Testing operations 1. Check the power supply between the outdoor unit and the auxiliary circuit breaker. f 1 phase power supply : L, N f 3 phases power supply : R, S, T, N 2. Check the indoor unit. 1) Check that you have connected the power and communication cables correctly.
Page 49
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC 6. View Mode : When the K4 switch is pressed, you can see information about our system state as below. Short push Display contents SEG1 SEG2 SEG3 SEG4 Unit Order frequency Hundreds' digit Tens' digit Unit digit Current frequency Hundreds' digit Tens' digit...
Page 51
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Troubleshooting The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorized Service Center. Outdoor unit If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB. Displayed Meaning Remarks...
Page 52
13. Installation AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC Displayed Meaning Remarks Error Code PCB Assy MAIN Outdoor EEPROM error Check Outdoor EEPROM data E471 MAIN/INVERTER IPM (IGBT Module) or PFCM Temperature sensor Error Check Outdoor Inverter PBA E474 MAIN/INVERTER PFC Overload Error Check Outdoor Inverter PBA E484 MAIN/INVERTER IPM is over heated.
Page 54
Ver.1.1 Samsung Electronics Co., LTD. B2B PM / SE Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677 Website : www.samsung.com, http://btsp.samsunggsbn.com Email : airconditioner@samsung.com Images and data in this book may subject to change without prior notice.