AF✴✴FSSDA✴✴ Series AF✴✴FSZDA✴✴❋Series Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product. ES FR IT PT DE DB68-04036A-04...
Safety precautions Carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order to be able to use it as reference after installation . WARNING Hazards or unsafe practices that may result in severe personal injury or death. CAUTION Hazards or unsafe practices that may result in minor personal injury or property damage.
Page 4
Safety precautions WarNING ▶ Perform the installation securely referring to the installation manual . - Incomplete installation could cause water leakage, electric shock or fire . ▶ Check first the following situations before starting the operation during the installation . - The pipe must be properly connected and make sure there is no leakage .
Page 5
▶ Do not open the front panel of the indoor unit during operation . - It may cause damage to the product . ▶ Check the product before installing it . - Check the unit for damage that may have taken place during transportation and do not install or use damaged equipment .
Choosing the installation location Indoor unit ▶ Install the unit at a place close to the wall facing the outside as it is necessary to perform piing connection with the outdoor unit . - It is effective to install the unit at the place where air flow is not blocked and the cool air can be distributed throughout the room .
Indoor/outdoor unit installation diagram Installation space for floor type indoor unit ▶ To minimize the waste of space due to installation, install the indoor unit as shown in below figure . - top view ❋ ❋ After completing the installation, remove the protection vinyl . (Be careful of static electricity) .
Page 9
Fixing outdoor unit Follow below method to firmly fix the outdoor unit . ▶ Using rubber leg - Put the rubber leg to the outdoor unit leg . (Refer to illustration on the right . ) ▶ Using anchor bolt Anchor bolt fixing dimension 660 mm - On a flat, rigid ground, use 4 anchor bolt (M10) to fix the unit .
Page 10
Indoor/outdoor unit installation diagram Connecting the outdoor unit drain hose Bottom part of the outdoor unit ▶ Push the drain plug into the drain hose connection part as far as possible . Drain plug ▶ Push the drain hose into the drain plug as far as possible and check Drain hose connection part to make sure water is drained properly .
accessories Indoor unit accessories remote controller Fixing bracket for indoor unit Batteries remote controller holder M4X16 screws User & installation manual Cleaning cloth (micro fiber) Outdoor unit accessories Indoor/outdoor unit Indoor/Outdoor unit power rubber leg Main power cable communication cable cable Drain plug Installation accessories...
Drilling a hole and fixing the indoor unit ▶ Drill a hole with diameter of 60~65 mm towards the outside . ▶ If the indoor unit is installed on unstable ground, it may be shaken by an external force or children, and eventually get knocked down .
Page 13
2 . Bend the connection pipe to an appropriate length using a bender depending upon the installation place . 3 . Perform pipe bending process . - Perform bending of the pipe using the pipe bender which has a specified bending radius . - Be sure to take full care to perform bending of the pipe successfully at one time .
Connecting pipes ▶ tightening of connection parts Alight the pipes to be connected and tighten the flare nuts with your hands first and then with a torque wrench, tighten it in a direction shown in below illustration . - You can avoid of gas leakage by applying refrigerant oil on the flare connection part . Pipe Flare connection part Monkey...
Connecting drain hose 1 . Slightly hit the hole, for drain hose, with your hands or hammer . 2 . Insulate the drain hose with drain insulation tube and fix it with tape . 3 . Direct the drain hose downward to establish natural draining . - Make sure to check for proper drainage after connection • Fix the drain hose tightly to prevent any water leakage .
Electrical work • The electrical work should be performed by a specialist qualifi ed for the work . • Avoid using multi-concent but use rate power supply for air conditioner . (Use separate power cable for outdoor CaUtION unit . ) Wiring standard ▶...
Page 17
Safety information on outdoor unit power supply ▶ Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed fl exible cord . (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F ) - Rated voltage: 450/750 V, H07RN-F (60245 IEC 66) - Use cable over 2 .
Electrical work How to connect your extended power cables 1 . Prepare a compressor and the following tools . tools Crimping pliers Connection sleeve (mm) Insulation tape Contraction tube (mm) Spec MH-14 20xØ6 . 5 (HxOD) Width 19mm 70xØ8 . 0 (LxOD) Shape 2 .
Page 19
5 . Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape . A total of three or more layers of insulation is required . ▶ Method 1 ▶ Method 2 Insulation tape Insulation tape 40 mm...
Vacuum pump Vacuuming pipe 1 . Completely connect the indoor/outdoor unit pipes . 2 . Connect the manifold gauge to the service valve port of the low pressure side on the outdoor unit . 3 . Execute vacuum pump for over 30 minutes . - If the pipe extension is larger, time of the vacuum pump should also get longer .
Performing leak test ▶ Use leak tester or soapsuds on the pipe connection part after performing vacuum pump . Check for Check for leakage leakage Test part for indoor unit Test part for outdoor unit ▶ Before inspecting the leakage, use a torque wrench to close the cap for the service valve . ( Comply with a tightening torque for each size of the diameter, and tighten the cap firmly to prevent any leakage .
Charging refrigerant 1 . Connect the manifold gauge in the low pressure side (gas) and press Set/Cancel, Mode, temp + button simultaneously for 5 seconds to enter the refrigerant charging mode . When the outdoor unit operates, charge the refrigerant . 2 .
Unit tCO2e Indoor unit 2 , b refrigerant type GWP value Outdoor unit R-410A 2088 • GWP=Global Warming Potential • Calculating tCO2e : kg x GWP / 1000 a Factory refrigerant charge of the product: see unit name plate . b Additional refrigerant amount charged in the field . (Refer to the above information for the quantity of NOtE refrigerant replenishment .