PM Series Power Meter
Quick Setup Guide - PMC-1000, PMC-
1001, PMM-1000, PMB-1960
Safety Information
DANGER!
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Any covers that may be displaced during the installation must be reinstalled before powering the unit.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
CAUTION
RISK OF EQUIPMENT DAMAGE
This product is designed only for use with 0.33V output current transducers (CTs).
DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
Failure to follow these instructions can result in overheating and permanent equipment damage.
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must control conductive pollution and
the possibility of condensation or high humidity. Consider the enclosure, the correct use of ventilation, thermal properties of the
equipment, and the relationship with the environment. Installation category: CAT II or CAT III
Provide a disconnect device to disconnect the meter from the supply source. Place this device in close proximity to the equipment
and within easy reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the relevant
requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. Disconnecting fuse holders can be used in
the USA and Canada. Provide overcurrent protection and disconnecting device for supply conductors with approved current limiting
devices suitable for protecting the wiring.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the device may be impaired.
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol is used on the product.
Power Meter Quick Setup Guide
QSG-PMM-0B-E  255-64-0004-00
1

Advertisement

Table of Contents
loading

Summary of Contents for Raritan PM Series

  • Page 1 PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. This equipment must only be installed and serviced by qualified electrical personnel.
  • Page 2: Equipment Maintenance And Service

    WARNING! This equipment must only be installed by qualified electrical personnel. This product contains no user serviceable parts. Do not open, alter or disassemble this product. All repairs and servicing must be performed by Raritan authorized service personnel. Failure to comply with this warning may result in electric shock, personal injury and death.
  • Page 3: Product Specification

    Product Specification Voltage Measurement Inputs: Input Range* 90-277VLN, 156-480VLL Phase to Ground* 277V Measurement Category CAT III, Pollution Level 2 Frequency 47-63 Hz 10MΩ Input Impedance *Ratings for models with field wiring terminals. For models with factory installed line-cords, rating is limited by plug and ratings are labeled on back on unit.
  • Page 4: Power Meter (Pmm) Connectors And Controls

    Mechanical: Terminal Block Screw 0.37 ft-lb (0.5Nm) to 0.44 ft-lb (0.6Nm) Torque Terminal Block Wire 14-24AWG (.5-1.6mm) Size Terminal Wire > 75 degree C Temperature Rating DIN Rail T35 (35mm) Environmental: Operating Temperature 0-60°C Operating Humidity 5-85%RH Operating Elevation 0-3000m Conformance: Safety UL/EN 61010-1...
  • Page 5: Power Meter Branch Monitor (Pmb) Connectors

    Power Meter Controller (PMC) MODBUS RDU isolated RS-485 Meter bus connector (to PMM) Meter bus terminator switch 10/100 base-t Ethernet. Feature port (Raritan asset strip) Sensor port (temperature, humidity, etc.) USB A & B (flash drives, WIFI, serial port) RS-232 (terminal CLI, modem)
  • Page 6: Din Rail Mounting

    DIN Rail Mounting 35mm DIN rail Cable supplied with PMB (do not substitute longer length cable) Modules snap into rail. Pull white tab here to remove. Voltage and Current Measurement Wiring Protect phase lines with fused disconnects rated for available short circuit current at connection point.
  • Page 7: Pmb Branch Circuit Wiring

    Circuit Type Circuit Description Wiring Connections Voltage Single-Phase L-N (120V,230V,240V) L-L (208V, 400V) Split-Phase North American 120/240V Panel, 2L+N circuit Three-Phase 3L, 3-phase without neutral 3L+N, 3-phase with neutral PMB Branch Circuit Wiring CT plugs into 2-pin locking connector (Molex 43640-0201) Branch Circuits have two labels: Red labels for odd/even numbered panels.
  • Page 8: Pmm Power Wiring

    PMM Power Wiring PMM can be powered from the voltage measurement inputs or from an auxiliary AC power source. Powering from the voltage measurement inputs minimizes circuitry, but the meter may stop functioning if the voltage turns off. Powering from an auxiliary single phase circuit is required when the voltage measurement circuit exceeds 240V, or when continued operation is required if the voltage measurement inputs turn off.
  • Page 9: Controller Wiring To Meters

    Controller Wiring to Meters Up to seventy 3-phase power meters (PMM) and eight branch circuit meters (PMM+PMB) are daisy-chain wired to a single controller (PMC) using shielded cat 5 Ethernet cable. The wiring order of the modules and controller is not important. All cables shielded Cat-5, each cable:100m max.
  • Page 10: Panel Layout

    Device Information, scroll to the IPV4 settings. Enter the IP address in the web browser:"https://IP address/" 4. Login with the default username and password. Allow 30 seconds for first connection.  Username: admin  Password: raritan Power Meter Quick Setup Guide QSG-PMM-0B-E  255-64-0004-00...
  • Page 11: Configuring Power Meters And Branch Circuit Monitors

    You can configure your product with a spreadsheet, or in the product's web interface. To configure with a spreadsheet: Go to Raritan.com and download the configuration spreadsheet from the BCM2 Support page. Follow the instructions in the spreadsheet. To configure with the product web interface: Make a network connection to the product.
  • Page 12 Configure Power Meter (PMM without PMB) Enter a name. Select the circuit type: Single Phase Split Phase 3-phase Enter the mains circuit breaker rating. Select the checkbox for each CT installed. Enter the CT rating. Ratings are marked on the CT. Click OK.
  • Page 13 Enter the current rating (circuit breaker rating) of the circuit. Select the checkbox for each CT installed. Enter the CT rating. Ratings are marked on the CT. Click OK. The configured branch circuit monitor displays in the dashboard . Configure Panel Branch Circuits In the dashboard, click the BCM to open the pop-up menu.
  • Page 14 Enter a name for the circuit. Select the circuit type: One-Phase LN, One- Phase LL, One-Phase LLN, or Three-Phase. Circuit type cannot be changed later. Enter the current rating of the circuit in Amps. Enter the rating of the CT connected at this circuit position in Amps.
  • Page 15 Configure Thresholds In the dashboard, click the power meter or panel to open the pop-up menu. Click Configure. A new dialog opens. Double-click the reading you want to set thresholds for. A new dialog opens on top. Select the checkbox for the level, and enter the threshold current in amps.
  • Page 16 Using the PMM's Display Automatic Mode: The PMM has a display with automatic and manual modes. In automatic mode, the display scrolls through readings. Manual Mode: In manual mode, you can select readings and settings to view. Press to view the Main Menu. To return to automatic mode, press once or several times.