A Wiring work(Cont.)
Rating current
Unit
Model
Rating current
AM FNLD
007
009
012
018
024
030
036
048
AM MNMD
007
009
012
015
018
Caution
Select the power cable in accordance with relevant local and national regulations.
Wire size must comply with local and national code.
For the power cable, use the grade of H07RN-F or H05RN-F materials.
You should connect the power cable into the power cable terminal and fasten it with a clamp.
The unbalanced power must be maintained within 10% of supply rating among whole indoor units.
If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is
exceeded over 10% of supply rating, the indoor unit is protected, stopped and the error mode indicates.
To protect the product from water and possible shock, you should keep the power cable and the
connection cord of the indoor and outdoor units in the iron pipe.
Connect the power cable to the auxiliary circuit breaker.
An all pole disconnection from the power supply must be incorporated in the fixed
wiring[≥1/8"(3mm)].
You must keep the cable in a protection tube.
Keep distances of 2"(50mm) or more between power cable and communication cable.
Maximum length of power cables are decided within 10% of power drop. If it exceeds, you must
consider another power supplying method.
The circuit breaker(ELCB or MCCB+ELB) should be considered more capacity if many indoor units
are connected from one breaker.
Use round pressure terminal for connections to the power terminal block.
For wiring, use the designated power cable and connect it firmly, then secure to prevent outside
pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head
will strip the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
See the table below for tightening torque for the terminal screws.
M3.5
M4
32
Unit
0.32A
AM FNMD
0.40A
0.51A
0.94A
0.98A
0.80A
AM FNHD
1.05A
1.40A
0.25A
AM MNHD
0.25A
0.26A
0.30A
0.65A
Tightening torque
0.8~1.2 N·m
0.59~0.89 lbf·ft
1.2~1.8 N·m
0.89~1.33 lbf·ft
Model
Rating current
018
1.40A
AM JNMD
024
1.50A
030
1.50A
036
1.60A
048
2.45A
036
1.47A
AM JNHD
048
2.38A
024
0.81A
AM JNMP
027
0.87A
030
0.92A
036
1.13A
048
1.84A
Unit
Model
Rating current
007
0.24A
009
0.24A
012
0.26A
015
0.32A
018
0.40A
024
0.93A
027
0.95A
030
1.11A
036
1.29A
048
1.76A
054
2.10A
006
0.24A
018
0.40A
028
0.95A
042
1.52A

Advertisement