Page 1
Duct Type Series BIG duct : AMFNHDEH Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product.
Safety Precautions The following safety precautions must be taken when using your air conditioner. WARNING • Risk of electric shock can cause injury or death. • Disconnect all remote electric power supplies before servicing, installing or cleaning. • Installation must be done by the manufacturer or service agent or a similar qualified person in order to avoid a hazard.
Page 4
Safety Precautions (Continued) ower suPPly lIne or cIrcuIt breaker If the power cable of this air conditioner is damaged, it must be replaced by service agent or similarly qualified persons in order to avoid a hazard. The unit must be plugged into an independent circuit if applicable or ...
Page 5
Make sure that you earth the cables. - Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing is not complete, electric shock or fire may occur. Install the circuit breaker. ...
Accessories The following accessories are supplied with the indoor unit. The type and quantity may differ depending on the specifications. User's Installation Pattern sheet Insulation cover manual manual pipe in Insulation cover Insulation pipe(A) Insulation pipe(B) Cable tie pipe out Flexible hose Clamp hose Washer...
Selecting the Installation Location Indoor Unit There must be no obstacles near the air inlet and outlet. Install the indoor unit on a ceiling that can support its weight. Maintain sufficient clearance around the indoor unit. Make sure that the water dripping from the drain hose runs away correctly and safely. ...
Page 8
Selecting the Installation Location (Continued) Drawing of the indoor unit Unit : mm 1306 Suspension position 1188 Air inlet duct flange 140X8=1120 140X8=1120 1188 Air outlet duct flange 1240 Discharge side Suction side Name Description Liquid pipe connection ø9.52 : ø19.05 ...
Indoor Unit Installation It is recommended to install theY-joint before installing the indoor unit. Place the pattern sheet on the ceiling at the spot where you want to install the indoor unit. Note Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity.
Purging the Unit On delivery, the indoor unit is loaded with inert gas. All this gas must therefore be purged before connecting the assembly piping. Wet cloth To purge the inert gas, proceed as follows. Unscrew the pinch pipe at the end of each refrigerant pipe. Result: All inert gas escapes from the indoor unit.
Cutting/Flaring the Pipes Make sure that you prepared the required tools. (pipe cutter, reamer, flaring tool and pipe holder) If you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe. There are some examples of correctly and incorrectly cut edges below.
Performing Leak Test & Insulation Leak test LEAK TEST WITH NITROGEN (before opening valves) In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R410A, it’s responsible of installer to pressurize the whole system with nitrogen (using a pressure regulator) at a pressure above 4.1MPa (gauge).
Page 13
Select the insulation of the refrigerant pipe. Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size. Indoor temperature of 30°C and humidity of 85% is the standard condition. If install in a high humidity condition, use one grade thicker insulator by referring to the table below.
Drain pipe and Drain hose Installation Care must be taken when installing the drain hose for the indoor unit to ensure that any condensate water is correctly drained outside. The drain hose can be installed to the right or left side of the base pan.
Page 15
Drain pipe Connection Without the drain pump Install horizontal drain pipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m. Install U-trap at the end of the drain pipe to prevent a nasty smell to reach the indoor unit.
Page 16
Drain pipe and Drain hose Installation (Continued) Centralized Drainage Without the drain pump Install horizontal drain pipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m. Install U-trap at the end of the drain pipe to prevent a nasty smell to reach the indoor unit.
Page 17
Testing the drainage Prepare a little water about 2 liters. Pour water into the drain pan in the indoor unit as shown in figure. Confirm that the water flows out through the drain hose. When the drain pump is installed, operate the unit as cooling mode and check a drain pump pumping.
Wiring Work Power and communication cable connection Before wiring work, you must turn off all power source. Indoor unit power should be supplied through the breaker ( ELCB or MCCB+ELB ) separated by the outdoor power. ELCB: Earth Leakage Circuit Breaker MCCB: Molded Case Circuit Breaker ELB: Earth Leakage Breaker The power cable should be used only copper wires.
Page 19
Selecting compressed ring terminal Silver solder Norminal Norminal Standard Standard Standard Standard dimensions for dimensions for Allowance Allowance Allowance Allowance dimension dimension dimension Min. Min. Max. dimension Min. cable (mm screw (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) +0.3 +0.2 ±0.2...
Page 20
Wiring Work (Continued) Example of Installation - Total power cable length L = 100(m), Running current of each units 1[A] - Total 10 indoor units were installed. 10[A] 9[A] 1[A] ELCB or MCCB+ Indoor unit1 Indoor unit2 Indoor unit10 0[m] 10[m] 20[m] 100[m]...
Page 21
Select the power cable in accordance with relevant local and national regulations. Wire size must comply with local and national code. Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F) You should connect the power cable into the power cable terminal...
Page 22
Wiring Work (Continued) How to connect your extended power cables Prepare the following tools. Connection sleeve Contraction tube Tools Crimping pliers Insulation tape (mm) (mm) Spec MH-14 20xØ6.5(HxOD) Width 19mm 70xØ8.0(LxOD) Shape As shown in the figure, peel off the shields from the rubber and wire of the power Power cable cable.
Page 23
Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape. Three or more layers of insulation are required. f Method 1 f Method 2 Insulation tape Insulation tape 40 mm 35 mm Apply heat to the contraction tube to contract it.
Setting an indoor unit address and installation option Set the indoor unit address and installation option with remote controller option. Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time.
Page 25
Option setting Status 1. Setting SEG2, SEG3 option Press Low Fan button(∨) to enter SEG2 value. Press High Fan button(∧) to enter SEG3 value. Each time you press the button, will be selected in rotation. … SEG2 SEG3 2.
Page 26
Setting an indoor unit address and installation option (Continued) Option setting Status 12. Setting Cool mode Press Mode button to be change to Cool mode in the OFF status. 13. Setting SEG16, SEG17 option Press Low Fan button(∨) to enter SEG16 value. Press High Fan button(∧) to enter SEG17 value.
Page 27
Setting an indoor unit address (MAIN/RMC) Check whether power is supplied or not. - When the indoor unit is not plugged in, there should be additional power supply in the indoor unit. Indoor Unit 1(L) The panel(display) should be connected to an indoor unit to receive option. 2(N) Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
Page 28
Setting an indoor unit address and installation option (Continued) Setting an indoor unit installation option (suitable for the condition of each installation location) Check whether power is supplied or not. - When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
Page 29
02 series installation option(Detailed) Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Use of external room temperature FAN RPM Explanation PAGE MODE Use of robot cleaning sensor / Minimizing fan operation Use of central control compensation when thermostat is off Remote Controller...
Page 30
Setting an indoor unit address and installation option (Continued) Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 EEV Step of Individual control Heating setting compensation / stopped unit Explanation PAGE of a remote Removing condensated water in Motion detect sensor during oil return/ controller heating mode defrost mode...
Page 31
Do not install the electronic heater in the flow channel of the indoor unit fan. Electronic heater should not be installed. Discharge side Suction side Air Flow Duct Indoor unit 05 series installation option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 (When setting SEG3)
Page 32
Setting an indoor unit address and installation option (Continued) 05 series installation option(Detailed) Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 (When setting SEG3) Use of Auto Change (When setting SEG3) (When setting SEG3) Standard for mode Explanation PAGE MODE...
Page 33
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Control variables when using hot water / Explanation external heater Remote Controller Display Details Indication Set temp. for Delay time for heater On/Off heater On At the same time No delay as thermo on At the same time 10 minutes as thermo on...
Page 34
Setting an indoor unit address and installation option (Continued) SEG 3, 4, 5, 6, 8, 9 additional information When the SEG 3 is set as "1" and follow Auto Change Over for HR only operation, it will operate as follows. Standard temp.
Changing a particular option You can change each digit of set option. Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 The tens’ digit of an The unit digit of an The option mode Explanation PAGE MODE option SEG you will option SEG you will Changed value you want to change change...
Final Checks and User Tips To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly. Check the followings. Strength of the installation site Tightness of pipe connection to detect a gas leak ...
Troubleshooting Detection of errors If an error occurs during the operation, an LED flickers and the operation is stopped except the LED. If you re-operate the air conditioner, it operates normally at first, then detect an error again. LED Display on the receiver &...
Page 38
Troubleshooting (Continued) LED Display Abnormal condition Error code 1. COND mid sensor is detached E241 2. Refrigerant leakage (2nd detection) E554 3. Abnomally high temperature on Cond (2nd detection) E450 4. Low pressure s/w (2nd detection) E451 5. Abnomally high temperature on discharged air on outdoor unit E416 (2nd detection) 6.
20DCDC-331110 20DCDC-331110 20DCDC-331110 HIGH 011054-195407- 011054-195429- 011054-19545B- 011054-19549E- 011054-1955D1- 011054-1955F3- AM280FNHDEH 231C1C-331110 231C1C-331110 231C1C-331110 231C1C-331110 231C1C-331110 231C1C-331110 Note represents E.S.P(External Static Pressure)range of factory setting. You don’t have to adjust the fan speed separately if the external static pressure of the installation place is in .
Page 40
This product is RoHS compliant DB68-03653A-06...