Wiring
AA
 Connect the rated cables only.
 Connect using a driver which is able to apply the rated torque to the screws.
 If the terminal is loose, fire may occur caused by arc. If the terminal is connected too firmly, the terminal may be damaged.
M3
M4
12.0~15.0
M5
20.0~25.0
• When connecting cables, you can connect the cables to the electrical part or connect them through the holes
below depending on the spot.
• Run transmission wiring between the indoor and outdoor units through a conduit to protect against external
forces, and feed the conduit through the wall together with refirgerant piping.
• Remove all burrs at the edge of the knock-out hole and secure the cable to the outdoor knock-out using lining and
bushing with an electrical insulation such as rubber and so on.
• Must keep the cable in a protection tube.
• Keep distances of 50mm or more between power cable and communication cable.
• When the cables are connected through the hole, remove the Plate bottom.
34
Tightening Torque (kgf • cm)
5.0~6.0
3phase AC power : L1(R), L2(S), L3(T), N
Communication : F1, F2
1phase AC power : L, N