hit counter code

Samsung RC***MHXGA Installation Manual page 30

Air to water heat pump mono outdoor unit
Table of Contents

Advertisement

Wiring
AA
Power Cable Specifications
Single Phase
Type of outdoor unit
A
B
C
 The power cable is not supplied with air conditioner.
 For power cable, use the grade H05RN-F materials in 1Φ system.
 This equipment complies with "IEC 61000-3-12".
Indoor Unit
(Water Pump, Valve, Wired RMC)
MIM-E03A
Booster Heater (3kw)
Booster Heater (~3kw)
+ Backup Heater (~3kw)
 The Power cable is not supplied with the heat pump.
 For power cable, use the grade H07RN-F materials in 1
 If you connect Backup Heater at separated power cable, you can reduce wire size. (Please refer to indoor unit installation manual)
3 Phase
Type of outdoor unit
A
B
C
 The power cable is not supplied with air conditioner.
 For power cable, use the grade H07RN-F materials in 3Φ system.
 Ssc(MVA) : 3.5(Type of outdoor unit A), Ssc(MVA) : 3.8(Type of outdoor unit B and C)
30
Outdoor
Power supply
RC090MHXEA
1Φ, 220-240V, 50Hz
RC120MHXEA
1Φ, 220-240V, 50Hz
RC140MHXEA
1Φ, 220-240V, 50Hz
RC160MHXEA
Load
Power supply
No Heater
1Φ, 220-240V, 50Hz
Outdoor
Power supply
3Φ, 380~415V, 50Hz
RC120MHXGA
3Φ, 380~415V, 50Hz
RC140MHXGA
3Φ, 380~415V, 50Hz
RC160MHXGA
Power cable
mm²,wires
4.0/3
6.0/3
4.0/3
6.0/3
4.0/3
6.0/3
Power cable
mm²,wires
1.5 / 3
2.5 / 3
4.0 / 3
6.0 / 3
6.0 / 3
8.0 / 3
system.
Φ
power cable
mm²,wires
1.5/4
2.5/4
1.5/4
2.5/4
1.5/4
2.5/4
Type GL
MAX. LENGTH
m
A
<10m
30
10m<L<20m
< 10m
30
10m<L<20m
< 10m
40
10m<L<20m
Type GL
MAX. LENGTH
m
A
<10m
10
10m<L<20m
10
<10m
20
10m<L<20m
20
<10m
40
10m<L<20m
40
Type GL
MAX. LENGTH
m
A
<10m
20
10m<L<20m
<10m
20
10m<L<20m
<10m
20
10m<L<20m

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rc***mhxea

Table of Contents