SYSTEM AIR CONDITIONER INDOOR UNIT AVXC1H022/028/036E✳ AVXC2H056/071E✳ AVXC4H045/056/071/090/112/128/140E✳ AVXCMH028/032/056/060E✳ AVXDDH045/056/071/090E✳ AVXDHH112/128/140E✳ AVXDLH071/090/112/128/140E✳ AVXDBH022/028/036/056/071E✳ AVXDSH022/028/036/040/045/056/071/090/112/128/140E✳ AVXDUH071/112/128/140E✳ AVXWPH022/028/036/045/056/071E✳ AVXWHH028/036/045/056/071E✳ AVXWVH028/036/056/071E✳ AVXTFH056/071E✳ OUTDOOR UNIT mini DVM : RVXMHF040/050E✳ RVXMHF050/060G✳ Plus2: RVXVHT080/100/120/140G✳ RVXFHT080/100/120/140G✳ DVM HR2 : RVXVRT080/100G✳ SERVICE Manual AIR CONDITIONER THE FEATURE OF PRODUCT Available to unit with the various indoor units.
If you charge gaseous refrigerant,it may affect the capacity and reliability of the product as a result of change formation of the refrigerant. G Connect only the indoor units fit on R410A refrigerant. Check whether the indoor units can be connected with the product’s catalogue. (When incorrect indoor units are connected,they cannot operate normally.) Samsung Electronics...
G If any gas or impurities except R410A refrigerant come into the refrigerant pipe, serious problem may occur and it may cause injury. G Make sure there is no leakage after installation. – Toxic gas may generate when refrigerant gas contacts with fire. G Leak test must be done using only Nitrogen(NO )gas. Samsung Electronics...
– The place where there is a machine that generates electromagnetic waves. The air conditioner may not operate normally due to control system. – The place where there is a danger of existing combustible gas, carbon fiber or flammable dust. The place where thinner or gasoline is handled. Samsung Electronics...
The DVM(Digital Variable Multi) air conditioning system is equipped with an epoch making technology such as Digital Scroll Compressor or advanced control solution letting you experience a whole new air conditioning system. As the next-gener- ation modular system in the world of high-efficiency air conditioners, Samsung’s DVM air conditioner will make you take pride in your choice.
Page 10
The electronic expansion valve controlled by a Fuzzy logic helps to keep indoor temperature stable in the range of 1˚C. 3. Durable Reliability All the main components of DVM system air conditioner go through B10 test before assemly. In addition, newly released products are tested to ensure long life so that they can offer high reliability. Samsung Electronics...
Page 11
Polybrominated biphenyl (PBB) and Polybrominated diphenylether (PBDE). Even though RoHs directive is applied to small and large electric home appliances, IT equipment, lighting devices, electromotive devices, toys, leisure sports equipment, and automatic vending machine, Samsung applies it to all its products as an Eco-friend- ly policy.
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) Samsung Electronics...
Page 18
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) Samsung Electronics 2-10...
Page 19
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) 2-11 Samsung Electronics...
Page 20
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) Samsung Electronics 2-12...
Page 21
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) 2-13 Samsung Electronics...
Page 22
- Indoor temperature : 20˚C DB - Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 10m(horizontal) ✳ 3) Noise level acquired in a dead room, so actual noise level may be different depending on the installation conditions. Samsung Electronics 2-14...
Page 23
- Indoor temperature : 20˚C DB - Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 10m(horizontal) ✳ 3) Noise level acquired in a dead room, so actual noise level may be different depending on the installation conditions. 2-15 Samsung Electronics...
Page 24
- Indoor temperature : 20˚C DB - Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 10m(horizontal) ✳ 3) Noise level acquired in a dead room, so actual noise level may be different depending on the installation conditions. Samsung Electronics 2-16...
Page 25
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) 2-17 Samsung Electronics...
Page 26
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) Samsung Electronics 2-18...
Page 27
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) 2-19 Samsung Electronics...
Page 28
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) Samsung Electronics 2-20...
Page 29
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) 2-21 Samsung Electronics...
Page 30
- outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal) ✳ 2) Nominal heating capacities are based on: ✳ 1) - indoor temperature : 20˚C DB, ✳ 1) - outdoor temperature : 7˚C DB, 6˚C WB Equivalent refrigerant piping : 10m(horizontal) Samsung Electronics 2-22...
5.2kW~9.0kW(1 room) DB96-05692E ✳ For China MXD-A13K300A DB96-05692B Below 4.0kW(3 rooms) MXD-A13K300B DB96-05692F ✳ For China MXD-A16K213A DB96-05692C Below 4.0kW(1 room) + MXD-A16K213B 5.2kW~9.0kW(2 rooms) DB96-05692G ✳ For China MXD-A16K300A DB96-05692D 5.2kW~7.2kW(3 rooms) MXD-A16K300B DB96-05692H ✳ For China 2-33 Samsung Electronics...
Page 42
P2SMA DB92-00495H P4NMA DB92-00875A 4 way cassette Cooling / Cooling &Heating Requisite Front Panel Type1 P4NMAA DB92-00875B ✳ For America P4SMA DB92-01024A 4 way cassette P4SCA Type2 DB92-00886A ✳ For China PMSMA Mini 4 way cassette DB92-00732G Samsung Electronics 2-34...
Page 43
MCM-B102C DB97-01405F System by each indoor unit. MR-AH01 DB97-00387F (Cooling/Heating) MR-AH01C (Cooling/Heating) DB97-00387M ✳ For China Wireless Cassette type Individual Control Option Remote Control Duct type MR-AC01 DB97-00387H (Cooling) MR-AC01C (Cooling) DB97-00387K ✳ For China 2-35 Samsung Electronics...
Page 44
Indoor Unit Option 16 rooms ON/OFF Controller all lines MCM-A202C DB97-00874J ✳ For China Control by room or zone, MIM-D00 DB97-04121B Reservation function, Indoor Unit Division of power, Option all lines Remote monitoring for power MIM-D00C DB97-04121C control Samsung Electronics 2-36...
(When communication error is for over 2 minutes) : On : Flickering : Off Samsung Electronics...
Page 46
- When stopping the operation during an error is displayed, all lamps are off. - When restarting after stopping an operation, redisplay the error status by deciding the error again on normal operation. - Refer to the “10. Troubleshooting” for detail contents related to the error mode. Samsung Electronics...
(When communication error is for over 2 minutes) : On : Flickering : Off Samsung Electronics...
Page 48
- When stopping the operation during an error is displayed, all lamps are off. - When restarting after stopping an operation, redisplay the error status by deciding the error again on normal operation. - Refer to the “10. Troubleshooting” for detail contents related to the error mode. Samsung Electronics...
(When communication error is for over 2 minutes) : On : Flickering : Off Samsung Electronics...
Page 50
- When stopping the operation during an error is displayed, all lamps are off. - When restarting after stopping an operation, redisplay the error status by deciding the error again on normal operation. - Refer to the “10. Troubleshooting” for detail contents related to the error mode. Samsung Electronics...
1. Error of electronic expansion valve close Displayed on outdoor unit 2. Error of electronic expansion valve open 3. Breakaway of EVA OUT sensor 4. Breakaway of EVA IN sensor : On : Flickering : Off Samsung Electronics...
Page 52
: Off - If you turn off the air conditioner when the LED is flickering, the LED is also turned off. - If you re-operate the air conditioner, it operates normally at first, then detects an error again. Samsung Electronics...
✳ In case several errors are displayed simultaneously, only the most high priority number of an error among errors in the below table is displayed. (The upper location at the below table has more high priority.) ✳ In case same error occurs at several indoor units, only the smallest indoor unit address is displayed. Samsung Electronics...
Page 54
Comp. down by high pressure Comp. down by low pressure Comp. down by the freezing protection control Comp. down by the sump protection control Loading failure Comp. down by the discharge temperature sensor COND OUT sensor breakaway Suction temperature sensor breakaway Samsung Electronics 3-10...
Page 55
Fixed comp3 Sump temperature sensor breakaway Fixed comp1 Discharge temperature sensor breakaway Fixed comp2 Discharge temperature sensor breakaway Fixed comp3 Discharge temperature sensor breakaway Fan motor over current error CT_low current Prohibit starting during operation of the Crack case heater 3-11 Samsung Electronics...
Page 56
➔ E441 ➔ E440 ➔ E442 ➔ E261 ➔ E153 ➔ E241 ➔ E246 ➔ E151 ➔ P703 ➔ E152 ➔ P702 ➔ E129 ➔ E128 ➔ E130 ➔ E121 ➔ E122 ➔ E123 ➔ CH • In case that the same error displays from multi-indoor units, the one having the faster address has the priority. Samsung Electronics 3-12...
Page 57
DIP switch for indoor unit setting was ON position even though indoor unit was not connected DIP switch for indoor unit setting was OFF position even though indoor unit was connedcted Setting number of indoor in MCU PCB is larger than installed indoors ✳ Others are same with DVM Plus 2 3-13 Samsung Electronics...
Input the second digit of option code by pressing the temperature adjustment button(up). example) 021E31142285 ✳ Result) ✳ If 2 is displayed, go to the step 4 (whenever pressing the button, 1~9, A,B,C,D,E,F are lit in order.) Samsung Electronics 3-14...
Page 59
If E displays, go to step 6. ✳ Step 6 ✳ Method) ✳ Input the fifth digit of option code by pressing the On timer button. example) 021E31142285 ✳ Result) ✳ If 3 displays, go to step 7. SEG 5 3-15 Samsung Electronics...
Page 60
2~7 steps, press the mode button to make the first digit 0. ✳ Step 9 ✳ Method) ✳ Input the eighth digit by pressing the temperature adjustment button(up). example) 021E31142285 ✳ Result) ✳ If 4 displays, go to step 10. Samsung Electronics 3-16...
Page 61
Result) ✳ If 2 displays, go to step 12. ✳ Step 12 ✳ Method) ✳ Input the 11st digit by pressing the On timer button. example) 021E31142285 ✳ Result) ✳ If 8 displays, go to step 13. 3-17 Samsung Electronics...
Page 62
Check the option code again and display of remote controller. repeat the step 1~14. (Operation mode/SET TEMP. /fan speed displays.) rear side Samsung Electronics 3-18...
4-1 Outdoor Unit 4-1-1 4/5/6HP(mini DVM) Parts Procedure Remark Outdoor 1) Outdoor unit of a package air conditioner. 2) Separate a front tightening part. (Use +Screw Driver.) 3) Separate the tightening part from side. (Use +Screw Driver.) Samsung Electronics...
Page 67
When assembling the parts, check whether each parts and Electrical Connector fixed firmly. 1) Remove nut flanges(Turn screw leftward, Fan Motor but turn right if you want to remove). & (Use Monkey Spanner.) Propeller Fan 2) Disassemble Propeller Fans. Samsung Electronics...
Page 68
Disassembly and Reassembly 4-1-2 8/10HP(DVM Plus2 2 /DVM HR2 2 ) Parts Procedure Remark 1) Remove fixing screw from the Cabinet. Control In (Use +Screw Driver.) 2) Separate the Cabinet from the Outdoor Unit. Samsung Electronics...
Page 69
Disassembly and Reassembly Parts Procedure Remark 3) Separate the Electrical Component Box from the Outdoor Unit. Samsung Electronics...
Page 70
1) Remove fixing screw from the Bell Mouth. & (Use +Screw Driver.) 2) Separate the Bell Mouth. 3) Remove fixing bolt from the Fan. 4) Separate the Fan from the Outdoor Unit. 5) Remove fixing screw and after removing screws, separate the Motor. Samsung Electronics...
Page 71
Disassembly and Reassembly 4-1-3 12/14HP(DVM Plus2 2 ) Parts Procedure Remark 1) Remove fixing screw from the Cabinet. Control In (Use +Screw Driver.) 2) Separate the Cabinet from the Outdoor Unit. Samsung Electronics...
Page 72
Disassembly and Reassembly Parts Procedure Remark 3) Separate the Electrical Component Box from the Outdoor Unit. Samsung Electronics...
Page 73
1) Remove fixing screw from the Bell Mouth. & (Use +Screw Driver.) 2) Separate the Bell Mouth. 3) Remove fixing bolt from the Fan. 4) Separate the Fan from the Outdoor Unit. 5) Remove fixing screw and after removing screws, separate the Motor. Samsung Electronics...
Page 89
Exploded Views and Parts List 4 way cassette type (cont.) I Body(AVXC4H045/056/071EB, AVXC4H090EC) 18-4 18-2 18-3 18-1 5-15 Samsung Electronics...
Page 90
ASS'Y CUSHION BASE ASS'Y,EPS,V0 DB31-00439A MOTOR INDOOR BLDC DB90-03188A ASS'Y BRACKET MOTOR ASS'Y DB39-01259A CONNECT MOTOR FAN SUB ASS'Y DB32-00169A THERMISTOR IN ASS'Y DB32-00141B THERMISTOR EVAP ASS'Y DB94-01065A ASS'Y DRAIN HOSE ASS'Y DB90-02689B ASS'Y CABI BASE ASS'YSGCC-M Samsung Electronics 5-16...
Page 91
Exploded Views and Parts List 4 way cassette type (cont.) I Body(AVXC4H090/112/128/140EB) 18-4 18-2 18-3 18-1 5-17 Samsung Electronics...
Page 92
ASS'Y CUSHION BASE ASS'Y,EPS,V0 DB31-00364A MOTOR INDOOR BLDC DB94-01059A ASS'Y BRACKET MOTOR ASS'Y DB39-01259A CONNECT MOTOR FAN SUB ASS'Y DB32-00169A THERMISTOR IN ASS'Y DB32-00141A THERMISTOR EVAP ASS'Y DB94-01065A ASS'Y DRAIN HOSE ASS'Y DB90-02689A ASS'Y CABI BASE ASS'Y,SGCC-M Samsung Electronics 5-18...
Page 93
Exploded Views and Parts List 4 way cassette type (cont.) I Panel(AVXC4H045/056/071/090/112/128/140EB, AVXC4H090EC) 5-19 Samsung Electronics...
Page 94
COVER SIDE C HIPS(BLK) DB63-01489A COVER SIDE D HIPS(BLK) DB64-01558A INLAY PCB DB64-01559A BUTTON PCB DB69-01419A CUSHION IN EPS,25 DB69-01420A CUSHION OUT EPS,25 DB61-02704A BRACKET STEPPING MOTOR SGCC-M,T1.0 DB61-02705A PLATE HANGER STS304,T0.5 DB93-02803A ASS'Y PCB DISPLAY ASS'Y Samsung Electronics 5-20...
Exploded Views and Parts List 5-1-4 Mini 4 way cassette type I Body 5-21 Samsung Electronics...
Page 96
MOTOR FAN ASS035WTVA,4WAYMINI-PJT,50Hz DB61-02495A BRACKET MOTOR IN SGCC-M,T1.2 DB63-01407A GROMMET MOTOR NR,35˚ DB90-02222A ASS'Y CABI BASE MINI 4WAY CASSETTE DB63-01372A GUARD SAFETY HSWR,T2.5 DB32-00066E THERMISTOR EVAP IN 300mm,MINI 4WAY CASSETTE DB97-04440A ASS'Y DRAIN HOSE INSTALL MINI 4WAY CASSETTE Samsung Electronics 5-22...
Page 97
Exploded Views and Parts List Mini 4 way cassette type (cont.) I Panel 5-23 Samsung Electronics...
Exploded Views and Parts List 5-1-16 Ceiling type 9 10 1112 45-7 45-6 45-3 45-4 45-5 45-2 45-8 45-1 5-65 Samsung Electronics...
Page 140
ASS'Y DB61-01157A BRACKET EVAP SGCC-M DB63-00624A COVER EVAP DB31-00179A MOTOR FAN ASS'Y(OSME-254SAC) DB67-00260A BLOWER DB61-01160A CASE FAN UP DB63-00611A COVER MOTOR SGCC-M DB61-01162A HOLDER MOTOR SGCC-M DB63-00738A GUARD SAFETY HSWR DB63-00739A GUARD FAN HSWR DB67-00257A DRAIN PAN Samsung Electronics 5-66...
Page 151
Exploded Views and Parts List 8/10HP(DVM Plus2/DVM HR2) (cont.) I RVXVHT080GC/RVXVHT100GC, RVXFHT080GC/RVXFHT100GC 5-77 Samsung Electronics...
Wiring Diagram 6-1-3 4 way cassette type I AVXC4H056/071/112/128/140EA This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 170
Wiring Diagram 4 way cassette type(cont.) I AVXC4H045/056/071/090/112/128/140EB, AVXC4H090EC This Document can not be used without Samsung's authorization. Samsung Electronics...
Wiring Diagram 6-1-8 Duct type(Slim 3 , Mid pressure) I AVXDSH090/112/128/140EA, AVXDUH071/112/128/140E✳ This Document can not be used without Samsung's authorization. Samsung Electronics...
Wiring Diagram 6-1-9 Duct type(Slim 3 ) I AVXDSH071/090/112/128/140EP This Document can not be used without Samsung's authorization. Samsung Electronics 6-10...
Wiring Diagram 6-2-4 8/10/12/14HP(DVM Plus2) I RVXVHT✳✳✳GA/RVXFHT✳✳✳GA This Document can not be used without Samsung's authorization. Samsung Electronics 6-18...
Page 185
Wiring Diagram 8/10/12/14HP(DVM Plus2) (cont.) I RVXVHT✳✳✳GC/RVXFHT✳✳✳GC This Document can not be used without Samsung's authorization. 6-19 Samsung Electronics...
SMPS Part EEV Control Part Zero Crossing Part External Control Part Motor Control Part Louver Control Part Temperature Sensor Part Display Control Part Communication Part Address Setting Switch Part This Document can not be used without Samsung's authorization. Samsung Electronics...
7-1-2 2 way cassette type SMPS Part EEV Control Part Zero Crossing Part External Control Part Motor Control Part Louver Control Part Temperature Sensor Part Display Control Part Communication Part This Document can not be used without Samsung's authorization. Samsung Electronics...
SMPS Part EEV Control Part Zero Crossing Part External Control Part Motor Control Part Louver Control Part Temperature Sensor Part Display Control Part Communication Part Address Setting Switch Part This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 192
EEV & SUB-PCB Part Loading Part External Control Part BLCD Fan Motor Control Part Louver Control Part Temperature Sensor Part Display PCB Part 485 Communication Part Address & Option Switch Set Part This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 193
SMPS Part EEV Control Part Zero Crossing Part External Control Part Motor Control Part Louver Control Part Temperature Sensor Part Display Control Part Communication Part Address Setting Switch Part This Document can not be used without Samsung's authorization. Samsung Electronics...
7-1-5 Duct type SMPS Part EEV Control Part Zero Crossing Part External Control Part Motor Control Part Display Control Part Temperature Sensor Part Address Setting Switch Part Communication Part This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 195
Schematic Diagram 7-1-6 Wall-mounted type(Premium) SMPS Part EEV Control Part Motor Control Part Louver & Grille Control Part Temperature Sensor Part Display Control Part Communication Part Address Setting Switch Part This Document can not be used without Samsung's authorization. Samsung Electronics...
Page 196
7-1-7 Wall-mounted type(Prestige) SMPS Part EEV Control Part Zero Crossing Part Louver & Grille Control Part Motor Control Part External Control Part Temperature Sensor Part Display Control Part Communication Part This Document can not be used without Samsung's authorization. Samsung Electronics...
Schematic Diagram Schematic Diagram 7-1-8 Wall-mounted type(Vivace) Zero Crossing Part Display Control Part Motor Control Part External Control Part Temperature Sensor Part EEV Control Part Louver & Grille Control Part This Document can not be used without Samsung's authorization. Samsung Electronics...
SMPS Part EEV Control Part Zero Crossing Part External Control Part Motor Control Part Louver Control Part Temperature Sensor Part Display Control Part Communication Part Address Setting Switch Part This Document can not be used without Samsung's authorization. Samsung Electronics 7-10...
Page 199
SMPS Part Segment Circuit Part Outdoor Load Control Part Address Setting Switch Part Comm. Terminal Circuit Part MICOM Program Download 3 Phase Check Part Temperature Sensor Part Reset Part This Document can not be used without Samsung's authorization. Samsung Electronics 7-11...
Page 200
MAIN MICOM Outdoor Load Control Part Segment Circuit Part Comm. Terminal Circuit Part Address Setting Switch Part 3 Phase Check Part MICOM Program Download Reset Part Temperature Sensor Part This Document can not be used without Samsung's authorization. Samsung Electronics 7-12...
Page 201
Schematic Diagram Schematic Diagram 7-3-2 MAIN PCB 2 SUB MICOM CT Sensor Part Temperature Sensor Part This Document can not be used without Samsung's authorization. Samsung Electronics 7-13...
Schematic Diagram Schematic Diagram 7-3-3 POWER PCB I RVXVHT✳✳✳GA/RVXFHT✳✳✳GA Power Input Part Power Generating Part for the Main PCB BLDC Motor Power Generating Part Main Power Connector This Document can not be used without Samsung's authorization. Samsung Electronics 7-14...
Page 203
Circuit Part around Motor Operation IC DC Source Part of Main PCB DC Source Part of Motor Operation IC Power Input Part Motor Operation IC Current Sensing Circuit Part Hall Sensing Part This Document can not be used without Samsung's authorization. Samsung Electronics 7-15...
Page 204
Schematic Diagram 7-3-5 CT PCB 1) CT TRANS Alter the electric current flowing in the compressor into the voltage value. 2) Rectify the voltage value. 3) This is the connector to send rectified voltage to the main PCB. 7-16 Samsung Electronics...
Page 206
Schematic Diagram 7-3-6 MCU PCB MAIN MICOM MICOM Main Power Address S/W Control Valve Control EEV Control Sensor Input Communication Display and Key Control MICOM Download EEPROM Control This Document can not be used without Samsung's authorization. Samsung Electronics 7-18...
MICOM DOWNLOAD CN71 BLUE AC POWER CN62 BLUE CN83 EXTERNAL CONTROL CN91 WHITE DISPLAY CN44 BLUE HALL IC CN81 CHECK & CN42 WHITE EVA-OUT SENSOR CN31 COMM1(OUTDOOR) CN41 WHITE ROOM/EVA-IN SENSOR CN33 BLUE COMM2(REMOCON) CN51 BLACK FLOAT S/W Samsung Electronics...
Page 208
RPM up Option drain pump Heating thermo-off +2˚C +5˚C Filter signal display 1,000hr 2,000hr Hot water coil Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control Preparation Samsung Electronics...
FLOAT S/W CN71 BLUE AC POWER ‘ CN60 WHITE LOUVER CN74 YELLOW DRAIN PUMP CN41 WHITE PIPE-IN/ROOM SENSOR CN81 CHECK CN42 WHITE EVA-OUT SENSOR CN83 EXTERNAL CONTROL CN62 BLUE CN61 BLACK MAIN PCB CONNECTER CN32 WHITE REMOCON DC12V Samsung Electronics...
Page 210
RPM up Option drain pump Heating thermo-off +2˚C +5˚C Filter signal display 1,000hr 2,000hr Hot water coil Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control Preparation Samsung Electronics...
YELLOW CN71 BLUE AC POWER CONNECTER CN62 BLUE CN83 EXTERNAL CONTROL CN60 WHITE LOUVER CN32 WHITE REMOCON DC12V & CN10 BLACK MICOM DOWNLOAD CN72 WHITE TRANS-IN CN31 COMM1(OUTDOOR) CN73 WHITE FAN-MOTOR CN33 BLUE COMM2(REMOCON) CN74 YELLOW DRAIN PUMP Samsung Electronics...
Page 212
RPM up normal Option drain pump Heating thermo-off +5˚C +2˚C Filter signal display 1,000hr 2,000hr Hot water coil Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control Preparation Samsung Electronics...
Page 213
WHITE DISPLAY CN81 CHECK CN73 WHITE BLDC MOTOR CN83 EXTERNAL CONTROL CN71 WHITE AC POWER CN51 BLACK FLOAT S/W CN74 YELLOW DRAIN PUMP & CN41 WHITE ROOM/EVA-IN SENSOR CN75 BLACK VANTILATOR CN42 WHITE EVA-OUT SENSOR CN33 BLUE COMM2(REMOCON) Samsung Electronics...
Page 214
RPM up Option drain pump Heating thermo-off +5˚C +2˚C Filter signal display 1,000hr 2,000hr Hot water coil Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control not use Spare Samsung Electronics...
EXTERNAL CONTROL OUT DC12V OUT CN81 CN32 WHITE (ERROR, COMPRESSOR STATE) (WIRED REMOCON POWER) CN10 BLACK MICOM PROGRAM DOWNLOAD EXTERNAL CONTROL IN CN83 (ON/OFF CONTROL SIGNAL) CN91 WHITE DISPLAY PCB CN51 BLACK FLOATING SWITCH CN13 WHITE SSR FAN CONTROL Samsung Electronics...
Page 216
RPM up normal Option drain pump Heating thermo-off +5˚C +2˚C Filter signal display 1,000hr 2,000hr Hot water coil Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control Preparation Samsung Electronics 8-10...
EXTERNAL OPTION CN83 EXTERNAL CONTROL CN76 YELLOW PCB CONNECTER CN62 BLUE CN77 HOT COIL & CN91 WHITE DISPLAY CN74 YELLOW DRAIN PUMP CN10 BLACK MICOM DOWNLOAD CN75 BLACK VENTILATOR CN31 COMM1(OUTDOOR) CN73 WHITE FAN-MOTOR CN33 BLUE COMM2(REMOCON) 8-11 Samsung Electronics...
Page 218
Option drain pump not use Heating thermo-off +2˚C +5˚C Filter signal display 1,000hr 2,000hr Hot water coil not use Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control Preparation Samsung Electronics 8-12...
EXTERNAL OPTION CN83 EXTERNAL CONTROL CN76 YELLOW PCB CONNECTER CN62 BLUE CN77 HOT COIL & CN91 WHITE DISPLAY CN74 YELLOW DRAIN PUMP CN10 BLACK MICOM DOWNLOAD CN75 BLACK VENTILATOR CN31 COMM1(OUTDOOR) CN73 WHITE FAN-MOTOR CN33 BLUE COMM2(REMOCON) 8-13 Samsung Electronics...
Page 220
Heating thermo-off +2˚C +5˚C Filter signal display 1,000hr 2,000hr Hot water coil not use Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control not use Preparation Samsung Electronics 8-14...
Page 221
EXTERNAL CONTROL CN76 YELLOW PCB CONNECTER CN62 BLUE CN77 HOT COIL & CN91 WHITE DISPLAY CN74 YELLOW DRAIN PUMP CN10 BLACK MICOM DOWNLOAD CN75 BLACK VENTILATOR CN31 COMM1(OUTDOOR) CN44 BLUE HALL IC CN33 BLUE COMM2(REMOCON) CN78 WHITE FAN-MOTOR 8-15 Samsung Electronics...
Page 222
Option drain pump Heating thermo-off +2˚C +5˚C Filter signal display 1,000hr 2,000hr Hot water coil Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control not use Preparation Samsung Electronics 8-16...
Page 223
CN32 WHITE REMOCON DC12V CN13 WHITE FAN SINGLE CONTROL CN83 EXTERNAL CONTROL CN79 WHITE FAN POWER CN62 BLUE CN77 HOT COIL “ CN91 WHITE DISPLAY CN74 YELLOW DRAIN PUMP ‘ CN10 BLACK MICOM DOWNLOAD CN75 BLACK VENTILATOR 8-17 Samsung Electronics...
Page 224
Heating thermo-off +2˚C +5˚C Filter signal display 1,000hr 2,000hr Hot water coil not use Electrical heater not use Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control not use Preparation Samsung Electronics 8-18...
Page 225
CN32 WHITE REMOCON DC12V CN13 WHITE BLDC PCB CONNECTION CN83 EXTERNAL CONTROL CN79 WHITE FAN POWER CN62 BLUE CN77 HOT COIL “ CN91 WHITE DISPLAY CN74 YELLOW DRAIN PUMP ‘ CN10 BLACK MICOM DOWNLOAD CN75 BLACK VENTILATOR 8-19 Samsung Electronics...
Page 226
Heating thermo-off +2˚C +5˚C Filter signal display 1,000hr 2,000hr Hot water coil not use Electrical heater not use Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control not use Preparation Samsung Electronics 8-20...
Page 227
PCB Diagram - BLDC SUB PCB COLOR FUNCTION CN71 BLUE AC220V POWER INPUT CN35 WHITE MAIN PCB CONNECTION CN72 WHITE FAN MOTOR CONNECTION 8-21 Samsung Electronics...
BLUE AC POWER CN91 WHITE DISPLAY CN45 WHITE REMOCON RECEIVER CN63 WHITE AUTO GRILLE CN32 BLUE COMM2(REMOCON) CN61 WHITE LOUVER CN31 COMM1(OUTDOOR) CN93 WHITE MICOM DOWNLOAD & CN43 WHITE REMOCON DC12V CN62 BLUE CN41 WHITE ROOM/EVA-IN SENSOR 8-23 Samsung Electronics...
Page 230
PCB Diagram Function Main address (00 ~99) SW01 SW02 Centralized control address set (00 ~FF) SW03 SW04 Function Centralized control Heating thermo-off +2˚C + 5˚C Min.EEV step at heating fix 80step 0 or 80step Samsung Electronics 8-24...
PCB Diagram 8-1-11 Wall-mounted type(Prestige) I MAIN PCB & I SUB PCB 8-25 Samsung Electronics...
Page 232
Option drain pump Heating thermo-off +2˚C +5˚C Filter signal display 1,000hr 2,000hr Hot water coil Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control Preparation Samsung Electronics 8-26...
Motor Rpm FeedBack DownLoad Connector ROOM/EVA IN EVE OUT Indoor Fan Motor COM1 POWER COM2 HVPS & SUB PCB Connection Blade Step Motor Module PCB Connection Auto Grill Step Motor1 Display PCB Connection Auto Grill Step Motor2 Melody 8-27 Samsung Electronics...
Page 234
PCB Diagram I SUB PCB The red number connecter is not used. External Signal MAIN PCB Connection Samsung Electronics 8-28...
FAN-MOTOR CN76 YELLOW CONNECTER CN32 WHITE REMOCON DC12V CN61 BLUE LOUVER CN31 COMM1(OUTDOOR) CN11 TRANS-OUT & CN33 BLUE COMM2(REMOCON) CN72 WHITE TRANS-IN CN91 WHITE DISPLAY CN10 BLACK MICOM DOWNLOAD CN81 CHECK CN62 BLUE CN42 WHITE EVA-OUT SENSOR 8-29 Samsung Electronics...
Page 236
RPM up normal Option drain pump Heating thermo-off +2˚C +5˚C Filter signal display 1,000hr 2,000hr Hot water coil Electrical heater Min.EEV step at heating fix 80step 0 or 80step Wired remocon group master not use External Control Preparation Samsung Electronics 8-30...
Page 237
12 : Room Temperature : CCH : YW396-07AV(RED) SMW250-06(WHT) 34 : Cond mid Temperature : Main Power : YW396-07AV(WHT) SMW250-06(WHT) 56 : Cond out Temperature : Earth : YOW236-01(WHT) SMW250-06(WHT) “ Download : SMW200-10(WHT) Thermistor : ISMW250-04(RED) Interface Module : YW396-02(BLU) 8-31 Samsung Electronics...
OIL/2TUBE/COND SENSOR & OPT1 WHITE CO/HP SELECT CN62 BLUE CN51 YELLOW COMP1 CT INPUT CN49 BLUE OUTAIR SENSOR CN52 BLUE COMP2 CT INPUT CN45 YELLOW SUMP SENSOR CN53 COMP3 CT INPUT CN99 WHITE DC SIGNAL TO POWER PCB 8-33 Samsung Electronics...
CN47 WHITE OIL/2TUBE/COND SENSOR CN75 WHITE VARIABLE COMP. CCH CN62 BLUE CN76 BLACK FIXED COMP. CCH CN99 WHITE DC POWER INPUT CN82 YELLOW OIL VALVE CN49 BLUE OUTDOOR SENSOR CN72 BLUE COMP. SIGNAL CN45 YELLOW SUMP SENSOR Samsung Electronics 8-34...
220V POWER INPUT CN72 WHITE DC310V FAN INPUT CN98 WHITE EARTH CONNECT CN11 AC17V / 9V OUTPUT & SILVER 220V TRANS INPUT CN73 WHITE FAN IN/OUT SIGNAL CN70 BLACK 220V POWER OUTPUT CN99 WHITE DC SIGNAL TO MAIN PCB 8-35 Samsung Electronics...
WHITE FEEDBANK SIGNAL SILVER 220V TRANS INPUT 220V POWER OUTPUT POWER TRANS & CN703 BLACK CN901 (TO MAIN PCB) AC17V/9V OUTPUT CN301 WHITE FAN MOTOR INPUT CN501 WHITE DC SIGNAL TO MAIN PCB CN401 YELLOW HEATSINK THERMAL Samsung Electronics 8-36...
COMMUNICATION CN11 BLUE LOW PRESSURE SENSOR & CN33 BLACK MAIN MICOM DOWNLOAD CN72 HIGH PRESSURE SENSOR CN91 BLACK SUB. MICOM DOWNLOAD CN10 YELLOW TEMPERATURE SENSOR CN81 WHITE EEV 1 CN62 WHITE TEMPERATURE SENSOR CN42 BLUE MAIN EEV Samsung Electronics 8-38...
9. Troubleshooting 9-1 Operating flow of outdoor unit Power on Tracking completed? E201 error(tracking error) Is 3 phase power OK? E425 error (reverse phase/ open phase error) Is preheating of CCH completed? Preheating CCH (For 2.5 hours) Normal operation Samsung Electronics...
3. If the number of the indoor units, founded by the indoor unit installation number setting switch, is not equal to the number of the indoor units, founded in the course of the tracking, Er and E2 are alternately displayed on the display part. Samsung Electronics...
3) If the 3 phase power is normal, check the phase of the power cable using 3 phase tester. When reverse phase 3 phase tester is displayed, change the power cable connection. 4) Press reset key (K3) after above management and check the power again. Samsung Electronics...
Page 248
3 phase power supply line I DVM Plus Series ! communication part @ power OF1 OF2 # power(Compressor) 3 phase power supply line indoor outdoor single phase communication communication AC230V line line supply line Samsung Electronics...
4. The check of operation ability by the temperature is performed only once at the initial stage. However, in case that the product is installed and operated for the first time, the power shall be put 6 hours before. Samsung Electronics...
3. Outdoor unit tracking 3 minute error 4. When sending the communication error from outdoor unit due to the mismatching of the communication numbers and installed numbers after completion of tracking (communication error for more than 2 minutes) : On : Flickering : Off Samsung Electronics...
Page 251
Indoor unit for 10 HP private use option setting error Blink ✳ When stopping the operation during an error is displayed, all lamps are off. ✳ When restarting after stopping an operation, redisplay the error status by deciding the error again on normal operation. Samsung Electronics...
If the above error code is occurred despite the condition does not correspond to the above judgment method, read the value of the outdoor inlet air temperature sensor by use of the view mode or S-net, and then if the value is different from the actual outdoor temperature, replace the temperature sensor. Samsung Electronics...
Page 253
In this case, after correctly connecting the pipe to the indoor unit and open the service valve, refrigerant circulates to the low pressure side; thus, the error is disappeared. Samsung Electronics...
Page 254
• When replace the oil valve, never use a Replace the oil valve (equal oil) welder to the equal oil piping. Operate 1 body. after cutting by the copper pipe cutter. (It is dangerous for firing because oil is gathered to the equal oil piping.) Samsung Electronics 9-10...
Page 255
Is there any clogged part in a piping Check the pipe. (Filter, etc.)? Is the outdoor fan Replace the relevant parts during cooling operation or the (Motor or Fan.) indoor fan during heating operation operated normally? Check the amount of refrigerant 9-11 Samsung Electronics...
Page 256
Is there any leakage on the liquid valve of the outdoor unit Replace the relevant parts. on the stop side or the emission Check Valve during some outdoor units are operated only? Check the amount of refrigerant Samsung Electronics 9-12...
Page 257
Is the voltage of PCB fan motor Replace PCB operated normally? output terminal normal? Operate when every room is cool. After checking the connection wire of the fan motor, replace the motor. Is high/low pressure normal? Check the amount of refrigerant. Completion 9-13 Samsung Electronics...
Page 258
10 minutes. Is the Sump temperature Replace the relevant value similar as the outdoor temperature sensor temperature value? Reattach the temperature sensor Complete the check. Samsung Electronics 9-14...
Page 259
Is there any leakage on the liquid valve of the outdoor unit on the stop side Replace the relevant parts. or the emission Check Valve during some outdoor units are operated only? Check the amount of refrigerant 9-15 Samsung Electronics...
Page 260
Is the resistance value of the COND OUT sensor Sensor defect: Replace the sensor proper? (Refer to Stop ¡ Is there is any change of The sensor side's path is blocked: sensor value during heating operation? Replace the heat exchanger Ass'y. Completion Samsung Electronics 9-16...
Page 261
1. Check Method Is the suction sensor and Reinsert the sensor sensor holder correctly attached? Reattach the sensor holder Is the resistance value of the The sensor defect : suction sensor proper? Replace the sensor (Refer to Completion 9-17 Samsung Electronics...
Page 262
Connect the separate ampere-meter. (Optional) Is the value measured by the Replace the CT sensor. separate ampere-meter same as CT sensor value? Is the CT value measured Compressor break: Replace the over 20A during operation? compressor. Complete the check. Samsung Electronics 9-18...
Page 263
Is there any leakage on the liquid valve of the outdoor unit on the Replace the relevant parts. stop side or the emission Check Valve during some outdoor units are operated only? Check the amount of refrigerant 9-19 Samsung Electronics...
Page 264
Is the drain pump operated? Is the terminal voltage of the drain pump PCB approximately AC 220V? Is the water level of the drain plate lowered? Replace the indoor unit Replace the drain pump. PCB. Normally operated. Replace the drain pump. Samsung Electronics 9-20...
Page 265
If no error is checked for the above check points, replace the relevant indoor unit EEV. - The replacement of EEV is inconvenient because it collects all refrigerant of the system; thus, before replacing it, must check the above points. 9-21 Samsung Electronics...
Page 266
If no error is checked for the above check points, replace the relevant indoor unit EEV. - The replacement of EEV is inconvenient because it collects all refrigerant of the system; thus, before replacing it, must check the above points. Samsung Electronics 9-22...
Page 267
Compressor running & indoor unit on and thermo on Error contents Indoor heat exchanger EVAP IN sensor breakaway 2. Check Method After checking whether the indoor heat exchanger EVAP IN sensor is separated or not, adjust after assembly. 9-23 Samsung Electronics...
Page 268
Compressor running & indoor unit on and thermo on Error contents Indoor heat exchanger EVAP IN sensor breakaway 2. Check Method After checking whether the indoor heat exchanger EVAP OUT sensor is separated or not, adjust after assembly. Samsung Electronics 9-24...
Page 269
After 60 minutes after compressor is started, do not perform the detection of the Sump temperature sensor breakaway. 2. Check Method After checking whether the relevant compressor sensor is broken away by the error code or not, assemble and adjust. 9-25 Samsung Electronics...
Page 270
Is the emission temperature sensor resistance value proper? Sensor defect : Replace the sensor (Refer to Is the sensor insertion location Sensor is inserted incorrectly: correct by the compressor order? Change the sensor location Complete Samsung Electronics 9-26...
Page 271
If compression is achieved smoothly during the relevant compressor operation, there is Is the CT value measured below no error. If compression is not 4A during operation? achieved, the compressor is broken. Complete the check. 9-27 Samsung Electronics...
If the motor is operated, there is no error. 2) Check whether the outdoor unit Fan Motor is rotated and locked or not. 3) Check the motor and the signal terminal connection status. 4) If the motor is not operated, the motor defect is judged. Samsung Electronics 9-28...
Page 273
2) When the above error is occurred in case there is no lock, the signal by overload and error action is judged. The signal is to display the motor load status and it is not an error. 3) Need to check whether there is an error of Fan load status or not. 9-29 Samsung Electronics...
Page 274
1) This signal is for motor protection in order not to start under reverse rotation condition by checking the moving status when the power of the outdoor unit fan motor is not turned on. 2) Check there is outside wind which can rotate the fan by force in the place where the outdoor unit is installed. Samsung Electronics 9-30...
Page 275
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value 43.0 far from the temperature table? Replace the indoor room temperature sensor because it is defect. Restart after replacing PCB. 9-31 Samsung Electronics...
Page 276
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value 43.0 far from the temperature table? Replace the indoor EVAP IN sensor because it is defect. Restart after replacing PCB. Samsung Electronics 9-32...
Page 277
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value 43.0 far from the temperature table? Replace the indoor EVAP OUT sensor because it is defect. Restart after replacing PCB. 9-33 Samsung Electronics...
Page 278
2) In case the fan motor starting Capacitor is PCB separate type, check the connection terminal. 3) Check the fan motor starting status. 4) If no error is checked for the above check points, replace the PCB. Samsung Electronics 9-34...
Page 279
After checking the communication wire and connecting the indoor unit one by one. After pre-checking connector of the outdoor unit PCB, replace the the wire, replace the indoor unit PCB. PCB. 9-35 Samsung Electronics...
Page 280
If there is no defect, search the indoor unit that interrupts the communication by connecting the indoor unit one by one. After pre-checking the wire, replace the indoor unit PCB. Good 0.7V 0.7V Samsung Electronics 9-36...
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value 43.0 far from the temperature table? Replace the outdoor temperature sensor because it is defect. Restart after replacing PCB. 9-37 Samsung Electronics...
Page 282
Replace the outdoor heat exchanger temperature sensor because it is defect. Restart after replacing PCB. Temperature Resistance Temperature Resistance (°C) (KΩ) (°C) (KΩ) 11.2 18.5 10.8 MUF-0601 Another model (model used PWM compressor) Samsung Electronics 9-38...
Page 283
PCB and measure the resistance value between the both terminals. 11.2 18.5 Is the resistance value far from the temperature table? Replace the outdoor constant speed compressor discharge temperature sensor because it is defect. Restart after replacing PCB. 9-39 Samsung Electronics...
Page 284
3. During the defrost operation, omit the error detection and start the detection after 5 minutes from the completion of the operation. ✳ 4. Short error detection: Detect an error if under 0.4V. ✳ 5. Omit the low pressure sensor error detection when the refrigerant charging and collection operation. Samsung Electronics 9-40...
Page 285
PCB and measure the resistance value between the both terminals. 11.2 18.5 Is the resistance value far from the temperature table? Replace the outdoor oil temperature sensor because it is defect. Restart after replacing PCB. 9-41 Samsung Electronics...
Page 286
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value far 43.0 from the temperature table? Replace the outdoor COND OUT sensor because it is defect. Restart after replacing PCB. Samsung Electronics 9-42...
Page 287
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value far 43.0 from the temperature table? Replace the dual-pipe temperature sensor because it is defect. Restart after replacing PCB. 9-43 Samsung Electronics...
Page 288
3 phase inlet and check it again. error occurred again? The reverse problem of inlet 3 phase lines is solved, thus it operates normally. Replace the PCB because it is a defect of 3 phase detection circuit. Samsung Electronics 9-44...
Compressor protecting action status (Not an error) I EEPROM Error Outdoor unit display Indoor unit display (Operation) (Timer) (Fan) (Filter) (Defrost) Judgment method Impossible to communicate between EEPROM and MICOM Causes Replace PCB due to EEPROM defection 9-45 Samsung Electronics...
Page 290
Is the power supply normal? Check the power. 12V, 5V Check the cut cable of the cut cable changing outdoor communication cable or connection Check the outdoor unit setting Change the setting. option K13, K14 Replace the PCB. Samsung Electronics 9-46...
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value 43.0 far from the temperature table? Replace the indoor room temperature sensor because it is defect. Restart after replacing PCB. 9-47 Samsung Electronics...
Page 292
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value 43.0 far from the temperature table? Replace the indoor EVAP IN sensor because it is defect. Restart after replacing PCB. Samsung Electronics 9-48...
Page 293
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value 43.0 far from the temperature table? Replace the indoor EVAP OUT sensor because it is defect. Restart after replacing PCB. 9-49 Samsung Electronics...
Page 294
Compressor running & indoor unit on and thermo on Error contents Indoor heat exchanger EVAP IN sensor breakaway 2. Check Method After checking whether the indoor heat exchanger EVAP IN sensor is separated or not, adjust after assembly. Samsung Electronics 9-50...
Page 295
Compressor running & indoor unit on and thermo on Error contents Indoor heat exchanger EVAP IN sensor breakaway 2. Check Method After checking whether the indoor heat exchanger EVAP OUT sensor is separated or not, adjust after assembly. 9-51 Samsung Electronics...
Page 296
If no error is checked for the above check points, replace the relevant indoor unit EEV. - The replacement of EEV is inconvenient because it collects all refrigerant of the system; thus, before replacing it, must check the above points. Samsung Electronics 9-52...
Page 297
If no error is checked for the above check points, replace the relevant indoor unit EEV. - The replacement of EEV is inconvenient because it collects all refrigerant of the system; thus, before replacing it, must check the above points. 9-53 Samsung Electronics...
Page 298
Is the drain pump operated? Is the terminal voltage of the drain pump PCB approximately AC 220V? Is the water level of the drain plate lowered? Replace the indoor unit Replace the drain pump. PCB. Normally operated. Replace the drain pump. Samsung Electronics 9-54...
Page 299
After checking the communication wire and connecting the indoor unit one by one. After pre-checking connector of the outdoor unit PCB, replace the the wire, replace the indoor unit PCB. PCB. 9-55 Samsung Electronics...
Page 300
If there is no defect, search the indoor unit that interrupts the communication by connecting the indoor unit one by one. After pre-checking the wire, replace the indoor unit PCB. Good 0.7V 0.7V Samsung Electronics 9-56...
Page 301
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value 43.0 far from the temperature table? Replace the outdoor temperature sensor because it is defect. Restart after replacing PCB. 9-57 Samsung Electronics...
Page 302
PCB and measure the resistance value between the both terminals. 12.1 18.0 27.3 Is the resistance value far 43.0 from the temperature table? Replace the outdoor COND OUT sensor because it is defect. Restart after replacing PCB. Samsung Electronics 9-58...
Page 303
12.1 18.0 27.3 43.0 Is the resistance value far from the temperature table? Replace the outdoor heat exchanger temperature sensor because it is defect. Restart after PCB exchange. 9-59 Samsung Electronics...
Page 304
Is the resistance value of the COND OUT sensor Sensor defect: Replace the sensor proper? (Refer to Stop ¡ Is there is any change of The sensor side's path is blocked: sensor value during heating operation? Replace the heat exchanger Ass'y. Completion Samsung Electronics 9-60...
Page 305
Error contents Outdoor unit COND OUT sensor breakaway 2. Check method Check if the corresponding outdoor unit COND OUT sensor is separated according to the error code, assemble and adjust it. 9-61 Samsung Electronics...
Page 306
Replace the outdoor heat exchanger temperature sensor because it is defect. Restart after replacing PCB. Temperature Resistance Temperature Resistance (°C) (KΩ) (°C) (KΩ) 11.2 18.5 10.8 MUF-0601 Another model (model used PWM compressor) Samsung Electronics 9-62...
Page 307
Check if the corresponding compressor sensor is separated according to the error code, assemble and adjust it. ✳Display method of the order and number of compressor (In case of 4 compressors) Control Box Control Box Front Digital compressor 9-63 Samsung Electronics...
Page 308
Replace the motor after checking Test operation for every the connection wire of fan motor. room(KEY 4) Is high/low pressure normal ? After checking the quantity of refrigerant, if needed recharge It is completed to check the system. the refrigerant. Samsung Electronics 9-64...
Page 309
If the above error code is occurred despite of condition being not included above judge method, read the value of outdoor inlet air temperature by use of view mode or S-net. And then if it is different with the actual outdoor temperature, replace the temperature sensor. 9-65 Samsung Electronics...
Page 310
Teva, out - Tair, in ≥ 3˚C Teva, in - Tair, in ≥ 2˚C Tcond, out - Tair, out < 2˚C Compressor running & indoor unit on and thermo on Error contents Loading failure or OLP Trip Samsung Electronics 9-66...
Page 311
• If waiting at the state that the power is on during the temperature failing down. CCH(Crank case heater) operates to delay the time to restart. Accordingly, separate the connecter to the CCH to block the power and reconnect the connecter after the completion of final check. 9-67 Samsung Electronics...
Page 312
This is the special operation mode to recollect oil discharged from the compressor, and it is entered for 3 minutes in 7 hours interval. It returns to the normal operation after oil collection operation for 3 minutes automatically. Samsung Electronics 9-68...
MCU again, remove all commu- nication connectors of MCU and outdoor unit. And then connect it one by one to find a communication obstacle and replace PCB after checking the communication line. 9-69 Samsung Electronics...
Page 314
If the error is occurred after restarting with a Reset correctly confluence kit change of confluence kit setup DIP switch of MCU and DIP switch and rotary switch address setup, replace MCU PCB. of MCU and restart. Samsung Electronics 9-70...
Page 315
Restart after setting correctly the indoor unit address setup rotary switch of MCU. If the error is occurred after restarting with a change of confluence kit setup DIP switch of MCU and indoor unit address setup, replace MCU PCB. 9-71 Samsung Electronics...
Page 316
Restart after setting correctly between indoor unit and MCU address. If the error is occurred again after restarting with a change of confluence kit setup DIP switch of MCU and indoor unit address setup, replace MCU PCB. Samsung Electronics 9-72...
Page 317
After checking the communication line connected from the outdoor unit to MCU. And if there is no error, connect MCU one by one to find MCU interrupting the communication and replace PCB after checking the communication line. 9-73 Samsung Electronics...
Page 318
Are not 2 address values the same? If the error is occurred again after restarting with a change DIP switch of MCU and indoor unit address setup, replace MCU PCB. Restart after setting 2 indoor unit addresses and MCU address setup value differently. Samsung Electronics 9-74...
Page 319
PCB or MCU PCB. Check indoor unit installation status to MCU. DIP switch for indoor unit set ON even though indoor unit was not installed. Set the switch of branch sphere not used to OFF. Replace MCU PCB. 9-75 Samsung Electronics...
Page 320
PCB or MCU PCB. Check indoor unit installation status to MCU. DIP switch for indoor unit set OFF even though indoor unit was installed. Set the switch of branch sphere not used to ON. Replace MCU PCB. Samsung Electronics 9-76...
Page 321
Check the number of indoor units installed in MCU Set the DIP switch for indoor unit DIP switchs for indoor unit in again according to connected MCU are correct? indoor units Check the other MCU with same method 9-77 Samsung Electronics...
Page 322
MCU Pipe between 4 way valve 4 way valve has large leakage. Change the 4 way valve and accumulator is hot Check the high and low pressure sensor Samsung Electronics 9-78...
10 11 12 13 14 15 16 indoor unit installation The number of switch Example) If 3 indoor units are installed, adjust the arrow of switch to "3". Note : • The display method of English characters and figures on PCB display part 10-3 Samsung Electronics...
(SEG 3, 4 display) (SEG 3, 4 display) Enter times Heating refrigerant Cooling refrigerant 1 time Reset Data display supplement( supplement( Heating test Cooling test 2 time operation( operation( Refrigerant collection 3 time Completion Pump down Completion 4 time Samsung Electronics 10-4...
Page 327
Temp.+3˚C Spare Spare Defrost a option 1 Defrost Defrost Defrost Defrost temperature temperature temperature temperature α α α α Defrost a option 2 = MID = HIGH = MID = Low sw03 Spare Auto/Manual Manual Auto Address 10-5 Samsung Electronics...
G Check the power L1(RED), L2(WHITE), and L3(BLACK) 3 phases of the compressor and the cabinet panel by use of 3 phases tester. G Check the 220V by use of the tester. 3 phases tester Samsung Electronics 10-6...
Page 329
• Check the input value after 30 minutes after running the compressor because the high/low is changed continually at the initial operation. • Don't perform the system operation more than 1 hour to check system pressure. 10-7 Samsung Electronics...
Page 330
G Install the S-NET program to the computer. G Connect a RS-485 converter with COM1 or COM2 port of computer. G Connect the communication wire connected with converter to F1,F2 terminal. • Connect the communication wire with (TX+:F1),(TX-:F2) on connecting. Samsung Electronics 10-8...
• If putting refrigerant into a refrigerant case, must use a rechargeable case for exclusive use. If remodeling the normal refrigerant case illegally, may get damaged by an accident such as explosion. 10-9 Samsung Electronics...
Page 332
4) If the low pressure goes down to below 2kg/cm ,g, lock the SVC valve on the gas side immediately and end the pumpdown operation. (For ending of the pumpdown operation, press the K2 button two times or press the K3 button once to reset.) Samsung Electronics 10-10...
Page 333
4) Lock the valves on the liquid side of the Main Unit and observe the low pressure same as the single outdoor unit case. 5) If the low pressure is lowered, lock the valves on the gas side of the Main Unit and end the pumpdown operation mode. 10-11 Samsung Electronics...
Page 334
Reference Information In case more than 2 units of outdoor unit are installed(cont.) Main Unit Sub Unit (Variable Outdoor Unit) (Constant Speed Outdoor Unit) Samsung Electronics 10-12...
Low pressure part's pressure (kgf/cm If the number on the Display is 4020, start to lock the low pressure valve. If it reaches 4000, finish it. 5) Stop the outdoor unit operation by pressing the K3 key once. 10-13 Samsung Electronics...
2. Use the K2 Key 3. Automatic operation by the basic setting time during cooling operation Sub3 Sub2 Sub1 Main 4. Use the key mode if required The number of pressing Display 7 times 7 times: Samsung Electronics 10-14...
12 times: All unit 12 times: 4. Operation Method : All the EEV of the outdoor unit on the vacuum mode is opened to the maximum degree of openness and all the Solenoid Valve is waited on the open state. 10-15 Samsung Electronics...
Because DVM plus 2 is the air-conditioning and heating product, must use the Bi-Directional Filter Drier. Use the Filter Drier specified on the below according to the outdoor unit's capacity. Outdoor unit Liquid Pipe Diameter Samsung SVC Material Code Manufacturer (ALCO) Model Name 8 HP / 10 HP 3/8"...
✳ 3. The design pressure is different at each product. Please refer to the installation manual for each product. ✳ 3. The design pressure is different at each product. Please refer to the installation manual for each product. (Reference) 1 Mpa 10.19716 kgf/cm (Reference) 1 Mpa 10.19716 kgf/cm 10-17 Samsung Electronics...
Page 340
Reference Information I Thermodynamic characteristic of R410A Samsung Electronics 10-18...
: ø9.52x10m g : ø6.35x10m j : ø6.35x10m b : ø15.88x10m e : ø9.52x10m h : ø6.35x10m k : ø6.35 x 9m c : ø9.52x10m f : ø9.52x10m i : ø12.70x10m 30x0.27 10x0.18 10x0.125 40x0.06 49x0.02 = 14.33 10-19 Samsung Electronics...
• Long stability over long period time • Since R410A don't have chlorine, the tester • R410A, R407C(E), R404A, R507A, R134a, must can detect Hydrogen. R12, R22, R502, R500 are detected. Gas leak • Available in the range of 0 to 40˚C. tester Samsung Electronics 10-20...
It occurs when the drain pump is plugged out or it is out of order. Check the power of the drain pump and the position of the drain hose, and when the pump is faulty, contact the drain pump manufacturer. Samsung Electronics do not manufacture drain pumps. So, we are not able to correct the drain pump problems.
Page 344
Set up a sun blind over the outdoor unit and clear the neighboring obstacles from the outdoor unit to provide good ventilation. When it goes off frequently during a heat wave, it would prevent the turn-off and increase the cooling capacity cleaning the outdoor unit or spraying some water to the heat exchanger. Samsung Electronics 10-22...
Page 345
There is a cost table. But, our service engineer needs to visit to total up the cost correctly. When you move in, make sure to contact Samsung Electronics Service Center or Authorized Service Agent in advance to streamline the process.
10-8 Refrigerant circuit diagram 10-8-1 HEAT PUMP 10-8-1-1 Cooling Operation I RVXMHF✳✳✳✳✳ High Temperature High Pressure Gas High Temperature High Pressure Liquid Low Temperature Low Pressure Gas Samsung Electronics 10-24...
Page 347
Oil Valve 1 Oil Valve 2 Accumulator High Temperature High Pressure Gas Temperature Sensor Solenoid Valve High Temperature High Pressure Liquid Pressure Sensor or Switch Electronic Expansion Valve Low Temperature Low Pressure Gas Service Valve Compressor Check Valve 10-25 Samsung Electronics...
Page 348
Oil Valve 1 Oil Valve 2 Accumulator Temperature Sensor Solenoid Valve High Temperature High Pressure Gas High Temperature High Pressure Liquid Pressure Sensor or Switch Electronic Expansion Valve Low Temperature Low Pressure Gas Service Valve Compressor Check Valve Samsung Electronics 10-26...
Page 349
Reference Information 10-8-1-2 Heating Operation I RVXMHF✳✳✳✳✳ High Temperature High Pressure Gas High Temperature High Pressure Liquid Low Temperature Low Pressure Gas 10-27 Samsung Electronics...
Page 351
Oil Valve 1 Oil Valve 2 Accumulator Temperature Sensor Solenoid Valve High Temperature High Pressure Gas High Temperature High Pressure Liquid Pressure Sensor or Switch Electronic Expansion Valve Low Temperature Low Pressure Gas Service Valve Compressor Check Valve 10-29 Samsung Electronics...
Page 352
Use to protect and control the compressor by measuring the temperature of the compressor outlet. 15. Cond Out Sensor Use to decide the amount of the refrigerant during cooling operation and to decide the start or cancellation of defrost operation during heating operation. Samsung Electronics 10-30...
Page 353
Do the heat exchange of the overcooling liquid of the condenser outlet with the refrigerant of the compressor inhalation side during cooling operation. 23. Oil Separator Collect the oil to the compressor by separating the emitted refrigerant and oil from the compressor. 10-31 Samsung Electronics...
- Always closed in cooling mode and when the majority of indoor units is in cooling mode - Always open in heating mode Cooling Valve - Open when indoor units is selected to Cooling Mode Heating Valve - Open when indoor units is selected to Heating Mode 10-39 Samsung Electronics...