hit counter code

Product Layout - Samsung MIM-A60N Installation Manual

Table of Contents

Advertisement

Available languages

Available languages

Checklist Prior to Installation

Product layout

No.
Name
Y1
Stage 1 cooling input
Y2
Stage 2 cooling input
G
Fan
Low Fan input when thermostat
G1
has multiple Fan outputs.
Mid Fan input when thermostat
G2
has multiple Fan outputs.
01
High Fan input when thermostat
G3
has multiple Fan outputs.
W1
Stage 1 heating input
W2
Stage 2 heating input
R
24VAC (out) to Thermostat
C
Common (out) to Thermostat
TR
24VAC (In) from Transformer
02
TC
Common (In) from Transformer
WARNING
Some Samsung indoor units are not supported. Refer to technical documents at www.SamsungHVAC.com for
compatibility details.
6 English
DGT_MIM-A60N-00_Thermostat Kit_IM_Global_L04_.indb 6
06
05
01
02
Description
07
03
04
08
No.
Name
Description
DI1
Emergency Input (Optional)
DI2
Not Used
COM
Input Common (Optional)
DO1
Error Feedback Output (Optional)
03
DO1
Error Feedback Output (Optional)
Emergency External Heat Output
DO2
(Optional)
Emergency External Heat Output
DO2
(Optional)
F3
04
F3, F4 Communication
F4
External Thermistor Sensor
05
CN7
(Optional)
06
DIP SW
DIP Switch (Setting Option Mode)
07
SW5
Reset Switch
Rotary Switch
08
RSW1,2
(Setting Y1/Y2/W1/W2 Temperature)
2020-01-16 오전 11:37:25