Page 1
SYSTEM AIR CONDITIONER OUTDOOR UNIT AM080/100/120/140/160/180/200/220/240/260SXVSSS AM080/100/120/200FXWASSS AM080/100/120/140/160/180/200/220JXVASS AM140/160/180/200/220/240/260/280/300KXVSSS AIR CONDITIONER CONTENTS 1. Precautions 2. Product Specifications 3. Disassembly and Reassembly 4. Troubleshooting 5. PCB Diagram and Parts List 6. Wiring Diagram 7. Cycle Diagram 8. Key Options 9. Test Operation...
4-3-6 Internal Communication error of the Outdoor Unit C-Box ............4-26 4-3-7 Internal PCB Communication error of the Outdoor Unit C-Box..........4-27 4-3-8 MCU branch part setup error-inconsecutive connection with the use of 2 branch Parts ............................4-29 Samsung Electronics...
Page 3
4-3-57 Error due to using single type outdoor unit in a module installation ....... 4-87 4-3-57 Indoor unit and MCU address duplication error ................. 4-88 5. PCB Diagram and Parts List ................5-1 5-1 ASS'Y PCB MAIN ................................5-1 5-2 ASS'Y PCB MAIN-HUB ..............................5-4 Samsung Electronics...
Page 4
9. Test Operation ..................... 9-1 9-1 Auto Trial Operation ..............................9-1 9-1-1 Auto Trial Operation Synopsis ........................9-1 9-1-2 Auto Trial Operation functions .........................9-3 9-1-3 How to troubleshoot of the "Undetermined"..................9-4 9-2 Amount of refrigerant automatically checking .................... 9-14 9-3 Model Naming ................................9-15 Samsung Electronics...
Explain to workers that the battery for the remote control needs to be separated for storage purposes when the product will not be used for a long time. – This can cause a problem for the remote control since battery fluid may trickle out. Samsung Electronics...
If the compressor is operating while the refrigerant pipe is not correctly connected and the service valve is opened, then air and other substances can enter the pipe. The interior of the refrigerant cycle may then build up excessive high pressure resulting in explosion and damage. Samsung Electronics...
When load changes, capacity amendment that is soft by continuous operation of Dual Inverter is available. Step 1 Step 2 Capacity Step 3 Step 4 Variable ■ Compressor driving : When load changes, is variable by fast inverter frequency. ■ Amenities elevation : 0.5°C Samsung Electronics...
Page 8
- Refrigerant cooling system : Forced circulation / electric heat performance is high and control of (thermal conductivity is 10 times higher than air) load is available. Refrigerant cooling system : It is cooling technology of inverter circuit that use refrigerating cycle technology. Cooling of inverter circuit Cooling of inverter circuit Samsung Electronics...
Monolayer structure Double Layer Structure - Inverter technology integration (Inverter control circuit composition) Control Box - C/Box volume maximum use structure Built-in type Controller embodi- ment - Integrated power supply + control unit - Piping service easiness Samsung Electronics...
Page 10
Applied inverter Compressor Inverter PCB (Compressor - Refrigerant cooling method Control PCB) - Mount power relay on PCB 3 phase power EMI PCB EMI PCB - Fuse mount Communication - Mount communication terminal Terminal block block on PCB Samsung Electronics...
Page 11
→ Did Power Relay mount to PCB. 3 phase power EMI PCB ← EMI PCB - Fuse mount Communication Did Communication Terminal block ← Terminal block mount to PCB. Water Hub PCB Water Hub PCB - External contact for DVM S WATER Samsung Electronics...
Page 12
→ Increases coil size and EMI PCB fuse capacity - Improves EMI characteristic. - Increases current due to high capacity compressor REACTOR - Improved wire connection terminal - Increases heat cooling capacity Refrigerant - Increases pipe size and heat cooling exchange area Samsung Electronics...
Page 13
After changed part and feature Pipe New Pipe Cooling for cooling Unapplied Cooling of inverter PCB. efRigeRant cooling system t is Cooling teChnology of inverter CirCuit that use refrigerating CyCle teChnology ooling of inverter CirCuit ooling of inverter CirCuit Samsung Electronics...
Page 14
Product Specifications TUBE Changed Changed item Basic After changed [HP] After changed [HR] part and feature New inverter Tube cycle technol- struc- ogy application ture New piping Samsung Electronics...
4 WAY V/V Sub Cooler Receiver Compressor Plate Heat Exchanger Oil separator Large size Liquid Pipe 4 WAY V/V High pressure Gas Pipe Low pressure Gas Pipe Accumulator CONTROL BOX Sub Cooler Oil separator Plate Heat Exchanger Receiver Compressor 2-12 Samsung Electronics...
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-18 Samsung Electronics...
Page 25
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. Samsung Electronics 2-19...
Page 26
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-20 Samsung Electronics...
Page 27
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. Samsung Electronics 2-21...
Page 28
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-22 Samsung Electronics...
Page 29
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. Samsung Electronics 2-23...
Page 30
Product Specifications Product Specifications Outdoor Unit (cont.) New Model Comparative Model TYPE Model Name AM080FXWANR/EU AM100FXWANR/EU AM120FXWANR/EU AM200FXWANR/EU RD100DRXH1 RD200DRXH1 RD300DRXH1 Power Supply Φ, #, V, Hz 3/AC380~415/50 3/AC380~415/50 34.8 Cooling Performance kcal/h 19780 24940 29928 49880 24940 49880 74820...
Page 31
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-26 Samsung Electronics...
Page 32
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-27 Samsung Electronics Samsung Electronics 2-28...
Page 33
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-29 Samsung Electronics Samsung Electronics 2-30...
Page 34
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-31 Samsung Electronics Samsung Electronics 2-32...
Page 35
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-33 Samsung Electronics Samsung Electronics 2-34...
Page 36
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-35 Samsung Electronics Samsung Electronics 2-36...
Page 37
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-37 Samsung Electronics Samsung Electronics 2-38...
Page 38
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-39 Samsung Electronics Samsung Electronics 2-40...
Page 39
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-41 Samsung Electronics Samsung Electronics 2-42...
Page 40
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-43 Samsung Electronics Samsung Electronics 2-44...
Page 41
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-45 Samsung Electronics...
Page 43
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-48 Samsung Electronics Samsung Electronics 2-49...
Page 44
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-50 Samsung Electronics Samsung Electronics 2-51...
Page 45
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-52 Samsung Electronics Samsung Electronics 2-53...
Page 46
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-54 Samsung Electronics Samsung Electronics 2-55...
Page 47
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-56 Samsung Electronics Samsung Electronics 2-57...
Page 48
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-58 Samsung Electronics Samsung Electronics 2-59...
Page 49
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. 2-60 Samsung Electronics Samsung Electronics 2-61...
MONKEY SPANNER -SCREW DRIVER NIPPER ELECTRIC MOTION DRIVER L-WRENCH For “disassembly and assembly” DVM PLUS Ⅳ indoor unit, please refer to the products with the same structures. Only those products that are not specified elsewhere are described here. Samsung Electronics...
1) Remove 14 screws from the cabinet equipment Part (Use + screw driver) 2) Remove 4 screws and separate cover control box (Use + screw driver) 3) Power, Compressor, Valve, Motor, Sensor connector connected to ASSY PCB remove. Samsung Electronics...
Page 53
5) 2 screws had fixed in terminal block after remove 4 screws had fixed to Cabinet for terminal block protection remove. 6) 5 screws had fixed to Front part remove. Samsung Electronics...
Page 54
7) 6 screws had fixed on side refrigerant cool- ing part outside remove . Do not separate Heat Sink pulling Assy Piping Cooling piping compulsorily. (It can be a cause of parts damage) 8) 2 screws had fixed on side refrigerant cool- ing part inside remove. Samsung Electronics...
Page 56
Cond Out Sensor Outdoor Temperature Sensor VAlVe & SeNSoR Valve & Sensor Comp Top Sensor Discharge Sensor High Pressure Switch INSulATIoN Model Insu Code Binding Wire AM080/100/120JXVSSH DB62-03808D Samsung Electronics...
Page 57
EVI In Sensor Hot Gas 1 Valve Hot Gas 2 Valve Liquid Sensor INSulATIoN Model Insu Code Binding Wire AM080/100/120JXVHGR DB62-03808E AM080/100/120JXVHGR DB62-04154B AM080/100/120JXVHGR DB62-03808C Samsung Electronics...
Page 58
Cond Out Sensor Outdoor Temperature Sensor VAlVe & SeNSoR Valve & Sensor Comp Top Sensor Discharge Sensor High Pressure Switch INSulATIoN Model Insu Code Binding Wire AM080/100/120JXVHGR DB62-03808D Samsung Electronics...
Page 59
Binding Wire 3 ■ AM080/100/120JXVSSS ► Comp Wire fix by Holder Wire. ► Fix Comp Wire-Core to Bracket Beam Control Box using large size Cable Tie(350mm). ► Separate double layer structure of C/Box after remove 3 screws and connector. Samsung Electronics...
Page 60
4Way+Oil Sepa Out Accum+EVI Bypass Oil Return+Suction Vapor Injection+EVI Bypass Hot Gas Vavle +Suction Hot Gas Vavle +Oil Sepa Out Expansion+Subcooler 4Way+Cond In Pinch Pipe Expansion+Cond Out Accum Oil Return Valve + Suction Liquid Ball Vavle +Colling Accum+Suction 3-10 Samsung Electronics...
Page 61
Accum+Accum Oil Vavle 4Way+Oil Sepa Out Accum+EVI Bypass 4Way+Cond In Vapor Injection+EVI Bypass Expansion+Cond Out Hot Gas Vavle +Oil Sepa Out Pinch Pipe Oil Return+Suction Accum Oil Return Valve+Suction LQD Ball Valve+Subcooler Subcooler+Expansion LQD Ball Valve+Cooling Accum+Suction Samsung Electronics 3-11...
Page 62
Cond Connector+Oil Sepa Out Accum+EVI Bypass Oil Return+Suction Vapor Injection+EVI Bypass Hot Gas Vavle +Suction Hot Gas Vavle +Oil Sepa Out Expansion+Subcooler Cond Connector+Cond In Pinch Pipe Expansion+Cond Out Accum Oil Return Valve + Suction Liquid Ball Vavle +Cooling Accum+Suction 3-12 Samsung Electronics...
1) Remove 11 screws from the cabinet equipment Part (Use + screw driver) 2) Remove 4 screws and separate cover con- trol box (Use + screw driver) 3) Power, Compressor, Valve, Motor, Sensor connector connected to ASSY PCB remove. Samsung Electronics 3-13...
Page 64
5) 2 screws had fixed in terminal block after remove 4 screws had fixed to Cabinet for terminal block protection remove. 6) 5 screws had fixed to Front part remove. 3-14 Samsung Electronics...
Page 65
. Do not separate Heat Sink pulling Assy Piping Cooling piping compulsorily. (It can be a cause of parts damage) 8) 2 screws had fixed on side refrigerant cool- ing part inside remove. Samsung Electronics 3-15...
Page 66
VAlVe & SeNSoR Valve & Sensor EVI SOL Valve Low Pressure Sensor Hot Gas Valve INSulATIoN Model Insu Code Binding Wire AM140JXVSSH DB62-04154D AM140JXVSSH DB62-04154D 3-16 Samsung Electronics...
Page 70
Binding Wire 3 ■ AM140JXV ► Comp Wire fix by Holder Wire. ► Fix Comp Wire-Core to Bracket Beam Control Box using large size Cable Tie(350mm). ► Separate double layer structure of C/Box after remove 3 screws and connector. 3-20 Samsung Electronics...
Page 71
Accum+Accum Oil Valve 4Way+Cond In Accum+EVI Bypass Expansion+Cond Out Vapor Injection+EVI Bypass Expansion+Subcooler Hot Gas Valve+Suction Pinch Pipe Hot Gas Valve+Oil Sepa Out Accum Oil Return Valve + Suction Oil Return+Suction Liquid Ball Valve+Subcooler In Subcooler+Subcooler In Samsung Electronics 3-21...
Page 72
Accum+EVI Bypass 4Way+Cond In Vapor Injection+EVI Bypass Expansion+Cond Out Hot Gas Valve+Suction Pinch Pipe Hot Gas Valve+Oil Sepa Out Accum Oil Return Valve+Suction Oil Return+Suction Subcooler+Subcooler In LQD Valve+Subcooler In Expansion+Subcooler Cooling+Subcooler In LQD Ball Valve+Subcooler In 3-22 Samsung Electronics...
Page 73
1) 11 screws that is fixing CABINET remove. equipment Part (Use + Screw driver) 2) Remove 4 screws that is fixing and separate Cover Control Box. (Use + Screw driver) 3) Power, Compressor, Valve, Motor, Sensor connector connected to ASSY PCB remove. Samsung Electronics 3-23...
Page 74
5) 2 screws had fixed in terminal block after remove 4 screws had fixed to Cabinet for terminal block protection remove. 6) 5 screws had fixed to Front part remove. 3-24 Samsung Electronics...
Page 75
7) 6 screws had fixed on side refrigerant cool- ing part outside remove . Do not separate Heat Sink pulling Assy Piping Cooling piping compulsorily. (It can be a cause of parts damage) 8) 2 screws had fixed on side refrigerant cooling part inside remove. Samsung Electronics 3-25...
Page 76
< Reference > Heat Sink Spread therminal grease on heat sink - Spread enough Thermal Grease evenly on Plate Heat Sink back whole using roller or brush. - Reassemble Plate Heat Sink in reverse order of disassembly. 3-26 Samsung Electronics...
Page 81
AM160/180/200/220SSXVSSS ■ AM140JXVA ► Comp Wire fix by Holder Wire. ► Fix Comp Wire-Core to Bracket Beam Control Box using large size Cable Tie(350mm). ► Separate double layer structure of C/Box after remove 3 screws and connector. Samsung Electronics 3-31...
Page 82
4Way+Oil Sepa Out Accum+Accum Oil Vavle 4Way+Cond In Accum+EVI Bypass Expansion+Cond Out Vapor Injection+EVI Bypass Expansion+Cooling Hot Gas Vavle +Suction Pinch Pipe Hot Gas Vavle +Oil Sepa Out Accum Oil Return Valve + Suction Oil Return+Suction Subcooler+Subcooler In 3-32 Samsung Electronics...
Page 83
4Way+Oil Sepa Out Accum+Accum Oil Vavle 4Way+Cond In Accum+EVI Bypass Expansion+Cond Out Vapor Injection+EVI Bypass Pinch Pipe Hot Gas Vavle +Suction Accum Oil Return Valve+Suction Hot Gas Vavle +Oil Sepa Out Subcooler+Expansion Oil Return+Suction LQD Ball Valve+Subcooler Samsung Electronics 3-33...
Page 84
Discharge+Oil Sepa Accum+Suction Cond Connector+Oil Sepa Out Vapor Injection+EVI Bypass Cond Connector+Cond In Hot Gas Vavle+Suction Expansion+Cond Out Hot Gas Vavle+Oil Sepa Out Expansion+Cooling Oil Return+Suction Pinch Pipe Accum Oil Return Valve+Suction Subcooler+Expansion Accum+Accum Oil Vavle Accum+EVI Bypass 3-34 Samsung Electronics...
1) 9 screws that is fixing CABINET remove. (Use + Screw driver) equipment Part 2) Remove 7 screws that is fixing and sepa- rate Cover Control Box. (Use + Screw driver) 3) Power, Compressor, Valve, Motor, Sensor connector connected to ASSY PCB remove. Samsung Electronics 3-35...
Page 86
5) 2 screws had fixed in terminal block after remove 4 screws had fixed to Cabinet for terminal block protection remove. 6) 4 screws had fixed to Front part remove. 3-36 Samsung Electronics...
Page 87
7) 6 screws had fixed on side refrigerant cool- ing part outside remove . Do not separate Heat Sink pulling Assy Piping Cooling piping compulsorily. (Is responsible for parts damage.) 8) 2 screws had fixed on side refrigerant cool- ing part inside remove. Samsung Electronics 3-37...
Page 88
< Reference > Heat Sink To Heat Sink Thermal Grease Spread service work - Spread enough Thermal Grease evenly on Plate Heat Sink back whole using roller or brush. - Reassemble Plate Heat Sink in reverse order of disassembly. 3-38 Samsung Electronics...
1) 9 screws that is fixing CABINET remove. (Use + Screw driver) equipment Part 2) Remove 6 screws that is fixing and sepa- rate Cover Control Box. (Use + Screw driver) 3) Power, Compressor, Valve, Motor, Sensor connector connected to ASSY PCB remove. Samsung Electronics 3-43...
Page 94
5) 2 screws had fixed in terminal block after remove 4 screws had fixed to Cabinet for terminal block protection remove. 6) 4 screws had fixed to Front part remove. 3-44 Samsung Electronics...
Page 95
7) 6 screws had fixed on side refrigerant cool- ing part outside remove . Do not separate Heat Sink pulling Assy Piping Cooling piping compulsorily. (Is responsible for parts damage.) 8) 2 screws had fixed on side refrigerant cool- ing part inside remove. Samsung Electronics 3-45...
Page 98
Disassembly and Reassembly Binding Wire 3 ■ AM200FXWA ► Comp wire & valve,sensor wires fix by Holder wire. ► Separate double layer structure of C/Box after remove 3 screws and connector. 3-48 Samsung Electronics...
Page 99
Receiver+Bypass hot gas Discharge+Oil Sepa Subcooler+Tube Liquid 4Way+Oil Sepa Subcooler+EVI Bypass 4Way+Accum EVI Bypass+Vapor Injection Accum+EVI Bypass Subcooler+Tube Liquid 4WAY+Tube Liquid Accum+Accum oil 4WAY+Cond Vapor Injection+Vapor Injection Comp+Vapor Injection Bypass hot gas+Oil Sepa Expansion+Cond Bypass hot gas+Suction Receiver+Expansion Samsung Electronics 3-49...
Page 100
1) Remove 10 screws from the cabinet equipment Part (Use + screw driver) 2) Remove 4 screws and separate cover control box (Use + screw driver) 3) Power, Compressor, Valve, Motor, Sensor connector connected to ASSY PCB remove. 3-50 Samsung Electronics...
Page 101
5) 2 screws had fixed in terminal block after remove 4 screws had fixed to Cabinet for terminal block protection remove. 6) 5 screws had fixed to Front part remove. Samsung Electronics 3-51...
Page 102
Do not separate Heat Sink pulling Assy Piping Cooling piping compulsorily. (It can be a cause of parts damage) 8) 2 screws had fixed on side refrigerant AM140KXVSSS cooling part inside remove. Use the driver with magnetic. AM160/180KXVASSS AM160KXVGSS 3-52 Samsung Electronics...
Page 105
■ AM140/160KXVGSS, AM140/160/180KXVASS ► Comp Wire fix by Holder Wire. ► Fix Comp Wire-Core to Bracket Beam Control Box using large size Cable Tie(350mm). ► Separate double layer structure of C/Box after remove 3 screws and connector. Samsung Electronics 3-55...
Page 106
■ AM140/160KXVGSS, AM140/160/180KXVASS Front Welding Parts Rear Welding Parts Welding Position Q'ty Welding Position Q'ty Discharge+Oil-sepa 4way+Cond in Discharge+Comp 4way+Oil-sepa out Suction+Accum 4way+Accum Suction+Comp Expansion+Cond out VI+Connector Expansion+Subcooler Hot-gas+Accum Cooling+Connector Connector+LQD Connector+Subcooler Suction+Oil-Return Pinch Pipe EVI-Bypass+Accum EVI-Bypass+Subcooler VI VALVE+Connector 3-56 Samsung Electronics...
1) 10 screws that is fixing CABINET remove. equipment Part (Use + Screw driver) 2) Remove 4 screws that is fixing and sepa- rate Cover Control Box. (Use + Screw driver) 3) Power, Compressor, Valve, Motor, Sensor connector connected to ASSY PCB remove. Samsung Electronics 3-57...
Page 108
5) 2 screws had fixed in terminal block after remove 4 screws had fixed to Cabinet for terminal block protection remove. 6) 6 screws had fixed to Front part remove. 3-58 Samsung Electronics...
Page 109
Do not separate Heat Sink pulling Assy Piping Cooling piping compulsorily. (It can be a cause of parts damage) 8) 2 screws had fixed on side refrigerant cool- ing part inside remove. Use the driver with magnetic. Samsung Electronics 3-59...
Page 110
< Reference > Heat Sink Spread therminal grease on heat sink - Spread enough Thermal Grease evenly on Plate Heat Sink back whole using roller or brush. - Reassemble Plate Heat Sink in reverse order of disassembly. 3-60 Samsung Electronics...
Page 111
Expansion Valve Liquid Sensor EVI In Sensor EVI Out Sensor Accum Oil Return Valve INSulATIoN Model Insu Code Binding Wire AM200/220SXVSSS DB62-08751D AM200/220SXVSSS DB62-08751A AM200/220SXVSSS DB62-08751E AM200/220SXVSSS DB62-08751C Samsung Electronics 3-61...
Page 113
AM180/200/220KXVGSS, AM200/220KXVASS ■ ► Comp Wire fix by Holder Wire. ► Fix Comp Wire-Core to Bracket Beam Control Box using large size Cable Tie(350mm). ► Separate double layer structure of C/Box after remove 3 screws and connector. Samsung Electronics 3-63...
Page 114
■ Front Welding Parts Rear Welding Parts Welding Position Q'ty Welding Position Q'ty Discharge+Oil-sepa 4way+Cond in Discharge+Comp 4way+Oil-sepa out Suction+Accum 4way+Accum Suction+Comp Expansion+Cond out VI+Connector Expansion+Cooling Hot-gas+Accum Cooling+Connector Suction+Oil-Return Cooling+Subcooler in VI VALVE+Connector Pinch Pipe EVI-Bypass+Subcooler EVI-Bypass+Accum 3-64 Samsung Electronics...
( 'A' direction) 3. Carefully remove the CABINET ( 'B' direction) 2) Remove 4 screws that is fixing and separate Cover Control Box. (Use + Screw driver) 3) Power, Compressor, Valve, Motor, Sensor connector connected to ASSY PCB remove. Samsung Electronics 3-65...
Page 116
5) 2 screws had fixed in terminal block after remove 4 screws had fixed to Cabinet for terminal block protection remove. 6) 5 screws had fixed to Front part remove. 3-66 Samsung Electronics...
Page 117
Do not separate Heat Sink pulling Assy Piping Cooling piping compulsorily. (It can be a cause of parts damage) 8) 2 screws had fixed on side refrigerant cool- ing part inside remove. Use the driver with magnetic. Samsung Electronics 3-67...
Page 118
< Reference > Heat Sink Spread therminal grease on heat sink - Spread enough Thermal Grease evenly on Plate Heat Sink back whole using roller or brush. - Reassemble Plate Heat Sink in reverse order of disassembly. 3-68 Samsung Electronics...
Page 120
Outdoor Temperature Sensor VAlVe & SeNSoR Valve & Sensor Expansion Valve Liquid Sensor EVI In Sensor EVI Out Sensor INSulATIoN Model Insu Code Binding Wire AM240/260/280/300SXVSSS DB62-08751G AM240/260/280/300SXVSSS DB62-08751C AM240/260/280/300SXVSSS DB62-04154C 3-70 Samsung Electronics...
Page 121
AM240/260/280/300KXVSSS, AM080KXVSSS ■ ► Comp Wire fix by Holder Wire. ► Fix Comp Wire-Core to Bracket Beam Control Box using large size Cable Tie(350mm). ► Separate double layer structure of C/Box after remove 3 screws and connector. Samsung Electronics 3-71...
Page 122
Accum + EVI Bypass Receiver + Cond Out Receiver + Expansion Expansion +Cooling Hot Gas Valve + Oil Sepa out Pinch Pipe Accum +Hot Gas Valve Cooling + Subcooler In Oil Return + Suction Vapor Injection + EVI Bypass 3-72 Samsung Electronics...
Page 123
Accum + Accum Oil Valve Expansion + Cond out Accum + EVI Bypass Expansion +Cooling Hot Gas Valve + Oil Sepa out Pinch Pipe Accum +Hot Gas Valve Cooling + Subcooler In Oil Return + Suction Vapor Injection + EVI Bypass Samsung Electronics 3-73...
Page 124
Front Welding Parts Rear Welding Parts Welding Position Q'ty Welding Position Q'ty Discharge+Oil-sepa Cond Connector+Cond in Discharge+Comp Cond Connector+Oil-sepa out Suction+Accum Service Valve+Accum Suction+Comp Expansion+Cond out VI+Connector Expansion+Subcooler Hot-gas+Accum Cooling+Connector Connector+LQD Connector+Subcooler Suction+Oil-Return Pinch Pipe EVI-Bypass+Accum EVI-Bypass+Subcooler VI VALVE+Connector 3-74 Samsung Electronics...
Page 125
Front Welding Parts Rear Welding Parts Welding Position Q'ty Welding Position Q'ty Discharge+Oil-sepa Cond Connector+Cond in Discharge+Comp Cond Connector+Oil-sepa out Suction+Accum Service Valve+Accum Suction+Comp Expansion+Cond out VI+Connector Expansion+Cooling Hot-gas+Accum Cooling+Connector Suction+Oil-Return Cooling+Subcooler in VI VALVE+Connector Pinch Pipe EVI-Bypass+Subcooler EVI-Bypass+Accum Samsung Electronics 3-75...
Page 126
Discharge+Oil Sepa Acuum+4Way Cond Connector+Oil Sepa Out Acuum+Suction Cond Connector+Cond In Accum+Accum Oil Valve Expansion+Cond Out Accum+EVI Bypass Expansion+Cooling Accum+Hot Gas Valve Pinch Pipe Subcooler in+Cooling Oil Return+Suction Vapor Injection+EVI Bypass Hot Gas Vavle +Oil Sepa Out 3-76 Samsung Electronics...
Add oil according to sheep of oil that pour decided addition before. Establish again by vacuum mode after connect power. Execute leakage examination using nitrogen vacuum work Add a refrigerant quantity deciding from step 5. Execute Auto Trial Operation after open SVC Valve. 3-77 Samsung Electronics...
Page 128
- Problem of that is blocked in oil circulation of (remaining oil of compressor that broke down below 0.3kg) compressor if is light more than 0.8kg than weight of compressor that weight of compressor that is changed to locality is changed newly inspects oil circulating system because possibility occurred is high. Samsung Electronics 3-78...
Page 131
- Power connector of ARV confirms that was linked right. - Extract connector in vacuum mode or confirm whether when insert, action sound of valve happens. ③ When CCH is badness, can become cause of compressor breakdown by oil foaming. 3-81 Samsung Electronics...
2) Separate 4 fixing screws from the brackets. (Use + Serew Driver) Cabinet front 1) Separate front cabinet from MCU. Control box cover 1) Separate 2 fixing screws from the control box cover. (Use + Serew Driver) 2) Separate control box cover from MCU. Samsung Electronics 3-82...
1) Separate 1 fixing screw from EEV kit. (Use + Serew Driver) 2) Separate cabinet from EEV kit. Control parts 1) Separate 2 fixing screws from EEV kit. (Use + Serew Driver) 2) Separate control part from EEV kit. 3-83 Samsung Electronics...
Set up the number of connected Indoor units (SMW200-10 black) MICOM. download (AS-PRO) For checking indoor unit communication (SMW200-07P white) (YW396-02P red) Transmitter 12V ERROR DISPLAY (YW396-02P blue) State Check Outdoor Unit Tact Switch (SMW250-04P red) EEPROM SOCKET Outdoor Unit Dip Switch Samsung Electronics...
※ If INV error is occurred(E464/364, E461/361, etc.), please wait more than 15 minutes until self-discharging after shutting off the power because it can not enter a discharge mode. ※ If normal completion discharge mode or self-discharge will be not completed, it is very dangerous to contact because a high DC voltage of inverter PBA is charged. Samsung Electronics...
Page 136
Indoor Unit Whole operation (The set temperature=3°C) Whole operation (The set temperature=40°C) Outdoor fan and valves Normally control conduct Operation time 60 minutes Etc. During the filling operation does not enter the special operation, such as oil recovery, defrost. Samsung Electronics...
Page 137
Operation side : 2000 Step , Stop side : 2000 step Maximum Operation Time 30 minutes Etc. Does not conduct the operation of the special operation, and protection control. Pressure and temperature is outside normal limits : Operation is shut down after gas pipe manually closed. Samsung Electronics...
Page 138
Discharge is complete, the power of the Inverter PCB is being blocked, communication function is blocked, E206 will occur. ► If want operation again after complete discharge mode : Restart after K3 key to Reset or Power Reset. ► Samsung Electronics...
Page 139
Outdoor temperature is less than or equal to 10°C : Heating Auto Trial Operation Oil recovery start Oil recovery start : It is after 10 minutes which Safety Start finishes. Etc. Oil recovery shut down and stop the normal pattern of the outdoor unit stop. Samsung Electronics...
Page 140
※ When there were error, 'Dicharge mode of DC link voltage' may not have been effective. Especialy if error E464 and E364 have been occured, power element might be damaged by fire and therefore, do not use the 'Discharge mode of DC link K3 (Number of press) Key operation Display on segment 1 time Intialize (Reset) setting Same as initial state Samsung Electronics...
Page 141
Starting frequency (Mild Start frequency) operation Indoor Unit Whole operation (The set temperature=3°C) Whole operation (The set temperature=40°C) Other Actuators Normally control conduct Operation time 60 minutes Etc. During the filling operation does not enter the special operation, such as oil recovery. Samsung Electronics...
Page 142
Does not conduct the operation of the special operation, and protection control. Pressure and temperature is outside normal limits : Operation is shut down after gas pipe manually closed. (However, all current limit control, and protection and control of IPM CompDown control is performed.) Samsung Electronics...
Page 143
Discharge is complete, the power of the Inverter PCB is being blocked, communication function is blocked, E206 will occur. ► If want operation again after complete discharge mode : Restart after K3 key to Reset or Power Reset. ► 4-10 Samsung Electronics...
Page 144
Water temperature is less than or equal to 10°C : Heating Auto Trial Operation Oil recovery start Oil recovery start : It is after 10 minutes which Safety Start finishes. Etc. Oil recovery shut down and stop the normal pattern of the outdoor unit stop. Samsung Electronics 4-11...
Page 146
Display method for error that occurred in outdoor unit Error Number Outdoor unit address E471 U200 E471 U200 E206 C001 E206 C002 Error Number, repeat display and other methods of error display Samsung Electronics 4-13...
Page 147
If the rotary switch (on the MCU) for address setting of the indoor unit has 3 or more of the same address When total number of indoor units assigned to MCU is same as actual number of installed indoor units but there E-213 is indoor unit that is not installed even though it is assigned on MCU 4-14 Samsung Electronics...
Page 148
Error due to over voltage /low voltage of inverter PBA2 E-367 Error due to unconnected wire of compressor 2 E-368 Output current sensor error of inverter PBA2 E-369 DC voltage sensor error of inverter PBA2 E-371 Error due to the INV2 Data Flash Samsung Electronics 4-15...
Page 149
Compressor stop due to full current control or error due to low current on CT2 E-464 Error due to over-current of inverter compressor 1 E-465 V-limit error of inverter compressor 1 E-466 Error due to over voltage /low voltage of inveter PBA1 4-16 Samsung Electronics...
Page 150
Error due to using single type outdoor unit in a module installation E-702 Error due to closed EEV of indoor unit (1st detection) E-703 Error due to opened EEV of indoor unit (1st detection) Auto Trial Operation incompleted (UnPrepared) Samsung Electronics 4-17...
2. Execute the Auto Trial Operation by Tact Switch. 3. UP display disappears after Auto Trial Operation is complete, normal operation is possible. 4. Auto Trial Operation is completed, if there is a history, normal opera- tion execution. 4-18 Samsung Electronics...
Page 152
● In case of wiring error (N-phase is changed with one of R, S and T) with the N-phase, will operate the power protection function, display E425 or stop the power. This is not a PCB power defect in this case, before PCB replacement, please CAUTION check the power on. Samsung Electronics 4-19...
Page 153
3. If the quantity of the indoor units configured with the indoor unit installation quantity setup switch does not match the quantity of the indoor units found during the tracking process, E201 and U200 will be displayed in order on the display module. 4. When you install more than one MCU, set the quantity of installed MCU. 4-20 Samsung Electronics...
Is the HUB PCB LED lighted up? Replace HUB PCB if there is abnormality. Is the communication wire of Connect the communication wire to the CN96 connector on the HUB PCB. MAIN/HUB connected? Replace the MAIN PCB. Samsung Electronics 4-21...
PCB. communication for inspection and change the indoor unit PCB. * Essential Requirements before Changing PCB in Case of Communication Error: Refer to p.50 Good Defective 0.7V 0.7V 4-22 Samsung Electronics...
Page 156
- Each resistance value should be measured in tens of kΩ~to hundreds of kΩ. - Difference between the two resistance values should be of some number of kΩ. ● Judging as defective - One or both are low with tens of Ω - One or both of them is open Samsung Electronics 4-23...
Case of Communication Error: Refer to p.50 the indoor unit which interferes with the communication to check and change the indoor unit PCB. Good Defective 0.7V 0.7V 4-24 Samsung Electronics...
Indoor unit and Outdoor unit. Check address of Outdoor unit. Re-address Outdoor unit Check operation of LED and 7-SEG each SUB UNIT normally. Replace MAIN PCB Essential Requirements before Changing PCB in Case of Communication Error: Refer to p.59 Samsung Electronics 4-25...
1) Check the Main PCB : Main PCB TX circuit inspection Does FAN PCB LD22/LD32 (LED) blink? 2) Check the Hub PCB : Hub PCB TX circuit inspection * Service after turn off the Main Power. Replace Main PCB 4-26 Samsung Electronics...
MCU PCB Branch part use setup Setting error Indoor unit address Branch A Indoor unit MCU BOX #0 address setup MCU PCB Branch part use setup Setting error Indoor unit address Branch A Indoor unit Samsung Electronics 4-29...
Find an MCU that is composed as the following picture to carry out assembly of branch part again. After completing the re-setting, press K3 button on the button to reset or turn it off to restart. Outdoor Unit PCB Quantity of Quantity of Indoor Unit Branch Indoor Unit: 3 MCU: 1 4-30 Samsung Electronics...
Address: 2 • Example of MCU address setting error ex) Two among three of MCU address was set to 0 Outdoor Unit PCB Quantity of Quantity of Indoor Unit Branch Indoor Unit: - MCU: 3 Branch Branch 4-32 Samsung Electronics...
MCU BOX #0 address setup MCU PCB Branch part use setup Indoor unit address Branch A MCU BOX #1 address setup MCU PCB Branch part use setup Indoor unit address Branch A MCU BOX #1 MCU PCB Branch A Samsung Electronics 4-33...
Branch A K3 button to reset or turn off to restart. MCU BOX #1 MCU PCB Branch A MCU BOX #1 MCU address setup MCU PCB Branch part use setup Indoor unit address Branch A Indoor unit 4-34 Samsung Electronics...
Check the actual use of the branch part. If it is used, turn on the Dip switch for branch part setup. After completing resetting, press the outdoor unit's K3 button to reset or turn off to restart. MCU BOX #1 MCU address setup MCU PCB Branch part use setup Indoor unit address Branch A Indoor unit Samsung Electronics 4-35...
Example of MCU indoor unit setting DIP switch error • ex) Indoor unit No.5 was connected to branch part C, but DIP switch No.3 (branch part C) is off. Outdoor Unit PCB Quantity of Quantity of Indoor Branch Indoor Unit: 4 MCU: 1 4-36 Samsung Electronics...
Temperature(°C) Resistance(KΩ) measure the resistance value between the 2 terminals. 12.1 18.0 Is the resistor value matching with 27.3 “NOTE1” table? 43.0 Replace this part as it is the defective itself. Restart operation after replace the PCB Samsung Electronics 4-37...
12.1 18.0 CN43 (7, 8) Did the resistance 27.3 value significantly stray from the following 43.0 temperature table? Replace this since it is the defective of the outdoor temperature sensor itself. Restart operation after replace the PCB 4-38 Samsung Electronics...
CN43 (5, 6) 18.0 Did the resistance 27.3 value significantly stray from the following 43.0 temperature table? Replace this part as it is the defective of the outdoor Cond Out sensor itself. Restart operation after replace the PCB. Samsung Electronics 4-39...
Is the Cond Out sensor resistance value reasonable? Defective Sensor : Replace Sensor (Refer to E231) Are there any changes Blocked Sensor Path : n the value of the sensor when operating from Change heat exchanger Ass'y stop to heating? Complete 4-40 Samsung Electronics...
Page 174
Is the Cond Out sensor resistance value reasonable? Defective Sensor : Replace Sensor (Refer to E231) Are there any changes Blocked Sensor Path : n the value of the sensor when operating from Change heat exchanger Ass'y stop to heating? Complete Samsung Electronics 4-41...
553.0 DIS2 : CN45 (3, 4) Is the resistor value matching with “NOTE1” table? Replace this part as it is the defective of the Compressor Discharge or Top Temperature sensor itself. Restart operation after replace the PCB 4-42 Samsung Electronics...
(Please check by connecting the Manifold gauge to the service valve) High pressure sensor Replace PCB terminal of PCB : Is the voltage between 3 and 4 pins 5V? The ▼ mark is the 1st pin on the PCB. Replace High Pressure sensor Samsung Electronics 4-45...
(Please check by connecting the Manifold gauge to the service valve) Low pressure sensor terminal of PCB : Is the Replace PCB voltage between 3 and 4 pins 5V? The ▼ mark is the 1st pin on the PCB. Replace Low Pressure sensor 4-46 Samsung Electronics...
2 terminals. 12.1 SUCT 18.0 CN44 (1, 2) 27.3 43.0 Is the resistor value matching with “NOTE1” table? Replace this part as it is the defective of the Outdoor Suction sensor itself. Restart operation after replace the PCB. Samsung Electronics 4-47...
LIQUID 12.1 CN45 (1, 2) 18.0 27.3 43.0 Is the resistor value matching with “NOTE1” table? Replace this part as it is the defective of the Liquid Pipe Temperature sensor itself. Restart operation after replace the PCB. 4-48 Samsung Electronics...
12.1 CN44 (3, 4) 18.0 27.3 43.0 Is the resistor value matching with “NOTE1” table? Replace this part as it is the defective of the Outdoor EVI In Temperature sensor itself. Restart operation after replace the PCB Samsung Electronics 4-49...
12.1 CN44 (5, 6) 18.0 27.3 43.0 Is the resistor value matching with “NOTE1” table? Replace this part as it is the defective of the Outdoor EVI Out Temperature sensor itself. Restart operation after replace the PCB 4-50 Samsung Electronics...
CN46 (1, 2) 12.1 18.0 27.3 43.0 Is the resistor value matching with “NOTE1” table? Change this part as it is the fault of the outdoor Suction-2 sensor itself. Restart operation after changing PCB Samsung Electronics 4-51...
Are there any blockage inside Pipe inspection the pipe? (filter etc.) Are the Outdoor Fan Replace relevant component operating normally for the cooling and the Indoor Fan operating normally (motor or fan) for the heating? Check the refrigerant amount. Samsung Electronics 4-53...
Page 187
Are there any blockage inside Pipe inspection the pipe? (filter etc.) When cooling operation, Check the water pipes or Replace water temperature, quantity, or heating relevant component(motor or fan) operation, indoor fan operates normally do? Check the refrigerant amount. 4-54 Samsung Electronics...
(filter etc.) Is there any leakage in the Liquid Pipe Valve or the Discharge Replace relevant component check valve leaking on outdoor unit that is off when only some Outdoor Units are operating? Check the refrigerant amount. Samsung Electronics 4-55...
Page 189
(filter etc.) Is there any leakage in the Liquid Pipe Valve or the discharge Replace relevant component check valve of the not-go-end Outdoor Unit when only some Outdoor Units are operating? Check the refrigerant amount. 4-56 Samsung Electronics...
Did the EMI PCB Fuse is short? Replace Fuse, if the rectifier diode of the inverter PCB is normal. Is EMI PCB CN21 Connection and then restart it connector and Inverter PCB accurately connected? Replace the MAIN PCB. 4-58 Samsung Electronics...
Manifold Gauge value in range? Are the 4Way Valve normally operating? Check the 4Way Valve Are the Indoor Unit and Outdoor Unit EEV Check the relevant EEV normally operating? Compressor Inspection Is current of compressor normally? Check the refrigerant Complete Samsung Electronics 4-59...
Replace EVI EEV Abnormal Check for Intercooler leakage. Normal Replace Intercooler Abnormal Check for Indoor Unit EEV leakage Normal Replace Indoor Unit EEV Is there a liquid-gas pipe directly connected to each other? Reinstall pipe Check the refrigerant 4-60 Samsung Electronics...
Out of the PCB Pressure sensor terminals, is there voltage between Replace PCB pins 3 and 4 5V? The ▼ mark is the 1st pin on the PCB. Replace Pressure sensor Samsung Electronics 4-61...
∙ Cooling operation : When the outdoor temperature is less than -25℃ ∙ System protection operation status (Is not breakdown) Cause of problem · If the outdoor temperature is satisfied the operating range, it will clear the error and start the operation automatically. 4-62 Samsung Electronics...
◑ ◑ display ※ ●: ON ◑: Flash ×: OFF Judgment • When the heating refrigerant charge : If the outdoor temperature is more than 15℃ Method Special Cause • System protection operation status (Is not breakdown) Samsung Electronics 4-63...
Fix the compressor Top temperature sensor in correct position. Is CCH resistance normal? (500~700 Ω /infinite for disconnection) Change CCH. Does the E445 error occur even after the outdoor unit K3” RESET? Normal Operation. Replace the PCB. 4-64 Samsung Electronics...
Page 198
Fix the compressor Top temperature sensor in correct position. Is CCH resistance normal? (500~700 Ω /infinite for disconnection) Change CCH. Does the E445 error occur even after the outdoor unit K3” RESET? Normal Operation. Replace the PCB. Samsung Electronics 4-65...
Motor (U ↔ V,V ↔ W,W ↔ U) less than 10Ω? Is the resistance between the body of FAN Motor Replace Fan Motor and chassis MΩ? Does the FAN Motor connection wire properly Check the connection wire connect? Replace Fan PCB 4-66 Samsung Electronics...
Page 200
Measurement error can occur for reasons such as the initial measurement condenser discharge. Measured over at least three times. Measure the diode 0.3~0.7V voltage values < Table 1 > Fan PCB FAN PCB < Figure 1 > Samsung Electronics 4-67...
If you rotate the fan by hand, Replace Fan Motor the noise occurs? Connection wire of Fan Motor did confirmation? Check the connection status, and then restart. (Check the connection status of the Fan1 and Fan2.) Replace Fan PCB 4-68 Samsung Electronics...
※ ●: ON ◑: Flash ×: OFF Judgment ∙ Momentary stop of compressor due to momentary blackout. Method Cause of ∙ Momentary stop of compressor due to momentary blackout. problem 1. Precautions : Replace Hub PCB or Main PCB. Samsung Electronics 4-69...
Connection wire of Fan Motor did confirmation? (Verify that the wire folded, or the connection Check the connecting wire and restart it. is detached.) Is there anything strange in Replace Fan PCB appearance Fan Motor? Replace Fan Motor 4-70 Samsung Electronics...
*Cold heat sink assembly defect occurs. Does the heatsink fixing bolt are tightened completely? Tighten Bolt Remove foreign objects and Did check the foreign objects apply the heat sink grease. between the heat sink and IPM? And then reassembly Replace fan PCB Samsung Electronics 4-71...
Page 205
(U ↔ V,V ↔ W,W ↔ U) less than 2Ω? Is the resistance between the body of Compressor and Replace Compressor. chassis Open? Does the Compressor connection wire properly connect to Repair / Replace the wire. the Inverter PBA? Continue. 4-72 Samsung Electronics...
(U-V, V-W, W-U) less than 2Ω? Is the resistance between the body of Compressor and Replace Compressor chassis MΩ? Does the Compressor Check the connection wire connection wire properly connect (Check the status of the to the compressor? connection UVW) Continue. 4-74 Samsung Electronics...
Page 208
Before change / After change Error, depending on the situation replace the Compressor or PCB Before change After change Measure Replace E464 E464 No.1Inverter PCB Replace E464 E364 No.1 Compressor Replace E364 E364 No.2 Inverter PCB Replace E364 E464 No.2 Compressor Samsung Electronics 4-75...
Page 209
COMP 1 9times (KD__) 8times (KD__) COMP 2 10times (KE__) 9times (KE__) MOTOR 1 11times (KF__) MOTOR 2 12times (KG__) Power Off ( Use to inverter checker ) PBA Defective Replace Compressor/Fan motor Replace Inverter PCB /Fan PCB 4-76 Samsung Electronics...
Page 210
P-IGBT Measured over at least three times. P-IGBT P-IGBT Measure the diode 0.3~0.7V voltage values N-IGBT N-IGBT N-IGBT < Table 1 > Inverter PCB 인버터 PCB < Figure 1 > Samsung Electronics 4-77...
Is Inverter PCB R,S,T Wire and EMI PCB CN21 Power Off and then re-connection connector accurately connected? Replace Inverter PCB Standard AC Voltage(Vac) Standard DC Voltage(Vdc) Type of Power Source AC Input Voltage Min. Max. Min. Max. 208~230V 460V 4-78 Samsung Electronics...
E496 Power Off DC power wire (Inv. PCB) Check the connector Check the status of DC LINK Connector connection Replace FAN PCB DC power wire (Fan PCB) E469 E369 Replace No1 INVERTER PCB Replace No2 INVERTER PCB Samsung Electronics 4-79...
Replace Outdoor Fan Motor Fan Motor and chassis MΩ? Is the Fan Motor wire properly Reconnect wires (Housing – Connector) connected to FAN PCB? Replace Fan PCB Fan PCB wire connection [FAn PCB] FAn Motor Connector Hall-sensor Connector Hall-sensor Connector 4-80 Samsung Electronics...
Page 214
∙ Occurs when overcurrent flows in the IPM. Judgment Method ∙ Detected by H/W or S/W Cause of problem ∙ Defective FAN Motor 1. Cause of problem Power Off E489 E389 Replace No1 Fan motor Replace No2 Fan motor Samsung Electronics 4-81...
Cause of problem ∙ PCB voltage sensing circuit defective 1. Cause of problem Power Off Is Power connection accurately connected? Power Cable re-connection E485 or E385? E493 or E393? E468 or E368? Replace Inverter PCB Replace Fan PCB 4-82 Samsung Electronics...
DC LINK connector disconnect from FAN PCB [Refer to Standard DC Voltage] (If the voltage is out of Std. range) Check the status of DC LINK Connector Replace connected wire Replace FAN PCB DC power wire (Inv. PCB) DC power wire (Fan PCB) Samsung Electronics 4-83...
(Verify that the wire folded, or the connection is detached.) Check the connecting wire and restart it. HALL IC on the PCB is connected correctly? Replace Fan PCB Restart When the error is repeated, replace the Fan Motor. 4-84 Samsung Electronics...
IPM? sink grease. And then reassembly Apply the heat sink grease and then Did properly apply the heat sink grease? (Between the heat sink and the IPM) reassembly. Good No Good Grease Service Code : DB81-02483A Complete Samsung Electronics 4-85...
Compressor Cut off Option Setting, E560. Is the outdoor unit EEPROM accurately Connect outdoor unit EEPROM and then reset. connected to connector? Download relevant model EEPROM and then reset. ※ Execute automatic commissioning for UP cancellation after EEPROM download. 4-86 Samsung Electronics...
Is installed by outdoor unit module? Download relevant model EEPROM and Outdoor unit single type exclusive use then reset. model (non-modular model), can not be ※ Execute automatic commissioning module installation. for "UP" cancellation after EEPROM (Single type only installation) download. Samsung Electronics 4-87...
※ Whole system power reset - To solve the problem through the power reset after the address is reset the power reset of individual units is meaningless and the power of the whole system must be reset. 4-88 Samsung Electronics...
Page 224
PCB Diagram and Parts List ASS'Y PCB MAIN (cont.) ■ AM140/160/180/200/220/240/260/280/300KXVSSS INV COMM Download huB PBA Comm. DRED External Con COMM PBA Comm.(Outdoor) COMM PBA Comm.(Indoor) COMM PBA Comm.(SOL-COM) IN-COM Pump Down Gas Leak Option Switch Error/Comp EEPROM Samsung Electronics...
Page 225
PCB Diagram and Parts List 5-2 ASS'Y PCB MAIN-HUB ■ AC Samsung Electronics...
Page 227
PCB Diagram and Parts List ASS'Y PCB MAIN-HUB (cont.) ■ DC Samsung Electronics...
Page 228
CN701 EVI VALVE 1,2 #1 : 4-WAY VALVE #1 : AC LIVE #1: EVI VALVE 1 #2 : 4-WAY VALVE #2 : AC NEuTRAL #3: EVI VALVE 2 #7: EVI VALVE 1 #8: EVI VALVE 2 #9: AC NEuTRAL Samsung Electronics...
PCB Diagram and Parts List 5-3 ASSY PCB INVERTER - Model : AM080/100/120/140/160/180/200/220FXVSSS, AM080/100/120/140/160/180/200/220JXVSSS, AM140/200/220KXVASS, AM140/180/200/220KXVGSS Samsung Electronics...
Page 231
PCB Diagram and Parts List ASS’Y PCB INVERTER (cont.) - Model : AM240/260HXVSSS, AM240/260JXVSSS, AM160/180/240/260/280/300KXVASS, AM160/240/260/280KXVGSS, AM080KXVSSS 5-10 Samsung Electronics...
Page 232
CN15-FAN DC LINK CN13-AC POWER R-INPuT R TOP S-INPuT S TOP #1 : AC #1: AC LIVE #1: R-IN #1: S-IN #2 : #2: AC NEuTRAL #3 : AC #3: AC NEuTRAL ⑬ T-INPuT T TOP #1: T-IN Samsung Electronics 5-11...
CN23- INVERTER 220V ② CN21-FAN A ③ CN22-MAIN 220 ④ RST- RST INPuT #1 : AC #1 : R #1 : AC T-IN #2 : #2 : S #2 : AC S-IN #3 : AC #3 : T R-IN 5-16 Samsung Electronics...
Page 238
PCB Diagram and Parts List ASS’Y PCB EMI (cont.) - Model : AM240/260HXVSSS, AM240/260JXVSSS, AM160/180/240/260/280/300KXVASS, AM160/240/260/280KXVGSS, AM080KXVSSS Samsung Electronics 5-17...
Page 239
CN107-T OuT ⑦ CN41-EARTh ⑧ CN101-R IN #1 : S-OuT #1 : T-OuT #1 : EARTh (PE) #1 : R-IN ⑨ CN102-S IN ⑩ CN103-T IN ⑪ R-INPuT R TOP #1 : S-IN #1 : T-IN #1: R-IN 5-18 Samsung Electronics...
Wiring Diagram 6. Wiring Diagram 6-1 AM080/100/120/140/160/180/200/220FXVSSS, AM080/100/120/140/160/180/200/220JXVSSS, AM140/200/220KXVASS, AM140/180/200/220KXVGSS This Document can not be used without Samsung’s authorization. Samsung Electronics Samsung Electronics...
Wiring Diagram Wiring Diagram 6-2 AM080/100/120/200FXWASS This Document can not be used without Samsung’s authorization. Samsung Electronics Samsung Electronics...
Page 243
Wiring Diagram Wiring Diagram 6-3 AM240/260HXVSSS, AM240/260JXVSSS, AM160/180/240/260/280/300KXVASS, AM160/240/260/280KXVGSS, AM080KXVSSS This Document can not be used without Samsung’s authorization. Samsung Electronics Samsung Electronics...
Wiring Diagram Wiring Diagram 6-4 AM080JXVAFH This Document can not be used without Samsung’s authorization. Samsung Electronics Samsung Electronics...
Wiring Diagram Wiring Diagram 6-5 AM100/120JXVAFH This Document can not be used without Samsung’s authorization. Samsung Electronics Samsung Electronics 6-10...
Wiring Diagram Wiring Diagram 6-6 AM140/160/180/200JXVAFH This Document can not be used without Samsung’s authorization. 6-11 Samsung Electronics Samsung Electronics 6-12...
Wiring Diagram Wiring Diagram 6-7 AM080/100/120/140/160/180/200/220JXVAJH This Document can not be used without Samsung’s authorization. 6-13 Samsung Electronics Samsung Electronics 6-14...
Suction Temperature Sensor T_CO Cond. Out Temperature Sensor T_EI EVI In Temperature Sensor T_EO EVI Out Temperature Sensor Liquid Pipe Temperature Sensor T_CT Comp. Top Temperature Sensor Ambient Temperature Sensor SV_G Gas Pipe Service Valve SV_L Liquid Pipe Service Valve Samsung Electronics...
EVI In Temperature Sensor T_EO EVI Out Temperature Sensor Liquid Pipe Temperature Sensor T_CT Comp. Top Temperature Sensor Ambient Temperature Sensor SV_G Gas Pipe Service Valve SV_LG Low P. Gas Pipe Service Valve SV_L Liquid Pipe Service Valve Samsung Electronics...
EVI In Temperature Sensor T_EO EVI Out Temperature Sensor Liquid Pipe Temperature Sensor T_CT Comp. Top Temperature Sensor Ambient Temperature Sensor SV_G Gas Pipe Service Valve SV_LG Low P. Gas Pipe Service Valve SV_L Liquid Pipe Service Valve Samsung Electronics...
Cond In Temp. Sensor T_EI EVI In Temp. Sensor T_EO EVI Out Temp. Sensor Liquid Tube Temp. Sensor T_CT1 Comp. Top Temp. Sensor T_CT2 Comp. Top Temp. Sensor Ambient Temp. Sensor SV_G Gas Pipe Service Valve SV_L Liquid Pipe Service Valve Samsung Electronics...
Suction Temp. Sensor T_CO Cond Out Temp. Sensor T_EI EVI In Temp. Sensor T_EO EVI Out Temp. Sensor Liquid Tube Temp. Sensor T_CT Comp. Top Temp. Sensor Ambient Temp. Sensor SV_G Gas Pipe Service Valve SV_L Liquid Pipe Service Valve Samsung Electronics...
25. Control box temp. Sensor : Control box internal temperature measurement, thermal protection used for the control. 26. Receiver : Storing the refrigerant piping system, a stable liquid refrigerant supply 27. Liquid Tube Valve : Refrigerant in the outdoor unit side, the indoor unit during heating operation to rotate the valve operation. 7-22 Samsung Electronics...
Outdoor unit address: No 4 Sub unit 3 Setting can be done from Main unit only. Ex) When 3 MCUs are installed → SW57: 3, SW57 Setting total number of connected MCU When 10 MCUs are installed → SW57: A Samsung Electronics...
Page 271
Minimum temperature of entering water -5 °C must be below -8 °C) Anti-freeze circulation (freezing point of anti-freeze Minimum temperature of entering water -10 °C must be below -15 °C) ※ Maintain appropriate concentration level of anti-freeze according to SW58 switch setting. Samsung Electronics...
Page 272
K4 x n times Ones digit (0 ~ 9) * K4: Press for 2 seconds - automatic detection of MCUs' quantity K2: long Step9 Save Restart * Press K1 for 2 seconds to exit without save regardless of setting step. Samsung Electronics...
Page 273
- K4 switch is pressed for a long time, all options settings return to the factory settings, but the settings are saved is not. K2 switch is pressed for a long time, 7-Segment enters the tracking mode and the settings will be saved. Samsung Electronics...
Page 274
-- If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored setting is saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress, setting will be saved. Samsung Electronics...
Page 275
-- If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored setting is saved Press and hold the K2 button When the segments shows that tracking mode is in progress, setting will be saved. Samsung Electronics...
When equivalent length of farthest is set) LEVEL 2 indoor unit from the outdoor unit is over 170m Disabled (Factory default) Energy saving mode triggers when Energy saving setting Main the room temperature reaches Enabled desired temperature while operating in heating mode. Samsung Electronics...
Page 277
When outdoor unit is over 80 m type 1 (Indoor unit is lower than outdoor above the indoor unit unit) Height difference type 2 When indoor unit is over 30 m (Outdoor unit is lower than indoor unit) above the outdoor unit Samsung Electronics...
Page 278
(DMS, S-NET 3, etc) Disable This function is not applicable for Disable Main Disable this model Disable (Factory default) 7-10 V Circulation water Individual When variable flow control valve is flow control 5-10 V applied 3-10 V Samsung Electronics...
Page 279
1 (Indoor unit is lower over 80m above the indoor than outdoor unit) unit Height difference type 2 When indoor unit is over 30 m (Outdoor unit is lower than above the outdoor unit indoor unit) 8-10 Samsung Electronics...
Page 280
Restrict excessive capacity Enabled (Factory default) Max capacity increase when operating Main restriction indoor units with small Disabled capacity. If the gas leak occurred it Disabled (Factory default) Gasleak Main should be entered in the Pumpdown Enabled pumpdown operation. Samsung Electronics 8-11...
Page 281
Key Options 8-3 How to check the view mode using a tact switch ■ AM080~260SXVSSS 8-12 Samsung Electronics...
Page 282
AUTO Indoor unit : "A","0" times automatic address automatic address Adress(ex. 07) MCU : "C","1" SEG1,2 SEG3,4 The device receives The device receives MANU times a manual address a manual address Indoor unit : "A","0" Adress(ex. 15) Samsung Electronics 8-13...
Page 283
Display method of automatically assigned address in K4 View mode. (EX : "MANU"→ "A004" →"MANU" →"A005" →"MANU" →"A006") Display Page 1 Page 2 SEG 1 SEG 2 SEC 3,4 MANU Indoor unit : "A" Indoor unit : "0" Address (No. 1→01) 8-14 Samsung Electronics...
'Discharge mode of DC link voltage'. Display on segment KEY operation (Number of press) 1 time Intialize (Reset) setting Same as initial state Samsung Electronics 8-15...
Page 285
8 times AUTO Indoor unit: “A” Indoor unit: “0” Address units MCU: “C” MCU: “1” (ex: 07) SEG4 SEG5 SEG6 9 times Manually assigned address of the units MANU Address Indoor unit: “A” Indoor unit: “0” (ex: 15) 8-16 Samsung Electronics...
- Check the Indoor and Outdoor abnormal noise. - Check the drainage of the Indoor Unit cooling operation. - More operation : Checking status by using the S-NET. (5) Refer to manual and explain air conditioner usage to user. Samsung Electronics...
Page 287
- Oblique line marked area in the during operation of the system can be protection control. (Auto Trial Operation of normal judgment can be difficult by the protection control operation.) - If out of warranty coverage and the boundary area : Auto Trial Operation judgment accuracy may be reduced. Samsung Electronics...
Must be carried out Auto Trial Operation after 1 hour from final operation stopped. (In this case, the vacuum mode of the air must maintain for more than 5 minutes.) - Restart of Auto Trial Operation after troubleshoot the item that "Undetermined" Samsung Electronics...
- If the Indoor temperature setting by wired remote control : Carried out the Auto Trial Operation after setting the Temperature sensor of Indoor Unit. - Indoor Unit of outdoor air introduction : Will be excluded from the Indoor air temperature, EVA In / Out Temperature sensor checking. Samsung Electronics...
Page 290
Outdoor Unit Temperature sensors, less than 10℃? Complete [Caution] - If the Outdoor Unit with a history of operation (Auto Trial Operation inclusion) : Must be carried out Auto Trial Operation after 1 hour from final operation stopped. Samsung Electronics...
Page 291
O the vacuum mode (All of the Outdoor Unit) Complete [Caution] - If the judgment of Pressure sensor "Undetermined" : Display the error to all of the Outdoor Unit and then Auto Trial Operation is exited. (Stop the overall system) Samsung Electronics...
Page 292
/Min deviation : less than 2" O the vacuum mode of Outdoor Unit Complete [Caution] - If the Outdoor Unit with a history of operation (Auto Trial Operation inclusion) : Maintain the vacuum mode for more than 5 minutes. Samsung Electronics...
Page 293
1) When closed Main EEV opening : Compressor suction degree of overheat impossible to ensure and less than DSH 20K. 2) When opened Main EEV opening : Compressor suction degree of overheat is high status. 3) Main EEV : Refer to the Service Manual. - Pressure sensor abnormal symptoms : Refer to the Service Manual. Samsung Electronics...
Page 294
CT Replace Inverter PCB sensor have the same value? Is refrigerant Is Compressor current(CT) value normal? in the system properly? Adjusts the refrigerant (Addition / Emitted) IIs operation current of Compressor normal? Replace Compressor Complete Samsung Electronics...
Page 295
Temperature(℃) When Auto Trial Operation, does maintain Thermo On status of Indoor ventilation Indoor Unit? 11.2 18.5 32.0 59.0 200.0 Adjusts the refrigerant Is refrigerant in the system properly? 242.0 (Addition / Emitted) 362.0 553.0 Complete 9-10 Samsung Electronics...
Page 296
Is 4Way Valve coil normal? (Wire breaking, operation impossible, etc.) Replace Valve coil Is PCB Output signal normal? Replace PCB Replace 4Way Valve Body (Retry the Auto Trial Operation : If the continuous "Undetermined" is displayed.) Complete Samsung Electronics 9-11...
Page 297
Is PCB Output signal normal? Replace Hub PCB Replace Main EEV Complete ※ Main EEV coil resistance value based (Measured temperature is 20°C) Operating Resistance of Voltage between the EEV Wiring Diagram (VDC) phase ( ) 9-12 Samsung Electronics...
Page 298
Service Valve is closed Refer to "Service Valve" Dedicated Error Code E505 High pressure sensor breakdown Refer to "High / Low pressure sensor E506 Low pressure sensor breakdown (Module installed)" ※ Other error codes : Refer to Service Manual. Samsung Electronics 9-13...
● Deficiency of Over-cooling : After the 10% addition of calculated total refrigerant amount, retry Checking the amount of refrigerant. ● Undetermined : Checking the amount of refrigerant confirms that is performed in warranty temperatures area. Ensure that there is no other problems in the system by Test Operation. 9-14 Samsung Electronics...
J : 460V, 60Hz, 3Φ Ex. H : 2014 V : DVM Inverter J : 2015 W : Outodoor K : 2016 M : 2017 Grade A : Standard+General+Module G : High+General Temp.+Module H : High+Low temperature+Module S : Flagship+General Temp.+Module Samsung Electronics 9-15...