4
Screw eight nuts to the suspension bolts making space for hanging the
indoor unit.
You must install the suspension bolts more than four when
installing the indoor unit.
5
Check the level of the indoor unit by using a leveler.
A tilt of the indoor unit may cause malfunction of a built-in float switch
and water leaks.
6
Adjust the height of the indoor unit by using the gauge of dimensions.
You should adjust the gauge of dimensions and the pattern sheet to fit
the cutting dimensions of ceiling.
Make sure that the indoor unit is installed at a level if the indoor unit
slants too much, there can be water leaks.
Side view
Air inlet
Air outlet
Gauge of Dimensions
7
Tighten the upper part nuts.
8
Remove the gauge of dimensions after installing the indoor unit.
Unit : mm(inch)
Ceiling
Nut
Washer
Rubber
Fasten the nut
Level