CASSETTE TYPE AIR CONDITIONER Operation & Installation Manual Please read this operation manual before using the air conditioner. Please keep this manual carefully and safely. No.0010576976 B AB092ACBJA AB122ACBJA AB142ACBJA AB182ACBJA AB142ACBFA AB182ACBFA 051220***,*AB092/122ACBIA*** **AB092/122ACBJA*******...
Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier. Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.
Cautions Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet and swing louver. Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.
There is a telecommunication interface for remote control on the operation panel of the indoor unit. After the peripheral equipment have been installed in accordance with the instruction manual of the selected remote control detector, the air conditioner will be computerized and controlled from a distant away place.
Setting Method: When the remote controller is on (excluding timer mode and fan mode),press the ìSLEEPî button on the remote controller 10 times within 5 seconds,and after the buzzer sounds 4 times, the air conditioner will enter the state of auto- restant function Cancel Method:Press the ìSLEEPî...
Part Name Indoor unit Swing louver (Air flow direction can be adjusted by using the SWING button on the remote controller) Air Inlet Grille Air Filter (Inside of the Inlet Grille) Operating Control Panel COMP TIMER OPER POWER outdoor unit Air inlet Air outlet Operating Control Panel...
Safety Precautions Carefully read the following information in order to operate the air conditioner correctly. Below are listed four kinds of Safety Precautions and Suggestions: WARNING: Incorrect operations may result in severe consequences of death or serious injures. Incorrect operations may result in injures or machine damages; in some cases may CAUTION : cause serious consequences.
Use discharge pipe correctly to ensure efficient discharge. Incorrect pipe usage may cause water leaking. Air conditioner canít be be installed in the environment with inflammable gas. The inflammable gas near air conditioner may cause fire hazard. Installed electrical-leaking circuit breaker.
Maintenance Clean the unit Turn off the power supply switch Take down air inlet grille As the figure, press the two locks on air inlet grille vertically, and make it move to grille, then rise it up 45 degree gently to take out the grille. Take down the filter Press the outside two edges of inlet grille with the thumbs, and pull out the filter corner with the...
Stop operation and turn off the power supply switch .Electric power is consumed even the air conditioner is in state. Clean the air filter, indoor unit and outdoor unit,and cover the unit with dustcoat.
Insufficient cooling Sunlight direct into the room ? When the air conditioner does not operate properly after you have checked the above-mentioned items or when following phenomenon is observed,stop the operation of the air conditioner and contact your sales dealer: The fuse or breaker often shuts down.
Customer Need-to-know Customer Need-to-know Please install the air conditioner according to the requirements specified in this manual to ensure the air conditioner works well. Be careful not to scratch the surface of the case when moving the air conditioner. Please keep the installation manual for future reference when maintenance and changing installation place.
Installation Tools Installation tools The installation tools listed in the following sheet can be used as required. 1. Screw driver 2. Hacksaw 3. Drill with a diameter of 60mm 4. Inner hexagon spanner,shifting spanner 5. Spanner (14, 17, 19,24,27mm) 6. Pipe cutter 7.
Installation Procedures 1.Selection of Installation Place (1) Place above the ceiling where it is enough space to arrange the unit. (2) Place where the drainage pipe can be arranged well. (3) Place where inlet and outlet air of indoor and outdoor unit will not be blocked. (4) Do not expose the unit to the place with heavy oil or moisture (e.g.kitchen and workshop).
Installation Procedures (3) Install a suspending bolt To support the unit weight ,anchor bolt should be used in the case of the existing ceiling. For new ceiling, use flush-in type bolt, built-in type bolt or parts pretared in the field. Before going on installing, adjust the distance to ceiling.
Installation Procedures 4. Installation of water drainage pipe (1) Install water drainage pipe Pipe diameter shall be equal or larger than that of connecting pipe (Pipe of polythene; size: 25mm; O.D.: 32mm ) Drainpipe should be short, with a downward slope at least 1/100 to prevent air bag from forming. If downward slope of drainpipe cannot be made,lifting pipe shall be installed.
Installation Procedures 6. Installation of Ornament Panel Install ornament panel on indoor unit (1) Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and check that the dimension of the ceiling opening is correct. Take off the lever gauge before installing the ornament panel.
Page 19
Installation Procedures (1) Dimension of connecting pipe Gas pipe 15.88mm Liquid pipe 9.52mm Gas pipe 12.7mm Liquid pipe 6.35mm Fit the nut on and fasten (2).Pipe cutting and expanding Must remove burrs if cut pipes with pipe cutter. Expand flare after insert the pipe expander. Diameter of pipe 6.35mm (1/4î) Liquid pipe...
Page 20
After attaching the each caps, check the gas leakage around the caps. CAUTION: If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out, then charge the liquid refrigerant into air conditioner according to the amount marked on the nameplate.
Electrical Wiring Cautions: Use copper wire only.Parameters of connecting line : H05RN-F 3G2.5mm +H05RN-F 1x0.75mm Power supply :1PH,220-230V~,50Hz. For AB092ACBJA,AB122ACBJA,AB142ACBJA,AB182ACBJA, the power supply connected from outdoor unit. For AB142ACBFA,AB182ACBFA, the power supply connected from indoor unit. 051220********092/122***** Wiring methods: 1.Wiring method of ring terminal...
Installation Procedures Wiring connection AB092ACBJA AB122ACBJA: INDOOR UNIT TERMINAL BLOCK OUTDOOR UNIT TERMINAL BLOCK Note: Mark of outdoor unit terminal block 1(N) is equal to 1(L); and 2(L) is equal to 2(N). AB142ACBJA AB182ACBJA: INDOOR UNIT TERMINAL BLOCK ******* OUTDOOR UNIT...
When the air conditoner is started, when the compressor starts or stops during operation or when the air conditioner is stopped,it som- etimes sounds ì Bi- Bi-î or ìGodo-Godoî. It is the flowing sound of the refrigerant , not a malfunction.
During heating,indoor fan is still running even unit is stopped. Please check the following things about your air conditioner before making a service call. Is the power supply switched on ? Power supply switch is not in ON position.
Check and Test Run Installation check and test run Require customers to use air conditioner according to the operation manual. The items checked during test run,please mark No gas leakage on the pipe joint ? How about the thermal insulation of the pipe joint:...