® ODEN ELECTRIC ACTUATORS P50R P220R And P500R ´ S GUIDE INSTALLATION AND MAINTENANCE MANUAL Oden P50R Copyright Oden Control AB (publ.) Version GR 2003-10-26...
Content: 1.0 General information ® Oden 1.1 The family 1.2 Operation and safety instructions 2.0 Technical description 2.1 Basic Unit 2.2 Spindle Adapter 2.3 Adapter consoles and screws 2.4.1 Connection board A 2.4.2 Connection board B 2.4.3 Connection board C 2.5 High temperature version—W 3.0 Mechanical installation 3.1 Acceptance control...
Actuators). Local regulations concerning technical equipment The P50R, P220R and P500R range are must be observed when installing and/or maintaining actuators. but can also be used as multi the actuator. Necessary steps to prevent any accidents turns actuators with a maximum working must be taken.
® The Oden actuator consists of : No potentiometer or battery are used to 2.1 Basic Unit remember this position value, nor limit switches or other sensitive electro-mecha- nical components. The unit consists of a sealed aluminium housing with a step-motor, a reduction gear- The reduction gearbox is based on the patent box, electronics and terminal blocks.
C — +90 tools are necessary: is also available. This Basic Unit is called P50W/P220W or P500W. P50R: The internal electronic is protected in a Spanner, 24 mm (cable inlets) separate tight box, which is connected to the Hexagon key, M5 (terminal lid) Basic Unit by a shielded cable.
But in spite of that many valve manufacturers still have their own A max A min ® standards, and Oden has designed adapters Oden P50R 52 mm 20 mm to the most common valves on the market. 79 mm 30 mm Oden P220R 3.3.3 Mechanical control...
will in any case not damage the actuator. enclosed rubber washer. (Warranty Notice the warning label on the hand-wheel. condition) Careless handling will damage the valve or the actuator. 5. T HE CALIBRATION - PC/PC SYSTEM As an extra protection against overloading the P50 can be delivered with a slipping coupling.
forces in the valve). The automatic 20-minutes valve normally does not have) or if the valve is calibration will avoid such occurrence. too sensitive for the calibration torque/force (for example the valve will jam at closed position), but yet you require the programmed The electronics will remember the calibration control torque/force, then we recommend position at a power break.
Position Calibration. move. Read the mA-value. Decrease the control signal very slowly until the valve 5.3 Summing up of the spindle starts to move in the other direction. Read the mA-value. The signal difference is a PC / PC – calibration system measure of the system backlash (positioning Using Power Calibration: accuracy).
Page 10
valve can cause problems depending on the making starting attempts continuously during lack of valve lange and spindle standards a long time period, which may cause fatigue damages to the valve or to the Actuator. accepted by the valve manufacturer. ®...
Page 11
Patent protected in all major countries. US patent 5,913,744 Oden Control AB (publ.) Phone: (+46) 08 767 76 57 Nilstorpsvägen 53 Fax: (+46) 08 767 47 18 181 47 LIDINGÖ E-mail: sales@odencontrol.se Sweden Version GR 2003-10-26...