Page 3
Item Unit Outdoor Unit Type Hermetic Motor Compressor Motor Type Brushless (4-poles) Rated Output 3.00 Type Propeller Fan Material Motor Type DC (8-poles) Input Power — Output Power Cooling: 600 (Top), 640 (Bottom) Fan Speed Heating: 520 (Top), 560 (Bottom) Fin material Aluminium (Pre Coat) Fin Type...
Page 4
Item Unit Indoor Unit Performance Test Condition EN 14511 Cooling: 16 ~ 43 Outdoor Ambient °C Heating: -28 ~ 25 Operation Range Cooling: 5 ~ 20 Water Outlet °C Heating: 20 ~ 55 (Below Ambient -15°C) 20 ~ 60 (Below Ambient -10°C) Cooling: 36 Internal Pressure Differential Heating: 52...
Features Inverter Technology - Energy saving High Efficiency Environment Protection - Non-ozone depletion substances refrigerant (R410A) Long Installation Piping - Long piping up to 30 meter with height difference 20 meter - Flexible 4-way piping for outdoor unit ...
Main Components Cabinet front plate Cabinet front plate (2 pieces) Remote controller Single Phase RCCB/ELCB (Main Power) Single Phase RCCB/ELCB (Backup Heater) Control board cover Control board Flow sensor Air purge valve Backup heater Overload protector (2 pieces for SXC09*3E5 or 3 pieces for SXC12*6E5) Expansion vessel Pressure relief valve...
Dimensions Indoor Unit <Top View> <Front View> <Side View> 58.9 141.9 326.9 <Bottom View> 424.5 404.1 54.6 69.5 437.3 Relative position between the indoor unit and the installation plate <Front View> More than 375 More than 375 Wall Wall Installation plate Indoor Unit body...
Refrigeration and Water Cycle Diagram Outdoor Indoor Side Side Water Pressure Gauge Expansion Liquid Vessel Water Capillary Side Flow Expansion (3-Way Tube Sensor Valve Strainer Strainer Valve) Subcooler Water Inlet (Connect Water Pipe Pump Sanitary Temp. Tank) Sensor Expansion Strainer Pipe Defrost Valve...
Page 11
WH-SXC12H6E8 EXTERNAL COMP. SW HEAT/COOL SWITCH SG SIGNAL SOLAR TEMP. SENSOR DEMAND SIGNAL WATER TEMP. ZONE 1 WATER TEMP. ZONE 2 POOL TEMP. SENSOR BUFFER TANK SENSOR ROOM TEMP. ZONE 1 ROOM TEMP. ZONE 2...
Installation Instruction The centre of installation plate should be at more than Indoor Unit 375 mm at right and left of the wall. The distance from installation plate edge to ground should more than 1556 mm. Select the Best Location ...
2. Gently pull the lower section of the front plate This water circuit must comply with all relevant towards you to remove the front plate from left and European and national regulations, i.e. IEC/EN right hooks. 61770. 3. Hold the left edge and right edge of front plate to ...
If necessary, use hose clamp to further tighten the hose at drain hose connector to prevent leakage. Spanner or Water will drip from this hose, therefore the outlet Wrench Torque wrench of this hose must be installed in an area where the outlet cannot become blocked.
Page 16
Terminals on the Outdoor Unit Colour of wires (Connecting cables) Terminals on the Indoor Unit (Power Supply Cord) Indoor Unit/ Terminals on the isolating Outdoor Unit devices from power supply connection (Disconnecting means) Power Supply 1 Power Supply 2 Screws RCCB/ELCB Terminal Board Screws...
Connecting Requirement Remote Controller Wiring For SXC09*3E5/SXC12*6E5 Indoor unit The equipment's power supply 1 complies with IEC/EN 61000-3-12 provided that the short circuit power S is greater than or equal to 1700kW at Remote Controller the interface point between the user's supply and the public system.
Page 18
11.1.6.4 Mounting The Remote 11.1.6.5 Replace The Remote Controller Controller Cover For exposed type Replace the existing Remote controller cover with Preparation: Make 2 holes for screws using a driver. Remote controller cover to close the hole left after remove the Remote controller. 1.
Page 19
2. Set the Pressure Relief Valve level “DOWN”. Pressure relief valve Lever Turn up Pressure relief valve 3. Start filling water (with pressure more than 0.1 MPa (1 bar)) to the Indoor Unit via water inlet. Stop filling water if the free water flow through Pressure Relief Valve drain hose.
Page 20
Tank Sensor Resistant Vs Temperature How To Fix Cable 16000 14000 12000 Connecting with external 10000 device (optional) 8000 6000 All connections shall follow to the local national 4000 wiring standard. 2000 It is strongly recommended to use manufacturer- recommended parts and accessories for -30 -20 -10 installation.
Page 21
For connection to optional PCB Bind all Optional 1. By connecting optional PCB, 2 Zone temperature optional cables PCB 7 with these control can be achieved. Please connect mixing bands valves, water pumps and thermistors in zone 1 and zone 2 to each terminals in optional PCB. Bind optional Temperature of each zone can be controlled cables with...
Page 22
Tank sensor AW-A2W-TSOD (Total cable length Room sensor Outdoor air sensor shall be 30m or less) Outdoor air sensor Tank sensor Please use Panasonic specified part Tank OLP Buffer tank sensor Connection of Optional PCB Pool water sensor (CZ-NS4P) Solar sensor...
Page 23
Use for measurement of the solar panel This section explains about the external devices temperature. (optional) recommended by Panasonic. Please Insert the sensor into the sensor pocket and paste always ensure to use the correct external device it on the solar panel surface.
For optional pump. Power supply: AC230V/50Hz, <500W CN-CNT cable Recommended part: Yonos 25/6: made by Wilo For optional mixing valve. Power supply: AC230V/50Hz (input open/output close) Operating time: 30s~120s With Optional PCB Recommended part: 167032: made by Caleffi 2.
Page 25
5. Use the included cord clamp to fix the CN-CNT cable to the wall. Pull the cable around as shown in the diagram so that external forces cannot act on the connector in the adaptor. Furthermore, on the Indoor Unit end, use the included cable tie to fix the cables together.
Page 26
Outdoor Unit Select the Best Location If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed. Avoid installations in areas where the ambient temperature may drop below -20°C for UD models and -28°C for UX models.
11.5.2 Install The Outdoor Unit 11.5.2.1 Installation Diagram It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation, please consult authorized dealer/specialist. This illustration is for explanation purposes only. Vinyl tape (Wide) Saddle Indoor/Outdoor connecting cable - For UX09*E5*, UX12*E5*, UD12*E5*, UD16*E5* use 4-CORE WIRE...
Service panel Connecting The Piping CAUTION Do not over tighten, over tightening cause gas leakage. Piping size (Torque) Model Liquid Rear direction UX09*E5*, UX12*E5*, UD12*E5*, UD16*E5*, ø15.88 mm (5/8") Ø9.52 mm (3/8") UX09*E8*, UX12*E8*, Rear pipe panel [65 N•m] [42 N•m] UX16*E8*, UD09*E8*, UD12*E8*, UD16*E8* Side panel...
Page 29
Evacuation Of The Equipment WHEN INSTALLING AN AIR-TO-WATER HEAT PUMP, BE SURE TO EVACUATE THE AIR INSIDE THE UNIT AND PIPES in the following procedure. Liquid side Indoor unit Outdoor unit Two-way valve Close Gas side Three-way valve Vacuum pump Close adaptor Vacuum...
Page 30
8. Next, insert a small amount of same refrigerant into the system through the centre hose, until the pressure reaches about 1MPa (10 BarG). (Low/Gas) pressure gauge (High/Liquid) pressure gauge R-### An example illustrations of setup for refrigerant leak detection. Step 2: Refrigerant leak detection through Electronic halogen leak detector and/or ultrasonic leak detector: 1.
Connect The Cable To The Outdoor Unit (FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT) 1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed flexible cable (see below table), type designation 60245 IEC 57 or heavier cable.
WIRE STRIPPING AND CONNECTING REQUIREMENT Wire stripping Conductor not Conductor over Conductor fully Indoor/outdoor fully insert insert insert connecting terminal board 5 mm or more (gap between wires) ACCEPT PROHIBITED PROHIBITED No loose strand when insert Pipe Insulation 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
Page 33
Maximum pump speed setting on remote control Standard pump speed is automatically controlled to get the designed water temperature different between water inlet and outlet (∆T). Instead of setting the standard pump speed, maximum pump speed is manually adjusted by the installer according to water circuit pressure drop.
Page 34
WH-SXC12H6E5 WH-UX12HE5 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 15.000 14.000 13.000 12.000 11.000 10.000...
Page 35
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 12.000 11.000 10.000 9.000 8.000 7.000 (°C) Outdoor Temperature 5.500 4.500...
Page 36
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C Piping length : 7 m 18.000 16.000 14.000 12.000 10.000 8.000 (°C) Outdoor Temperature 5.500 4.500...
Page 37
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C Piping length : 7 m 15.000 13.000 11.000 9.000 7.000 5.000 (°C) Outdoor Temperature 5.500 4.500...
Page 38
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 13.000 12.000 11.000 10.000 9.000 8.000 Piping Length (m) 4.000 3.500 3.000...
Page 39
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 11.000 10.000 9.000 8.000 7.000 6.000 Piping Length (m) 3.800 3.700 3.600...
7000 2210 9230 2370 7000 1350 6250 2660 8550 2710 5600 1600 WH-SXC12H6E5 WH-UX12HE5 Water In (°C) Water Out (°C) Outdoor Air (°C) Capacity (W) Input Power (W) Capacity (W) Input Power (W) Capacity (W) Input Power (W) 10000 1750...