Page 2
Instruction manual AQ101, AQ101D, AQ110P, AQ01 2 (48 Revision History Revision Public EN_MV_1.0 Date 15. May 2020 Changes Revision Public EN_MV_1.1 Date 09. June. 2020 Changes Scheme 2a tripping matrix table is added. Scheme 2a dipswitch setting is added. Application example of scheme 2a is added.
Page 3
Instruction manual AQ101, AQ101D, AQ110P, AQ01 3 (48 Abbreviations HSO – High speed output BI – Binary input BO – Binary output CBFP – Circuit breaker failure protection QD – Quenching device IL – Phase current Io – Neutral sequence current LED –...
Instruction manual AQ101, AQ101D, AQ110P, AQ01 7 (48 1.1.2 AQ101D ARC FLASH PROTECTION RELAYS Figure 1-2: AQ101D din rail mounting Installation picture *) See panel cut-out dimensions on separate cut-out sheet included with this manual. See installation and mounting related technical parameters refer to chapter 8.1.
Instruction manual AQ101, AQ101D, AQ110P, AQ01 10 (48 Always ensure that current measurement circuits are not energized during disconnection. See rated voltages and connector tightening torques from chapter 7.1 “Technical data”. 1.2.2 AQ101, AQ101D ARC FLASH PROTECTION RELAYS Function Function Binary input 2 –...
Instruction manual AQ101, AQ101D, AQ110P, AQ01 12 (48 ONFIGURATION (AQ101, AQ101D, AQ110P) SWITCHES Functionality such as tripping logic is configured using dipswitch settings. Tripping may be selected based on arc light only or arc light and current thresholds. Scheme selection is made with dip switches by calculating the sum of weight factors 2.1.1 AQ101, AQ101D...
Instruction manual AQ101, AQ101D, AQ110P, AQ01 13 (48 2.1.2 AQ110P 2.1.2.1 Scheme 1a SW 1 Text Function at ON position Function at OFF position S1: L> / L> + I> Sensor 1 tripping with light only Sensor 1 tripping with light and criterion.
Page 14
Instruction manual AQ101, AQ101D, AQ110P, AQ01 14 (48 2.1.2.2 Scheme 1b SW 1 Text Function at ON position Function at OFF position S1: L> / L> + I> Sensor 1 tripping with light only Sensor 1 tripping with light and criterion.
Page 15
Instruction manual AQ101, AQ101D, AQ110P, AQ01 15 (48 2.1.2.3 Scheme 2a SW 1 Text Function at ON position Function at OFF position S1: L> / L> + I> Sensor 1 tripping with light only Sensor 1 tripping with light and criterion.
Instruction manual AQ101, AQ101D, AQ110P, AQ01 16 (48 (AQ110P OTENTIOMETERS ONLY Current pick-up setting (set point) is done with potentiometers on the back side of the device. Use flat head screw driver for moving the potentiometer to the desired set point. See chapter 4.1.2 for accurate setting of the current activation level. Figure 2-1: Current pick-up potentiometers.
Instruction manual AQ101, AQ101D, AQ110P, AQ01 17 (48 2.3.1 AQ101, AQ101D Scheme 0 S5** BI1* Table 2-5: AQ101 scheme 0 protection scheme logics. *) BI1 is common over current measurement channel. BI1 is necessary to be activated simultaneously with light sensors for making trip with light + current settings. Refer to DIP switch configuration.
Page 18
Instruction manual AQ101, AQ101D, AQ110P, AQ01 18 (48 Scheme 2a IL1-3 Table 2-7: AQ110 scheme 2a protection scheme logics. *) S5 is optional and may be used as fiber optic sensor input or quenching device control. Refer to the technical manual and ordering codes. **) T3 and T4 are mainly for fault location identification.
Instruction manual AQ101, AQ101D, AQ110P, AQ01 20 (48 PERATION AQ101, AQ101D, AQ110P ARC FLASH PROTECTION RELAYS 3.1.1 INDICATORS All the devices contain LED indicators for operating states as per the latter definitions. Color Steady ON Blinking Arcteq logo Blue Auxiliary supply Auxiliary power disconnected connected...
Page 21
Instruction manual AQ101, AQ101D, AQ110P, AQ01 21 (48 Color Steady ON Blinking Arcteq logo Blue Auxiliary supply Auxiliary power disconnected connected Power Blue Auxiliary supply Auxiliary power disconnected connected Error System healthy System failure Configuration mismatch. Protection partly operational. T1 / T2 / T3 / Normal status Corresponding trip relay activated...
Instruction manual AQ101, AQ101D, AQ110P, AQ01 22 (48 3.1.2 EXT POCKET All devices contain a text pocket for entering sensor specific information. Text pocket can be slide out and texts can be entered with a pen or with ready print paper or label.
Instruction manual AQ101, AQ101D, AQ110P, AQ01 23 (48 3.1.3 ET BUTTON All devices contain a set button in the front panel, which is used for installing the system, checking the number of connected sensors and units, resetting the device after trip event and clear the alarm signals. Figure 3-2: Set button.
Instruction manual AQ101, AQ101D, AQ110P, AQ01 24 (48 AQ01 ARC FLASH SENSOR Figure 3-3: AQ01 sensor configuration Sensor connectors are located at both ends of the sensor for series connecting maximum three sensors in one line. After connecting the sensor to relay, the ERROR LED turns on, and the appropriate sensor channel LED starts to blink.
Instruction manual AQ101, AQ101D, AQ110P, AQ01 25 (48 OMMISSIONING AQ101, AQ101D, AQ110P ARC FLASH PROTECTION RELAYS 4.1.1 YSTEM INSTALLATION When all the connections are done, the system shall be commissioned by installing the devices one by one by pressing the set button according to the instructions on chapter 3.1.3.
Page 26
Instruction manual AQ101, AQ101D, AQ110P, AQ01 26 (48 Light channel activation Figure 4-2: Light channel activation. Light channels are commissioned by applying strong light to the light sensor detector area. The same procedure applies also for fiber sensors. Applying light to the sensor. Corresponding light sensor channel LED lights steadily when light has been detected.
Instruction manual AQ101, AQ101D, AQ110P, AQ01 27 (48 4.1.3 CTIVATION OF OUTPUTS RIPPING Activation of output relays, electrical binary outputs and high-speed outputs (AQ110P only) is dependent on the application scheme of each device. Refer to chapter 2.3 for definition of scheme logics and related LED indicators in chapter Error! Reference source not found..
Instruction manual AQ101, AQ101D, AQ110P, AQ01 32 (48 ROUBLE SHOOTING AQ101, AQ101D, AQ110P ARC FLASH PROTECTION RELAYS Error led IF relay Led: State state state Possible issues Binary input Blink - Bad connection between sensors or other devices or Sensor connected to BI - Damaged wire - Unit amount or sensor amount changed...
Instruction manual AQ101, AQ101D, AQ110P, AQ01 34 (48 7.1.3 UXILIARY VOLTAGE Us (min-max): 85 – 265V AC / DC Us (nominal) 110, 220 V DC, 110, 115, 220, 230 V AC 50/60 Hz 18 – 72 V DC 24, 36, 48, 60 V DC Maximum interruption in normal operating state: 100 ms Maximum power consumption:...
Instruction manual AQ101, AQ101D, AQ110P, AQ01 35 (48 7.1.6 HSO1, HSO2 (AQ110P PEED UTPUTS ONLY Number Rated voltage 250 V DC Continuous carry 0.5 A Make and carry for 0.5s 15 A DC Make and carry for 3s 6 A DC Make and carry for 20s 2 A DC Breaking capacity DC, when time constant...