15. Exploded Views and Parts List ..................... 5-1 RHF025EE ............................5-2 RHF035EE/RHF050EE/RHF080EE/RHF100EE ................16. Electrical Parts List ........................6-1 MAIN PCB ............................17. Wiring Diagram ..........................18. Schematic Diagram ........................19. Circuit Descriptions ........................9-1 PCB Circuit Descriptions ........................Samsung Electronics...
Page 3
14-1 Ventilator Operation Priniple 14-1 ....................... 14-2 Index for Model Name 14-2 ......................... 14-3 Cleaning the Dust Filter 14-3 ........................ 14-4 Cleaning the Heat Exchange Element 14-5 ..................14-5 Q & A for Non-trouble 14-7 ........................14-6 Terminology 14-8 ............................ Samsung Electronics...
– If the product is installed out of the insulation, it may result in electric shock or malfunction due to moisture generated in the product. ● Do not install the product in humid place such as bathroom. – It may cause electric shock or malfunction. Samsung Electronics...
– Stop operating and turn off the unit when it smells burning or any error in operation is found. Contact a dealer or a qualified installer. If continue operation of the unit, electric shock, fire or unit falling may occur. Samsung Electronics...
● Make sure air fan stops rotating before cleaning and other treatment. – If not, it may cause electric shock or injury. ● Do not utilize steel scrubber or chemicals such as benzene or thinner. – It may cause discoloration or unit falling. Samsung Electronics...
■ Operation at Cold Area Optimized automatic ventilation operation is conducted to prevent condensation and air volume reduction. ■ Low Noise and Low Power With highly efficient motor and optimized system design, operation noise and electric consumption is minimized. Samsung Electronics...
Page 8
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro- mote high efficiency energy devices, Trial Operation Conditions [Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB) [Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB) 3. Duct length refers to its size when friction loss coefficient stands at 0.02 Samsung Electronics...
Page 9
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro- mote high efficiency energy devices, Trial Operation Conditions [Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB) [Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB) 3. Duct length refers to its size when friction loss coefficient stands at 0.02 Samsung Electronics...
Page 10
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro- mote high efficiency energy devices, Trial Operation Conditions [Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB) [Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB) 3. Duct length refers to its size when friction loss coefficient stands at 0.02 Samsung Electronics...
Page 11
Performance Ventilation Method Type 1(Supply, Exhaust) Type 1(Supply, Exhaust) Element 1EA (Cellulous) 1EA (Cellulous+Plastic) Remote Controller Digital Wired and LCD Switch Exterior Chasiss Installation Method Ceiling Type (Fill up) Ceiling Type (Fill up) High Efficient Energy Device Authorization Samsung Electronics...
Page 12
Element 2EA (Cellulous) 2EA (Cellulous) 2EA (Cellulous+Plastic) Remote Controller Digital Wired and LCD Wired and LCD Switch Exterior Chasiss Installation Method Ceiling Type (Fill up) Ceiling Type (Fill up) Ceiling Type (Fill up) High Efficient Energy Device Authorization Samsung Electronics...
Page 13
Wired and LCD Switch Exterior Chasiss Installation Method Ceiling Type (Fill up) Ceiling Type (Fill up) Ceiling Type (Fill up) High Efficient Energy Device Authorization 2-4 Option Specifications Item Descriptions Code-No. Q'TY Remark MWR-VH01 ERV Wired Remocon Sold Separately (DB97-03447E) Samsung Electronics...
Page 14
• Check PCB PATTERN OPEN/SHORT • Check MOTOR SA (SUPPLY AIR) • Check PCB connection Fan Motor error • Check WIRE disconnection • Check MOTOR EA (EXHAUST AIR) • Check PCB connection Fan Motor error • Check WIRE disconnection Samsung Electronics...
Page 15
100 • Check DAMPER SWITCH seconds while monitoring the • Check PCB connection • Check WIRE disconnection damper) ✳ 602~609 indicate errors due to ERV wired remote control. Refer to the ERV wired remote control installation manual. Samsung Electronics...
Page 16
3-2 Option Switch & Key Function Address Display Operation KEY Address Set up Optional Switch Set Up SW01 SW02 SW05 SW06 SW07 Samsung Electronics...
Page 17
■ RMC ADDRESS Setup • RMC ADDRESS setup refers to ADDRESS setup switch needed to control ventilator with centralized controller. • RMC ADDRESS setup is not required in case of centralized control. Indoor unit RMC ADDRESS Number on the centralized controller Samsung Electronics...
Page 18
✳ All switches are set to ON position at the time of shipping. If switches are set to on your own in case of installation, it may cause operation errors. Make sure set the switches to ON/OFF position according to the manual. Samsung Electronics...
Page 19
SEG3 : If MASTER is set, MAIN ADDRESS of transmitting SLAVE appears. If SLAVE is set, its MAIN ADDRESS appears. SEG4 : If MASTER is set, MAIN ADDRESS of receiving SLAVE spears. If SLAVE is set, its RMC ADDRESS appears. Samsung Electronics...
Page 20
Exhaust Air FAN RPM 1,350RPM Supply Air FAN RPM 950RPM Turn Off Indoor Temperature 25°C Turn Off Outdoor Temperature 30°C Turn Off Density 1,220ppm Installed Unit Number 3 unit Turn Off Turn Off ■ Numbers and Alphabets on PCB Display Samsung Electronics...
Page 22
Ass’y Cabi 1) Remove the 3 bolts on Cover Element to Cover Element detach it.(Use +Screw Driver.) 2) Loosen the clips connected to the Cover. 3) Separate the connector connected to the Damper by pulling out the connector body. Samsung Electronics...
Page 23
Ass’y Element 1) Pull up the 2 strings hanging out from the 2 ends of Element to detach the Element. Bracket Body 1) Remove the 4 bolts and separate Bracket Element, A Body Element, A. (Use +Screw Driver.) Samsung Electronics...
Page 24
Procedure Remark Cushion Bypass 1) Slide Cushion Bypass to the direction seen in the picture besides. Take caution not to break down EPS structure. 2) Find Wire connected to the temperature sensor. Separate the 2 temperature sensor connectors. Samsung Electronics...
Page 25
Parts Procedure Remark Cabi Cover 1) Detach Cabi Cover by removing 9 bolts. (Use +Screw Driver.) Cushion Mid 1) Slide Cushion Mid to the direction seen in the picture besides. Take caution not to break down EPS structure. Samsung Electronics...
Page 26
The bolts are not required to be removed. 4) Detach the whole Ass’y Blower Motor (which is made up of Fan, Motor, Bracket Motor, and Cover Bell Mouse). 5) 2 Motors are placed within the unit for input and outlet. Samsung Electronics...
Page 27
1) Unscrew the nuts fixing Fan by rotating them right. (Use Monkey Spanner.) Do not touch the Fan. Its sharp edge may cause injury. 2) Detach the Motor with removing the 4 bolts fixing Bracket. (Use +Screw Driver.) Samsung Electronics...
Page 28
Procedure Remark Ass’y Case Blower 1) Remove the 2 bolts attached at the sides of the body. (Use +Screw Driver.) 2) Remove the 4 bolts on the other side of Cabi Cover to detach it. (Use +Screw Driver.) Samsung Electronics...
Page 29
Disassembly and Reassembly Parts Procedure Remark 3) Detach the Ass’y Case Blower. 4) Unscrew the Bracket Case Blower and the Case Blower. (Use +Screw Driver.) Samsung Electronics...
Page 30
Disassembly and Reassembly Parts Procedure Remark Ass’y Damper/ 1) Remove all bolts to separate Bracket and Ass’y-Lever Bypass Cam. (Use +Screw Driver.) Samsung Electronics 4-10...
Page 31
1) Remove the 3 bolts on Cover Element to Cover Element detach it.(Use +Screw Driver.) 2) Loosen the clips connected to the Cover. 3) Separate the connector connected to the Damper by pulling out the connector body. 4-11 Samsung Electronics...
Page 32
Disassembly and Reassembly Parts Procedure Remark Samsung Electronics 4-12...
Page 33
Parts Procedure Remark Ass'y Element 1) Remove the 4 bolts and separate Bracket Body Element, B. (Use +Screw Driver.) 2) Pull down the 2 strings hanging out from the 2 ends of Element to detach the Element. 4-13 Samsung Electronics...
Page 34
Take caution not to break down EPS structure. Cushion Mid 1) Slide Cushion Mid to the direction seen in the picture besides. 2) Separate the 2 temperature sensor connectors. Take caution not to break down EPS structure. Samsung Electronics 4-14...
Page 35
The bolts are not required to be removed. 4) Detach the whole Ass’y Blower Motor (which is made up of Fan, Motor, Bracket Motor, and Cover Bell Mouse). 5) 2 Motors are placed within the unit for input and outlet. 4-15 Samsung Electronics...
Page 36
(Use +Screw Driver.) 2) Find the Element and 2 Dust Filters. Ass’y Element 1) Detach Element and Filter from the unit. Ass’y Filter Make sure detach the Filter before the Element. 2) There are 2 Element within the product. Samsung Electronics 4-16...
Page 37
Each guide is attached to the product with 1 bolt. Thermistor 1) Separate the Temperature Sensor from Ass'y Wire the fixed part. The Temperature Sensor is attached with wire clips. 2) The input and output channel has 1 Temperature Sensor each. 4-17 Samsung Electronics...
Page 38
Cushion Mid 1) Slide the EPS structure to the side and detach it, as seen in the picture besides. 2) Slide and pull the EPS structure to separate it, as seen in the picture besides. Samsung Electronics 4-18...
Page 39
Cushion Mid. Put the part written with “Down↓” downwards and put the part with “Motor→” towards the Motor when assembling the unit. Make sure not to break down EPS structure. 4-19 Samsung Electronics...
Page 40
Remark Connector 1) Separate the Damper from the unit. Damper Cam (Use +Screw Driver.) 2) Separate the connectors by holding their bodies and pulling them out. 3) Unscrew bolts attached to Bracket and Cam. (Use +Screw Driver.) Samsung Electronics 4-20...
Page 41
1) Unscrew the nuts fixing the Fan by rotating them left. (Use Monkey Spanner.) 2) Unscrew the bolts fixing Motor to detach if from the Motor Bracket. It has 4 bolts. (Use +Screw Driver.) Do not touch the Fan. Its sharp edge may cause injury. 4-21 Samsung Electronics...
Page 42
2) Separate the Case Blower by sliding the Case Blower upwards. Cushion Blower-EA 1) Detach the EPS structure fixed to Case Cushion Blower-SA Blower by sliding the structure to the side. Make sure not to break down the EPS structure. Samsung Electronics 4-22...
Page 43
(Use +Screw Driver.) 2) Find the Element and 2 Dust Filters. Ass’y Element 1) Detach Element and Filter from the unit. Ass’y Filter Make sure detach the Filter before the Element. 2) There are 2 Element within the product. 4-23 Samsung Electronics...
Page 44
Each guide is attached to the product with 1 bolt. Ass’y Fan Parts 1) Separate motor connectors. 2) Loosen the holder fixing the motor wire by twisting it slightly. 3) 2 Motors are placed within the product for supply air and exhaust air. Samsung Electronics 4-24...
Page 45
Cushion Mid. Put the part written with “Down↓” downwards and put the part with “Motor→” towards the Motor when assembling the unit. Make sure not to break down EPS structure. 4-25 Samsung Electronics...
Page 46
Remark Connector 1) Separate the Damper from the unit. Damper Cam (Use +Screw Driver.) 2) Separate the connectors by holding their bodies and pulling them out. 3) Unscrew bolts attached to Bracket and Cam. (Use +Screw Driver.) Samsung Electronics 4-26...
Page 47
1) Detach the whole Ass’y Blower Motor (which is made up of Fan, Motor, Bracket Motor, and Cover Bell Mouse) through the inspection hole. 2) 2 Motors are placed within the unit for supply air and exhaust air. 4-27 Samsung Electronics...
Page 48
1) Unscrew the nuts fixing the Fan by rotating them left. (Use Monkey Spanner.) 2) Unscrew the bolts fixing otor to detach if from the Motor Bracket. It has 4 bolts. (Use +Screw Driver.) Do not touch the Fan. Its sharp edge may cause injury. Samsung Electronics 4-28...
Page 49
5. Exploded Views and Parts List 5-1 RHF025EE (Refer to 5-3p) 22-1 (Refer to 5-4p) 13-1 22-1 (Refer to 5-5p) 12-1 10-1 Samsung Electronics...
Page 60
FOAM-PU DB62-04167B INSULATION-ELEMENT FRONT FOAM-PU 30-3 DB63-01472A GUARD-ELEMENT SIDE DB63-01472B GUARD-ELEMENT SIDE 30-4 DB63-01473A GUARD-ELEMENT CENTER DB64-01473B GUARD-ELEMENT CENTER 30-5 DB64-01262A HANDLE-ELEMENT 30-6 6002-000488 SCREW TAPPING 30-7 DB96-06053A ASS’Y-SRE ELEMENT RECOVERY ELEMENT DB96-06055A ASS’Y-SRE ELEMENT RECOVERY ELEMENT Samsung Electronics 5-12...
Page 91
Indoor CO density Sense Operating Monitor Output Fan Motor Contorl Part Damper Motor Position Sense Damper Motor Control AC220V Output EXE Load Control Part AC220V Output Power Input AC220V This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 92
Indoor CO density Sense Operating Monitor Output Fan Motor Contorl Part Damper Motor Position Sense Damper Motor Control AC220V Output EXE Load Control Part AC220V Output Power Input AC220V This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 93
■ Sheet #1 DC310V DC12V DC5V SMPS Circuit Part Display Control Part Power Input 220V 60Hz Damper Control MICOM Motor Control Part EXE Control Sensor Circuit Part Comm. Circuit This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 94
Schematic Diagram Operating Instructions and Installation Schematic Diagram ■ Sheet #2 GRID Drive Circuit Address Set up Optional Switch Set Up This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 95
9. Circuit Descriptions 9-1 PCB Circuit Descriptions SMPS Circuit Part Motor Load Circuit Part Comm. Circuit Part This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 96
6. SWITCHING DIODE of secondary side should not utilize usual rectification DIODE because SWITCHING speed of SMPS reaches 130kHz. High speed SWITCHING DIODE is required. 7. SMPS stops operation if SHORT occurs post voltage of DC12V because of FEEDBACK from DC12V. Samsung Electronics...
Page 97
CONTROL IC of BLDC. It may cause SHORT of DC15V or DC310V. 6. If SHORT of DC15V or DC310V takes place, 2A FUSE (F702) opens and DC15V rectification DIODE may be damaged, which stops operation of SMPS. Samsung Electronics...
Page 98
: A-B>200mV : HIGH, B-A>200mV : LOW ● DATA is received and prepared with “R” PORT. When sending the DATA, HIGH is input at ENABLE. 4. EXCLUSIVE GATE Non-polar communication realization element to change signal LEVEL with utilizing INVERSE when connections is switched. Samsung Electronics...
Page 102
Dust filter protects heat exchange element and filter supplied air. ■ Electric Component Box It is made up of circulation of the unit. ■ Duct Connection Flange It refers to the pipe connected to the duct for supply air, outdoor air, indoor air and exhaust air. 11-1 Samsung Electronics...
Page 103
Dust filter protects heat exchange element and filter supplied air. ■ Electric Component Box It is made up of circulation of the unit. ■ Duct Connection Flange It refers to the pipe connected to the duct for supply air, outdoor air, indoor air and exhaust air. Samsung Electronics 11-2...
Page 104
If multiple ventilators are controlled by one ERV wired remote control only and an external controller is used to control one of the multiple ventilators, the ERV wired remote control will display the status of the randomly selected ventilator and it may differ from the status of some other ventilators. 11-3 Samsung Electronics...
Page 105
Heat-EX mode. 1. Press buttons once to set the On Timer. 2. Press buttons until the required time is displayed. Reservation 3. Press (Confirm/Cancel) button to complete Function On Timer the setting. -Turn On Samsung Electronics 11-4...
Page 106
Main Function(cont.) Function Mode Explanation Remark 1. Press buttons to set the Off Timer. 2. Press buttons until the required time is displayed. Reservation Function Off Timer -Turn Off 3. Press (Confirm/Cancel) button to complete the setting. 11-5 Samsung Electronics...
Page 107
Check assembly or replace motor Check whether outdoor temperature Wait until the outdoor temperature Operation at cold places If supply air fan or exhaust air fan are is below -15˚C reaches -15˚C not working Check outdoor temperature sensor Replace sensor (SHORT/OPEN) Samsung Electronics 12-1...
Page 108
Communication error between the wired remote control and the ventilator COM1/COM2 cross installation error Communication error by installing COM1 Dual MASTER Damper error ✳ 602~609 indicate errors due to ERV wired remote control. Refer to the ERV wired remote control installation manual. 12-2 Samsung Electronics...
Page 109
PCB, to measure resistance between the two electrodes. Is measured resistance a lot different from the value 12.1 specified by the table besides? 18.0 Outdoor temperature 27.3 thermistor disorder(replacement) 43.0 Restart the unit after having replaced PCB. Samsung Electronics 12-3...
Page 110
DATA once in six seconds. It waits for 5 seconds and conducts data check for one second. • CO sensor and LED 1 light up for 1 second when the sensor check DATA. • CO Sensor checks DATA ranges 400PPM~2,000PPM. • The process requires 2 second of preheating, during which, DATA can changes. 12-4 Samsung Electronics...
Page 111
PCB dislocated from PCB? Assembly connector Check product operation Does Motor rotate in case of operation? Is Motor RPM is lower than 120? Is DC0V~DC6V power measured from Motor ③↔⑤? Motor check or PCB check or replacement replacement Samsung Electronics 12-5...
Page 112
PCB dislocated from PCB? Assembly connector Check product operation Does Motor rotate in case of operation? Is Motor RPM is lower than 120? Is DC0V~DC6V power measured from Motor ③↔⑤? Motor check or PCB check or replacement replacement 12-6 Samsung Electronics...
Page 113
Reconnect communication line between Mster and Slave. Eliminate all communication connectors on Slave PCB and connect them again one by one. Find out the Slave interrupting communication and check its lines. Then, replace Slave PCB. Good +0.7V -0.7V Samsung Electronics 12-7...
Page 114
Reconnect communication line between Mster and Slave. Eliminate all communication connectors on Slave PCB and connect them again one by one. Find out the Slave interrupting communication and check its lines. Then, replace Slave PCB. Good +0.7V -0.7V 12-8 Samsung Electronics...
Page 115
Find out the SLAVE interrupting Set option switch again with pressing communication and check its lines. RESET KEY K3 of MASTER PCB for re-tracking. Then, replace SLAVE PCB. Replace MASTER PCB if tracking is not conducted. Samsung Electronics 12-9...
Page 116
Eliminate all PCB communication line and communication connectors on PCB and connect connector and replace PCB. them again one by one. Find out the ventilator interrupting communication and check its lines. Then, replace PCB. Good +0.7V -0.7V 12-10 Samsung Electronics...
Page 117
Store TEST Data at specific domain of EEPROM Read stored TEAT Data from the specific domain of EEPROM Does stored TEST Data match with read TEST Data? EEPROM TEST END EEPROM_Error_Count++ EEPROM_Error_Count<5 ERROR occurs. PCB check or replacement Samsung Electronics 12-11...
Page 118
Check operation Is AC220V power measured from Is DAMPER switch working? connector (CN72) ①↔③? PCB check or replacement PCB check or replacement Is OPEN/SHORT signal working at connector (CN51)? Switch check or replacement PCB check or replacement 12-12 Samsung Electronics...
Page 119
Eliminate all communication wired remote control PCB. connectors on ventilator PCB and connect them again Then replace PCB. one by one. Find out the ventilator interrupting communication and check its lines. Then, replace PCB. Good +0.7V -0.7V Samsung Electronics 12-13...
Page 120
Clean or replace the filter if it is damaged. Is filter working properly? Clean or replace the heat exchange element Is heat exchange element working properly? if it is damaged. Clean or replace the duct if it is damaged. Is duct working properly? 12-14 Samsung Electronics...
Page 121
12-4-15 When cold air is infused Is the unit infusing cold air? DAMPER → Heat-EX mode ? Control DAMPER (Change to Heat-EX mode) Is heat exchange element Check heat exchange element and fix it. working properly? Samsung Electronics 12-15...
Page 122
Are Filter well cleaned? Eliminate Dust or other substance. Are Heat Exchange Element well cleaned? Eliminate the substance. Is there any substance inside the Duct? Measure RPM and fix it. Is Fan Motor working properly? Replace or repair PCB. 12-16 Samsung Electronics...
Page 124
Address setup - MAIN - RMC Operation monitor output Damper Motor output Option setup switch External load control Power input DC smooth circulation BLDC Motor control - Supply Air Fan Motor - Exhaust Air Fan Motor 13-1 Samsung Electronics...
Page 125
ON/OFF indication control Operation monitor Central Error indication output controlle - Repeater - Central control, External load SENSOR control control circuit part Contact point output DC0.5V ~DC4.95V External control Indoor temperature SENSOR input Outdoor temperature SENSOR SENSOR Samsung Electronics 13-2...
Page 126
■ Heat-EX mode : Temperature and humidity of indoor air and outdoor air are exchanged (The function minimizes heat loss from the process of ventilation). ■ By-Pass mode : Ventilation process without exchanging heat of indoor and outdoor air. 14-1 Samsung Electronics...
Page 128
• If the dust filter is damaged, purchase it individually in a service center or an agency that you bought the product. • Make sure to turn off the sub power supply. 14-3 Samsung Electronics...
Page 129
• If the dust filter is damaged, purchase it individually in a service center or an agency that you bought the product. • Make sure to turn off the sub power supply. Samsung Electronics 14-4...
Page 130
• If the heat exchange element is damaged, purchase it individually in a service center or an agency that you bought the product. • Make sure to turn off the sub power supply. • Do not wash the heat exchange element. It may decrease its efficiency. 14-5 Samsung Electronics...
Page 131
• If the heat exchange element is damaged, purchase it individually in a service center or an agency that you bought the product. • Make sure to turn off the sub power supply. • Do not wash the heat exchange element. It may decrease its efficiency. Samsung Electronics 14-6...
Page 132
- Dust filter (Standard) : Clean the element with vacuum cleaner (once in 6 months) - Replacement period : • Once in 2 years (However, the replacement frequency varies according to environment.) • Remote control supports filter replacement alarm function 14-7 Samsung Electronics...
Page 133
Sleeping Mode It means Volatile Organic Compounds causing headache, breathing disorder and VOCs dermatitis such as paint and glue smells of new houses. Others It refers formaldehyde or formalin, the representative VOC together with HCHO benzene, toluene, xylene. Samsung Electronics 14-8...