ROOM AIR CONDITIONER AS-1808BR AS-2408BR SERVICE Manual AIR CONDITIONER CONTENTS 1. Installation 2. Disassembly and Reassembly 3. Troubleshooting 4. Exploded Views and Parts List 5. Refrigerating Cycle Block Diagrams 6. Wiring Diagrams 7. Schematic Diagrams E DB68-30986A(2)
E DB68-30986A(2) 1. Installation 1-1 Refrigerant Refill • Fill the airconditioner with coolant, or refill when necessary during use. 1 Purge air(for new installation only). 2 Turn the 3-way valve clockwise to close, connect the pressure gauge(low pressure side) to the service valve, and open the 3-way valve again.
Page 3
1-2 "Pump down" Procedure • 'Pump down' shall be carried out when an evaporator is replaced or when the unit is relocated in another area. 1 Remove the caps from the 2-way valve (B) and the 3-way valve(A). Suspension hook High pressure 2 Turn the 3-way valve clockwise to close...
2. Disassembly and Reassembly Stop operation of the airconditioner and remove the power plug from the wall outlet before repairing the unit 2-1 Indoor Unit Parts Procedure Remark Front Grille 1) Stop the air conditioner operation and block the main power. 2) Seperate the tape of front.
Page 5
Parts Procedure Remark Filter Frame 1) Loosen the left and right screw of the Holder Filter, and Separate the Holder Filter. Ass'y Tray Drain 1) Do 1 2 , above. Separate the holder at the rear side of Indoor unit. 2) Take the display PCB out.
Page 6
Parts Procedure Remark Heat Exchanger 1) Do " 1 2 3 4 ", above. 2) Loosen the left screws of the heat exchanger. Lifting the heat exchanger up a little to push the up side for separation from the indoor unit Fan Motor and 1) Do "...
Page 7
2-2 Outdoor Unit Parts Procedure Remark Cabinet 1) Turn off the unit and remove the power cable 2) Remove the top cover. 3) Remove the control box cover. 4) Unplug the ass'y cable. 5) Remove the cabi-side. 6) Remove the cabi-front. * When you assemble the parts, check if the each parts and electric connectors are fixed firmly.
3. Troubleshooting 3-1 Items to be checked first 1) The input voltage should be rating Voltage ±10% range. The air conditioner may not operate properly if the voltage is out of this range. 2) The indoor unit and the outdoor unit shall be linked by 4 cables. Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
Page 9
3-2 Fault Diagnosis by Symptom 3-2-1 No Power(completely dead)-Initial diagnosis 1) Checklist : (1) Is input voltage normal? (2) Is AC power linked correctly? (3) Are connections between primary side, secondary side of the power transformer and PCB good. (4) Is output voltage of DC regulator IC KA7812(IC01) normal? (11.5VDC-12.5VDC) (5) Is output voltage of DC regulator IC KA7805(IC02) normal? (4.5VDC-5.5VDC) Troubleshooting procedure Remove power cord and plug in again in approx.
Page 10
3-2-2 When the Indoor Unit Fan Does Not Operate. (Initial Diagnosis) 1) Checklist : (1) Is input voltage normal? (2) Is the indoor unit fan properly connected(CN73)? (3) Is the starting codenser CR 71 properly soldered? (4) Is HALL IC in indoor fan motor properly connected(CN43)? (5) When in operation mode, does the indoor unit fan operate? 2) Troubleshooting procedure Remove power cord and plug in again in approx.
Page 11
3-2-3 When the Outdoor Unit Does Not Operate. (Initial Diagnosis) Checklist : (1) Is input voltage normal? (2) Is the set temperature of the remote control higher than room temperature in COOL mode? (3) Is the CONNECTOR-WIRE OUTDOOR linked correctly? (4) Is the indoor unit wire properly connected with the outdoor unit wire? Troubleshooting procedure Remove power cord and plug in again in approx.
Page 12
3-2-4 When the UP/DOWN Louver Motor Does Not Operate. (Initial Diagnosis) Checklist : (1) Is input voltage normal? (2) Is the UP/DOWN louver motor properly connected with the connector (CN61)? Troubleshooting procedure Remove power cord and plug in again in approx. 5 seconds. Check as in the procedure Is operating lamp blinking in 3 minutes and then lamp off? "No Power parts".
Page 13
3-2-5 If Operation By Remote Control Unit Is Impossible. (Initial Diagnosis) 1) Checklist : (1) Is operation selector switch of the indoor unit set at "REMOTE"? 2) Troubleshooting procedure Remove power cord and plug in again approx. 5 Seconds. Is operating lamp blinking in 3 minutes and then lamp off? Check as in the procedure "No Power parts".
4. Exploded Views and Parts List 4-1 Indoor Unit...
Page 16
Parts List Q’TY CODE NO Description Specification Remark AS-1808BR AS-2408BR DB92-10285M ASS'Y GRILLE ASS'Y DB64-40155A WINDOW FILTER DB64-70069A PANEL CENTER DISPLAY DB64-70068A PANEL LED CENTER DB64-70067A PANEL FRONT HIPS DB92-10287A ASS'Y GRILLE SUPPORT DB92-10289A ASS'Y SUPPORT RH DB63-10404E COVER SCREW M...
5.Refrigerating Cycle Block Diagram INDOOR UNIT OUTDOOR UNIT Capillary tube 2-way valve Liquid side Heat Heat exchanger exchanger (Evaporator) (Condenser) Gas side 3-way valve Cooling Compressor Gas leak check point Refrigerating cycle temperature and pressure STD Pressure Piping Temp. (°F ) Use Temp.
6. Wiring Diagrams 6-1 Indoor Unit AS-1808BR AS-2408BR...
Page 26
6-2 Outdoor Unit 6-2-1 AS-1808BR CAPACITOR 40uF / 2.5uF x 450VAC 6-2-2 AS-2408BR NAME TB1,2 TERMINAL BLOCK FAN MOTOR MAGNETIC CONTACTOR CAPACTOR FUSE(2A, 250V) SPARK-KILLER MODEL MOTOR & COMP CAPACITOR AS-2408BR 2.5/40uF X 450VAC...