Summary of Contents for Samsung AM080FXMDGH Series
Page 1
SYSTEM AIR CONDITIONER OUTDOOR UNIT Model Code : AM080/090FXMDGH AM080MXMDGH AM080MXMDGC AIR CONDITIONER CONTENTS 1. Precautions 2. Product Specifications 3. Disassembly and Reassembly 4. Troubleshooting 5. PCB Diagram and Parts List 6. Wiring Diagram 7. Cycle Diagram 8. Key Options 9.
Explain to workers that the battery for the remote control needs to be separated for storage purposes when the product will not be used for a long time. – This can cause a problem for the remote control since battery fluid may trickle out. Samsung Electronics...
If the compressor is operating while the refrigerant pipe is not correctly connected and the service valve is opened, then air and other substances can enter the pipe. The interior of the refrigerant cycle may then build up excessive high pressure resulting in explosion and damage. Samsung Electronics...
When load changes, capacity amendment that is soft by continuous operation of Dual Inverter is available. Step 1 Step 2 Capacity Step 3 Step 4 Variable Compressor driving : When load changes, is variable by fast inverter frequency. Amenities elevation : 0.5°C Samsung Electronics...
Page 7
- Refrigerant cooling system : Forced circulation / electric heat performance is high and control of (thermal conductivity is 10 times higher than air) load is available. Refrigerant cooling system : It is cooling technology of inverter circuit that use refrigerating cycle technology. Cooling of inverter circuit Samsung Electronics...
- Refrigerant cooling method Inverter PCB ← (Compressor - Magnet S/W Control PCB) Did Power Relay mount to PCB. 3 phase power EMI PCB ← EMI PCB - Fuse mount Communication Did Communication Terminal block ← Terminal block mount to PCB. Samsung Electronics...
Product Speci cations 2-1-3 Structure of product (DVM S ECO) Motor / Fan Control Box 4Way V/V ( Not available on cooling only model. ) Oil Separator Accumulator Heat Exchanger Gas Pipe Plate Heat Exchanger Compressor Liquid Pipe Samsung Electronics...
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. Samsung Electronics...
Page 11
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m). 5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m. Samsung Electronics...
MONKEY SPANNER -SCREW DRIVER NIPPER ELECTRIC MOTION DRIVER L-WRENCH For “disassembly and assembly” DVM PLUS Ⅳ indoor unit, please refer to the products with the same structures. Only those products that are not specified elsewhere are described here. Samsung Electronics...
1) Remove 3 screws. (use "+" screw driver) Top Cover 1) Remove 8 screws around cover. (use "+" screw driver) Cabi Front Install 1) Remove 1 screws (use "+" screw driver) and lift up to take off. Samsung Electronics...
Page 15
Remark Guard Cond 1) Take off the sensor. 2) Remove 4 screws. (use "+" screw driver) CABI BACK RIGHT 1) Take out the sensor wire through the hole on cabinet. 2) Remove 10 screws. (use "+" screw driver) Samsung Electronics...
Page 16
Disassembly and Reassembly Parts Procedure Remark CABI BACK RIGHT Cabi Back Install 1) Remove 1 screw. (using "+" screw driver) Samsung Electronics...
Page 17
Disassembly and Reassembly Parts Procedure Remark Cabi Front LF 1) Remove 10 screws. (using "+" screw driver) Samsung Electronics...
Page 18
(using "+" screw driver) 2) Pull out the connector on main pcb board. Bracket motor 1) Remove 2 screws to take off bracket cond. (using "+" screw driver) 2) Remove 2 screws on the base. (using "+" screw driver) Samsung Electronics...
Page 19
The follow step can be divided into 2 case 4) Case 1:Take off the control box directly without welding, a) Remove 2 screws that fix ing reactorwire. (using "+" screw driver) b) Pull out the connector as right pic. Samsung Electronics...
Page 20
2 screws that fix- ing pcb case. f) Band the handel of the case and take off the assy inverter pcb. (Reffer right pic) Becareful when take off inverter pcb;when reassemble should ensure the silicon grease thin and even Samsung Electronics...
Page 21
Discharge the refrigerant first; h) Weling two points as right picture;(using welding tool) 5) Remove 3 screws that fixing control box with partition and bracket valve. 6) Then you can take off the whole control box. Samsung Electronics...
Page 22
2) Separate 2 parts of the pipe using a welder Make sure the power is disconnected before work. Oil separator 1) Separate 2 parts of the pipe using a welder. 2) Unscrew and remove 2 mounting screws in oil separator. (Use + Screw Driver.) Samsung Electronics...
Page 23
Disassembly and Reassembly Parts Procedure Remark 4way valve 1) Separate 2 parts of the pipe using a welder. 2) Separate 2 parts of the pipe using a welder. Samsung Electronics...
Page 24
Disassembly and Reassembly Parts Procedure Remark 4way valve 3) Unscrew and remove 1 mounting screws in Assy bracket valve. (Use + Screw Driver.) 4) Unscrew and remove 2 mounting screws in Bracket accume. (Use + Screw Driver.) Samsung Electronics...
Page 25
Disassembly and Reassembly Parts Procedure Remark Cond Out 1) Unscrew and remove 3 screws on each side of the Ass’y Cond Out. (Use + Screw Driver) Samsung Electronics...
Page 26
Disassembly and Reassembly Parts Procedure Remark Compressor 1) Separate the flet from the compressor. 2) As shown in the picture, unscrew and remove 4 mounting screws from the bottom.(Use L-Wrench or Monkey Spanner or Socket Wrench) Samsung Electronics...
Page 27
Disassembly and Reassembly Parts Procedure Remark Main EEV 1) Separate 2 parts of the pipe using a welder. 2) Unscrew and remove 1 mounting screws in Bracket accume. (Use + Screw Driver.) Samsung Electronics...
1) Remove 3 screws. (use "+" screw driver) Top Cover 1) Remove 8 screws around cover. (use "+" screw driver) Cabi Front Install 1) Remove 1 screws (use "+" screw driver) and lift up to take off. Samsung Electronics...
Page 29
Remark Guard Cond 1) Take off the sensor. 2) Remove 4 screws. (use "+" screw driver) CABI BACK RIGHT 1) Take out the sensor wire through the hole on cabinet. 2) Remove 10 screws. (use "+" screw driver) Samsung Electronics...
Page 30
Disassembly and Reassembly Parts Procedure Remark CABI BACK RIGHT Cabi Back Install 1) Remove 1 screw. (using "+" screw driver) Samsung Electronics...
Page 31
Disassembly and Reassembly Parts Procedure Remark Cabi Front LF 1) Remove 10 screws. (using "+" screw driver) Samsung Electronics...
Page 32
(using "+" screw driver) 2) Pull out the connector on main pcb board. Bracket motor 1) Remove 2 screws to take off bracket cond. (using "+" screw driver) 2) Remove 2 screws on the base. (using "+" screw driver) Samsung Electronics...
Page 33
The follow step can be divided into 2 case 4) Case 1:Take off the control box directly without welding, a) Remove 2 screws that fix ing reactorwire. (using "+" screw driver) b) Pull out the connector as right pic. Samsung Electronics...
Page 34
2 screws that fix- ing pcb case. f) Band the handel of the case and take off the assy inverter pcb. (Reffer right pic) Becareful when take off inverter pcb;when reassemble should ensure the silicon grease thin and even Samsung Electronics...
Page 35
Discharge the refrigerant first; h) Weling two points as right picture;(using welding tool) 5) Remove 3 screws that fixing control box with partition and bracket valve. 6) Then you can take off the whole control box. Samsung Electronics...
Page 36
Units must be released in advance . Oil separator 1) Separate 3 parts of the pipe using a welder. 2) Unscrew and remove 2 mounting screws in oil separator. (Use + Screw Driver.) Samsung Electronics...
Page 37
Disassembly and Reassembly Parts Procedure Remark Assy tube suction 1) Separate 4 parts of the pipe using a welder. Samsung Electronics...
Page 38
1) Separate 2 parts of the pipe using a welder. 2) Unscrew and remove 2 mounting screws in Bracket accume. (Use + Screw Driver.) 3) Unscrew and remove 1 mounting screws in oil separator. (Use + Screw Driver.) Samsung Electronics...
Page 39
Disassembly and Reassembly Parts Procedure Remark Assy tube 4way valve 1) Separate 5 parts of the pipe using a welder. Samsung Electronics...
Page 40
1) Separate 2 parts of the pipe using a welder. Assy tube lower 1) Separate 1 parts of the pipe pressure using a welder. 2) Unscrew and remove 2 mounting screws in Bracket valve. (Use + Screw Driver.) Samsung Electronics...
Page 41
Disassembly and Reassembly Parts Procedure Remark Assy tube subcooler 1) Separate 2 parts of the pipe using a welder. Assy tube main EEV 1) Separate 2 parts of the pipe using a welder. Samsung Electronics...
Page 42
Disassembly and Reassembly Parts Procedure Remark Cond Out 1) Unscrew and remove 3 screws on each side of the Ass’y Cond Out. (Use + Screw Driver) Samsung Electronics...
Page 43
Procedure Remark Compressor 1) Unscrew and remove 1 mounting screws from the top. 2) Disconnect the comp wire from the compressor. 3) Separate the flet from the compressor. 4) Separate 2 parts of the pipe using a welder. Samsung Electronics...
Page 44
Disassembly and Reassembly Parts Procedure Remark Compressor 5) As shown in the picture, unscrew and remove 4 mounting screws from the bottom.(Use L-Wrench or Monkey Spanner or Socket Wrench) Samsung Electronics...
Page 45
Disassembly and Reassembly [Reference Sheet] Pipe Welding Position AM080/090FXMDGH WELDING POSITION Q'ty 4WAY+OIL SEPA DISCHARGE+OIL SEPA DISCHARGE+COMP EEV OUT+TUBE COOLING TUBE COOLING+TUBE PHE IN TUBE EVI+ACCUM SUCTION+ACCUM 4WAY+TUBE CONNEROR TUBE CONNECTOR+COND IN SUCTION+COMP VAPOR INJECTION+COMP COND OUT+EEV IN Samsung Electronics...
Page 46
Disassembly and Reassembly [Reference Sheet] Pipe Welding Position AM080MXMDGH , AM080MXMDGC WELDING POSITION Q'ty SUCTION+ACCUM 4WAY+ACCUM TUBE COOLING+ TUBE SERVICE V/V TUBE COOLING+ TUBE EEV EVI TUBE DISCHARGE+COMP 4WAY+OIL SEPA SUCTION+COMP 4WAY+TUBE CONNEROR Samsung Electronics...
Leakage test by nitrogen gas and release all nitrogen gas from outdoor unit and evacuate again. Add an additional refrigerant to the system which was decided step 3. Open the service valve and choose Auto Trial Operation through pushing K1 switch in outdoor main PCB and hold 1 time. Samsung Electronics...
Page 48
GB052* : 31.7kg / GB066* : 35.5kg / GB070 : 36.8kg (including oil 1200cc) If broken compressor is 0.8kg or more lighter than new one, Oil return line is blocked. 2. Check the weight of oil lubricating part. (Assy. accumulator, Assy. oil separator) Samsung Electronics...
1) Separate 1 fixing screw from EEV kit. (Use + Serew Driver) 2) Separate cabinet from EEV kit. Control parts 1) Separate 2 fixing screws from EEV kit. (Use + Serew Driver) 2) Separate control part from EEV kit. Samsung Electronics...
4. Troubleshooting 4-1. Service Operation 4-1-1 Special Operation Samsung Electronics...
Page 51
Troubleshooting K1 button function K1 Control (Note 1) Not available on AM***FXM**C Series K2 button function “K” “9” XX Samsung Electronics...
Page 52
Troubleshooting K3 button function K4 button function Main version Fan 1 version FAN1 Fan 2 version FAN2 AUTO MANU AM080FXM✳ 87 °C 87 °C 87 °C Samsung Electronics...
Page 53
Troubleshooting How to display integrated error code A002 A002 U200 U200 C001 C002 Error code Samsung Electronics...
4-2 Appropriate Measures for Different Symptom Error due to repeated address setting (when 2 or more devices has same address within the network). (E-108) E-108 ◑ ◑ × × × ※ ● ◑ A000 A001 A002 A00 K3 reset Whole system power reset Samsung Electronics...
Page 62
Communication error between indoor and outdoor unit (E-201) (Installation number setting error repeated indoor unit address, indoor unit communication cable error.) E-201 ◑ ◑ × × × Filter ◑ × ◑ × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 63
Troubleshooting Communication error between indoor and outdoor unit (E-201) Samsung Electronics...
Page 64
Troubleshooting Communication error on all PBA within the outdoor unit C-Box, communication cable error. (E-205) E-205 ◑ ◑ × × × Filter ◑ × ◑ × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 65
Troubleshooting Communication error on all PBA within the outdoor unit C-Box, communication cable error. (E-206) E-206 ◑ ◑ × × × Filter ◑ × ◑ × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 66
Troubleshooting Error on outdoor temperature sensor of outdoor unit (Short or open). (E-221) E-221 ◑ ◑ × × × Filter ◑ × ◑ × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 67
Troubleshooting Error on COND OUT temperature sensor of main outdoor unit (Short or open). (E-231) E-231 ◑ ◑ × × × Filter ◑ × ◑ × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 68
Troubleshooting Error on discharge temperature sensor of compressor 1 (Short or open). (E-251) E-251 ◑ ◑ ◑ × × Filter ◑ ◑ ◑ × 27°C ◑ ◑ ◑ × × ※ ● ◑ Samsung Electronics...
Page 69
Discharge temperature sensor of compressor 1 is detached from the sensor holder on the pipe. (E-262) / Top sensor of compressor 1 is detached (E-266) E-262 / E-266 ◑ ◑ ◑ × × Filter ◑ ◑ ◑ × 27°C ◑ ◑ ◑ × × ※ ● ◑ Samsung Electronics...
Page 70
Troubleshooting Suction temperature sensor is detached from the sensor holder on the pipe. (E-269) E-269 ◑ ◑ ◑ × × Filter ◑ ◑ ◑ × 27°C ◑ ◑ ◑ × × ※ ● ◑ Samsung Electronics...
Page 71
Troubleshooting Refrigerant leakage or error on high pressure sensor (Short or open). (E-291) E-291 ◑ ◑ × × × Filter ◑ ◑ × × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 74
Troubleshooting Error on temperature sensor of double layer pipe/liquid pipe(sub heat exchanger) (Short or open). (E-311) E-311 ◑ ◑ × × × Filter ◑ ◑ × × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 75
Troubleshooting Error on EVI (ESC) IN temperature sensor (Short or open). (E-321) E-321 ◑ ◑ × × × Filter ◑ ◑ × × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 76
Troubleshooting Error on EVI (ESC) OUT temperature sensor(Short or open). (E-322) E-322 ◑ ◑ × × × Filter ◑ ◑ × × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 77
Troubleshooting Error due to operation failure of Fan2 (E-346) / Error due to operation failure of Fan1 (E-446) E-346 / E-446 Criterion Samsung Electronics...
Page 78
Troubleshooting Error due to operation failure of Fan2 (E-346) / Error due to operation failure of Fan1 (E-446) Samsung Electronics...
Page 79
Troubleshooting Motor wire of Fan2 is not connected. (E-347) E-347 ◑ ◑ ◑ × × Filter ◑ ◑ ◑ × 27°C ◑ ◑ × × × ※ ● ◑ Samsung Electronics...
Page 80
Troubleshooting Lock error on Fan2 of outdoor unit. (E-348) / Lock error on Fan1 of outdoor unit. (E-448) E-348 / E-448 Samsung Electronics...
Page 81
Troubleshooting Error due to overheated motor of outdoor unit's Fan2 (E-353) / Error due to overheated motor of outdoor unit's Fan1. (E-453) E-353 / E-453 Samsung Electronics...
Page 82
Troubleshooting Error due to overheated IPM of Fan2. (E-355) / Error due to overheated IPM of Fan1. (E-455) E-355 / E-455 Samsung Electronics...
Page 83
Troubleshooting Error due to overcurrent of Fan2. (E-378) /V-limit error on Fan2 of compressor. (E-389) / Error due to overcurrent of Fan1. (E-478) / V-limit error on Fan1 of compressor. (E-489) E-378 / E-389 / E-478 / E-489 Samsung Electronics...
Page 84
Troubleshooting Hall IC connection error of Fan2 (E387) / Hall IC connection error of Fan1. (E487) E-387 / E-487 Samsung Electronics...
Page 85
Output current sensor error of Fan2. (E-393) / Output current sensor error of inverter PBA 1. (E-468) / Error due to input current of inverter 1. (E-485) / Output current sensor error of Fan1. (E-493) E-378 / E-389 / E-478 / E-489 Samsung Electronics...
Page 86
Troubleshooting DC voltage sensor error of Fan2. (E-396) / DC voltage sensor error of inverter PBA 1. (E-469) / DC voltage sensor error of Fan1. (E-496) E-396 / E-469 / E-496 Samsung Electronics...
Page 96
Troubleshooting Phase reversal or phase failure(3Ø outdoor unit wiring, R-S-T-N), connection error on 3 phase input. (E-428) Samsung Electronics...
Page 97
EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect connector insertion of EVI (ESC) EEV. (E-438) E-438 ◑ ◑ ◑ × × Filter ◑ ◑ ◑ × 27°C ◑ ◑ ◑ × × ※ ● ◑ Samsung Electronics...
Page 98
Troubleshooting EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect connector insertion of EVI (ESC) EEV. (E-438) Samsung Electronics...
Page 99
Troubleshooting Error due to refrigerant leakage. (E-439) / Operation prohibited due to low pressure. (E-443) E-439 / E-443 Pressure sensor Open/Short error determination method valve) Samsung Electronics...
Page 100
Heating mode restriction due to high air temperature. (E-440) / Operation prohibited due to low pressure. (E-441) E-440 / E-441 ◑ ◑ ◑ × × Filter ◑ ◑ ◑ × 27°C ◑ ◑ ◑ × × ※ ● ◑ Samsung Electronics...
Page 101
Troubleshooting Refrigerant charging restriction in heating mode when air temperature is over 15°C. (E-442) E-442 ◑ ◑ ◑ × × Filter ◑ ◑ ◑ × 27°C ◑ ◑ ◑ × × ※ ● ◑ Samsung Electronics...
Page 107
Troubleshooting Error due to overheat caused by contact failure on IPM of inverter PBA 1. (E-500) E-500 Both end resistance values of IGBT module pin(8, 9 pin) 9000 3000 2000 1200 Samsung Electronics...
Page 108
Troubleshooting Outdoor unit’s option switch setting error (Using E2P option of other models or emergency operation for compressor malfunction option setting was enabled on all compressors of corresponding outdoor unit). (E-560) E-560 Samsung Electronics...
Page 109
Troubleshooting Outdoor unit’s option switch setting error (Using E2P option of other models or emergency operation for compressor malfunction option setting was enabled on all compressors of corresponding outdoor unit). (E-563) E-563 Samsung Electronics...
Page 110
Troubleshooting Error due to using single type outdoor unit in a module installation. (E-573) E-573 Samsung Electronics...
③ ④ CN23- INVERTER 220V CN21-FAN A CN22-MAIN 220 RST- RST INPUT #1 : AC #1 : R #1 : AC T-IN #2 : #2 : S #2 : AC S-IN #3 : AC #3 : T R-IN Samsung Electronics...
YEL / GRN (BLK) 1 2 3 CN45 WHT BLK BRN SKYBLU CN77 (WHT) (WHT) CN36 CN55 (BLU) COMM PCB (RED) BRN SKYBLU CN44 (YEL) INDOOR-OUTDOOR SOLUTION 3 PHASE POWER COMM This Document can not be used without Samsung’s authorization. Samsung Electronics...
25. Control box temp. Sensor : Control box internal temperature measurement, thermal protection used for the control. 26. Receiver : Storing the refrigerant piping system, a stable liquid refrigerant supply. 27. Liquid Tube Valve : Refrigerant in the outdoor unit side, the indoor unit during heating operation to rotate the valve operation. Samsung Electronics...
■ Setting outdoor unit key function Switch Setting Function Remarks Not applicable Enable maximum capacity restriction for cooling Restrict excessive capacity increase when operating indoor operation units with small capacity Disable maximum capacity restriction for cooling SW53 operation Not applicable Not applicable Samsung Electronics...
Standard + General temp. + Non module Model grade Standard + Tropical + Non module 380 ~ 415 V, 50 Hz, 3 Phase Power 380 V, 60 Hz, 3 Phase Mode Heat pump (R410a) CHINA EUROPE PHILIPPINES Buyer INDIA TURKEY MIDDLE EAST SAUDI ARABIA Samsung Electronics...