2.2
REF615R
Engineering Manual
In PCM600 it is possible to set up a hierarchical structure of five levels for the IED
identification.
Project
Substation = name of the substation
Voltage level = identifies to which grid type or part the IED belongs in the substation
Bay = bay within the voltage level
IED = the selection of the IED that is used in the bay; it is possible to insert
several IEDs within a bay, for example, one control IED and two protection IEDs

Standard configuration concept

The product series covers IEDs developed for the protection of medium voltage
applications. Every product has predefined application-specific software called
standard configuration that contains protection, control, supervision and measurement
function blocks and default logical connections; for more information, see the
application manuals. The product also includes the standard configuration specific
default single-line diagram.
The standard configuration software consists of connections between an application's
functions developed according to the needs of a particular functional application. The
inputs and outputs are similarly assigned to a default set of connections such as
position indication and Master trip. The alarm LEDs are assigned to default
connections based on the order number.
Current and voltage channels for protection and measurement functions
are fixed as a part of standard configuration and cannot be reassigned
with Signal Matrix or Application Configuration in PCM600.
The single-line diagram consists of an application-specific general arrangement of a
single-line diagram that includes position indications and the selection of controllable
objects and measurements.
The content of the standard configuration depends on the intended functional
application. The standard configurations also have selectable software options, which
are selected when ordering the IED. Some of the software options are related to the
IED hardware.
The standard configurations can be used as is, but they can also be modified by using
the PCM600. The standard configuration itself can be modified or extended by using
the Application Configuration tool, the Signal Matrix tool and the communication
Section 2
IED engineering process