SINUMERIK 840/840C SINUMERIK 880/880 GA2 Computer Link General Description Planning Guide 09.95 Edition Manufacturer Documentation...
Page 2
SINUMERIK 840/840C SINUMERIK 880/880 GA2 Computer Link General Description Planning Guide Manufacturer Documentation Valid for: Control Software version SINUMERIK 840 from 1 SINUMERIK 840C from 1 SINUMERIK 880 T/M from 3 SINUMERIK 880 GA2 T/M from 1 September 1995 Edition...
Page 3
This does not, however, represent an obligation to supply such functions with a new control or when servicing. This publication was produced on the Siemens 5800 Office System. Subject to change without prior notice. The reproduction, transmission or use of this document or its contents is not permitted without express written authority.
Page 4
The term ”SINUMERIK 8X0” is used in this description as a short form for ”SINUMERIK 840/880”. Technical information This documentation applies to software version 1 and higher in the case of SINUMERIK 840 and 840C to software version 3 and higher in the case of SINUMERIK 880 GA2 to software version 1.
Page 5
General Local Area Networks Interface Modules Message Frames Configuration and Test Abbreviations Appendix...
A computer link can be realised using a bus connection or using one of many serial connections. The following figure shows the SIEMENS computer systems used for CAD, FMS, NC Archive and PPC as well as the RC, NC and PLC systems on a common bus cable. If older systems are to be connected to the bus, e.g.
(opposite: closed networks). 1.1.5 SINEC AP 1 SINEC AP 1 is the Siemens Network Architecture Automation Protocol Version 1, a Siemens automation protocol. It was developed for the integration of the following systems in a factory automation system: •...
One or several logical peers can be served via a TPV transport connection. (When connecting the SINUMERIK 8X0 to the Siemens FMS only one logical peer per transport connection is allowed.) The ”logical peer” is determined by the addressing in the application layer alone in the case of a serial connection.
At present there are no uniform international standards for layers 5 to 7 of the OSI model for the NC applications. As a first step to standardization of OSI layers 5 to 7 within the company, Siemens have therefore defined the AP 1 automation protocol. It is suitable for use on all Siemens automation devices.
Page 33
Number of bus interface modules interfaces interfaces CP 231 CP 315 CP 373 Examples of complements with interface modules for SINUMERIK 840 SYSTEM Slot 4....13 Standard control CP 231: Bus connection CP 315: Serial connection (basic board, 1 SS) CP 373: Serial connection (expansion board, 3 SS) Rack configuration for SINUMERIK 840 3–4...
The PROTID characterizes the protocol version. For SINEC AP1.0 it is preset with Hex. MPXADR =00 (Multiplex Address) Multiplexing in layer 7 is not used with connection to Siemens FMS systems. COMCLS =04 (Command Class) COMCLS describes global functions;04 means serial transfer.
SINUMERIK 8X0 systems permits the use of different protocols on the application layer. For this purpose, the SINEC Technological Functions (STF) have been defined by Siemens as a common level-7 protocol. The SINEC Technological Functions are fully compatible with ISO 9506 (MMS), parts 1 and 2 with regard to the scope of functions and can thus easily be integrated in MAP 3.0.
Pass data to the PLC • Process functions by means of standard routines. The SINUMERIK 880 contains its own COM CPU. The COM area in the SINUMERIK 840 is built into the NC CPU. Multiport RAM Standard routines Connection monitoring...
Page 91
Note: For reasons of compatibility a maximum message frame length of 224 bytes must be used with links to Siemens FMS systems or SINUMERIK 850. The maximum message frame length can be set via machine data . In case of larger data volumes, subsequent message frames are sent until all data has been transmitted.