ROOM AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT AS24A2QC US24A2QC AS18A2QC US18A2QC SERVICE Manual AIR CONDITIONER CONTENTS 1. Installation 2. Disassembly and Reassembly 3. Troubleshooting 4. Exploded Views and Parts List 5. Refrigerating Cycle Block Diagrams 6. Wiring Diagrams 7. Schematic Diagrams E DB68-00277A(6)
1. Installation 1-1 Refrigerant Refill Procedure • Refill an air-conditioner with refrigerant when refrigerant has been leaked at installing or using 1. Purge air(for new installation only). 2. Turn the 3-way valve clockwise to close, connect the pressure gauge(low pressure side) to the service valve, and open the 3-way valve again.
Page 3
1-2 “Pump down” Procedure Pump down' shall be carried out when an evaporator is replaced or when the unit is relocated in another area. 1. Remove the caps from the 2-way valve and the 3-way valve. 2 Turn the 3-way valve clockwise to close and connect a pressure gauge(low pressure side) to the service valve, and open the 3-way valve again.
2. Disassembly and Reassembly Stop operation of the air conditioner and remove the power cord before repairing the unit. 2-1 Indoor Unit Parts Procedure Remark Front Grille 1) Stop the air conditioner operation and block the main power. 2) Seperate tape of front panel upper. 3) Contract the second finger to the left, and right handle and pull to open the inlet grille.
Page 5
Parts Procedure Remark Ass’y Tray Drain. 1) Do “1”, above. Separate the drain hose from the extension drain hose. 2) Take the display PCB out. (Center of indoor unit) 3) Loosen two fixing screws of left and right 4) Pull tray drain out from the back body. Electrical Parts 1) Do “1”, “2”, above (Main PCB)
Page 6
Parts Procedure Remark Fan Motor and 1) Do “1” “2” ”3” “4”, above. Cross Fan 2) Loosen the fixing three screws and separate the motor holder. 3) Loosen the fixing screw of fan motor. (By use of M3 wrench) 4) Separate the fan motor from the fan. 5) Separate the fan from the left holder bearing.
Page 7
2-2 Outdoor Unit Parts Procedure Remark Cabinet 1) Turn off the unit and remove the power cable 2) Remove the top cover. 3) Remove the control box cover. 4) Unplug the ass'y cable. 5) Remove the cabi-side. 6) Remove the cabi-front. * When you assemble the parts, check if the each parts and electric connectors are fixed firmly.
3. Troubleshooting 3-1 Items to be checked first 1) Is the voltage of the power correct? The input voltage shall be rating voltage ±10% The airconditioner may not operate properly if the voltage is out of this range. 2) Is the link cable linking the indoor unit and the outdoor unit linked properly? The indoor unit and the outdoor unit shall be linked by cables.
3-2 Fault Diagnosis by Symptom 3-2-1 No Power(completely dead)-Initial diagnosis 1) Checklist : (1) Is input voltage normal? (rating voltage ±10% range) (2) Is AC power linked correctly? (3) Are connections between primary side, secondary side of the power transformer and PCB good. (4) Is output voltage of DC regulator IC KA7812 (IC01) normal? (11VDC-12.5VDC) (5) Is output voltage of DC regulator IC KA7805 (IC02) normal? (4.5VDC-5.5VDC) Troubleshooting procedure...
Page 10
3-2-2 When the Indoor Unit Fan Does Not Operate. (Initial Diagnosis) 1) Checklist : (1) Is the indoor unit fan motor properly connected with the connector (CN73)? (2) Is the AC voltage correct? (3) Is HALL IC in indoor fan motor properly connected with the connector (CN43)? (4) Is the running capacitor properly connected with the solder part of the PCB? 2) Troubleshooting procedure After unplugging out the power cord should...
Page 11
3-2-3 When the Outdoor Unit Does Not Operate. (Initial Diagnosis) 1) Checklist : (1) Is input voltage normal?(rating voltage ±10% range) (2) Is the set temperature of the remote control higher than room temperature in COOL mode? (3) Is the POWER IN connector (CN78) linked correctly? (4) Is the outdoor unit properly connected with the TERMINAL BLOCK connector(5P)? Troubleshooting procedure After unplugging out the power cord should be...
Page 12
3-2-4 When the UP/DOWN Louver Motor Does Not Operate. (Initial Diagnosis) Checklist : (1) Is input voltage normal? (rating voltage ±10% range) (2) Is the UP/DOWN louver motor properly connected with the connector (CN61)? Troubleshooting procedure Remove power cord and plug in again in approx. 5 seconds. Is operating lamp blinking? Check as in the procedure "No Power parts".
Page 13
3-2-5 If Operation By Remote Control Unit Is Impossible. (Initial Diagnosis) 1) Troubleshooting procedure Remove power cord and plug in again approx. 5 Seconds Is operation lamp blinking? Check as in the procedure “NO Power parts”. Refer to page 5-2. “...
Page 20
Parts List Q’TY CODE NO Description Specification Remark US24A2QC DB90-10634A ASS’Y-CABI FRONT SC-90073T DB90-20210A ASS’Y-BASE OUT SC-90073T DB67-50074A ASS’Y-FAN AS+G/F20% DB60-20020A Bolt special M8L25 DB31-10110E MOTOR FAN OUT OSME - 716SRC DB95-20147A ASS’Y-MOTOR B/K SGCC-M DB94-50039A PARTITION SGCC-M DB75-30102B ASS’Y-CONDENSER ASS’Y DB90-40176B COVER-CONTROL...
Page 21
4-2-3 PCB Box Parts List Q’TY CODE NO Description Specification Remark AS24A2QC AS18A2QC DB61-10163A CASE-CONTROL DB93-10553C Ass'y main PCB PD-S18B1Q-02 DB32-10008E Ass'y Thermistor 103AT 240/240 DB93-10599B Ass’y PCB Display ASS’Y DB26-10065B Transformer AC230V/DC17...
5. Refrigerating Cycle Block Diagram INDOOR UNIT OUTDOOR UNIT Capillary tube 2-way valve Liquid side Heat Heat exchanger exchanger (Evaporator) (Condenser) Gas side 3-way valve Cooling Compressor Gas leak check point Refrigerating cycle temperature and pressure STD Pressure Piping Temp(°F) Use Temp.
Page 26
7-2 Outdoor Unit US18A2QC MARK NAME MARK NAME MAGNETIC CONTACTOR TB 1,2 TERMINAL BLOCK CAPACITOR FAN MOTOR FUSE(2A,250V~) SPARK KILLER US24A2QC MARK NAME MARK NAME MAGNETIC CONTACTOR TB 1,2 TERMINAL BLOCK CAPACITOR FAN MOTOR FUSE(2A,250V~) SPARK KILLER...