Page 1
Pool & Spa Heater Atmospheric Models Lo NOx Models 206A, 266A, 336A & 406A 207A, 267A, 337A & 407A WARNING: If these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Page 2
WATER CHEMISTRY (Corrosive water voids all warranties) For your health and the protection of your pool equipment, it is essential that your water be chemically balanced. The following levels must be used as a guide for bal- anced water. Other Pool & Spa Recommended Level(s) Fiberglass Pools Fiberglass Spas Types...
CONTENTS PART ONE Wiring Diagram - Digital Models, Lo NOx OWNER'S OPERATING INSTRUCTIONS SECTION 4 SERVICING INSTRUCTIONS SECTION 1 General Location of Controls START-UP PROCEDURES Control Panel Removal Before Start-Up Control Adjustments - Digital and AFT Models Lighting Instructions & Shut-Off Procedures - Control Adjustments - Millivolt Models Manually Lighted Pilots MV Thermostat Operation - Digital Board...
PART ONE OWNER'S OPERATING INSTRUCTIONS FOR YOUR SAFETY - READ BEFORE OPERATING WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. SECTION 1 - START-UP PROCEDURES Your pool/spa heater has been designed for years of safe and reliable pool/spa water heating.
CAUTION: Propane gas is heavier than air and will settle on the ground. Since propane can accumulate in confined areas, extra care should be exercised when lighting propane heaters. LIGHTING INSTRUCTIONS AND SHUT-OFF PROCEDURES MILLIVOLT SYSTEM (MANUALLY LIGHTED PILOT) *If you cannot reach your gas supplier, call the This appliance has a pilot that must be lit by fire department.
CAUTION Propane gas is heavier than air and will settle on the ground. Since propane can accumulate in confined areas, extra care should be exercised when lighting propane heaters. OPERATING INSTRUCTIONS AND SHUT-OFF PROCEDURES ELECTRONIC IGNITION SYSTEM (AUTOMATICALLY LIGHTED PILOT) *If you cannot reach your gas supplier, call the This appliance is equipped with an ignition fire department.
AFTER START-UP Feel the inlet and outlet pipes. Outlet pipe should be only slightly warmer than the inlet. It should not be hot. WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control to the appliance.
2. Your pump strainer basket may be full. If so SECTION 3 - MAINTENANCE AND remove debris. CARE PROCEDURES 3. Your filter may be dirty. If so, backwash or clean WARNING: Check the heater for possible rodent filter. (To tell if your filter is dirty, look to see if the nests after long periods of non-use.
WINTERIZING THE POOL & SPA HEATER COLD WEATHER OPERATION Heaters installed outdoors in freezing climate areas IMPORTANT FREEZE INFORMATION may be shut down for the winter. Observe the follow- ing procedure for winterizing the heater: MODERATE CLIMATE: Heater operation can contin- ue during short-term cold spells.
PART TWO INSTALLATION AND SERVICE INSTRUCTIONS SECTION 1 - RECEIVING EQUIPMENT The manufacturer recommends that this manual be reviewed thoroughly before installing your pool/spa heater. If there are any questions that this manual does not answer, please contact the factory or your local represen- tative.
SECTION 2 - GENERAL SPECIFICATIONS These heaters are design-certified and tested under the latest requirements of the ANSI Z21.56 / CSA 4.7 Standard for Gas-Fired Pool Heaters. All heaters can be used either indoor or outdoors. The appropriate top designated for each type of use is required. If necessary, the top can be changed at a later date to change from outdoor to indoor or vice versa.
CLEARANCES ALL HEATERS For clearances from combustible surfaces, see the When installed according to the listed minimum clear- chart below. ances from combustible construction, the pool heater can still be serviced without removing permanent CLEARANCE FROM construction around the heater. COMBUSTIBLE CONSTRUCTION However for ease of servicing, we recommend a clear- INDOOR INSTALLATIONS:...
Page 13
Heaters must not be installed under an overhang of less than three 3 ft from the top of the heater. Three sides must be open in the area under the overhang. Roof water drainage must be diverted away from the heaters installed under overhangs with the use of gutters.
FLORIDA BUILDING CODE 2001 WIND SPEED = 150 MPH, 3 SECOND GUST EXPOSURE = C 206/266/336/406 Atmospheric MODEL # 20” 23” 26” 29” 40” 28” 2” x 6” x 1/8” Pallet Anchor Bracket (4 Total) (Kit# 011636) 3” Min. Conc. Pad by others 1/4”...
010744 009832 appliance. 336/337 010745 009833 Optional Raypak D-2 406/407 010745 009833 Power Vent For more information consult the D-2 Power Vent manual, (Catalog No. 6000.57.1). The power vent assembly is a fan-assisted combustion system designed for application to models 206-407. The unit, when installed as directed, is capable of operating in applications such as through-the-wall venting and reduced horizontal and vertical vent pipe sizes in new and current installations.
The discharge opening must be a minimum of 2 ft ver- GAS SUPPLY CONNECTIONS tically from the roof surface and at least 2 ft higher than any part of the building within 10 ft. Vent stack shall be at least 5 ft in vertical height above the drafthood out- let.
GAS PRESSURE REGULATOR ELECTRONIC IGNITION GAS VALVES-CONTINUED The gas pressure regulator is preset at 4.0 in. WC throughout for natural gas, and 10.5 in. WC. for propane gas. The pressure at the gas valve, taken with a manometer, should be about 4.0 in. WC natural gas (3.1 in.
required, use a silicon base such as AquaLube etc. POLYMER HEADERS (STANDARD MODELS) Before attaching the 2-inch unions to the inlet/outlet There are two sets of flange gaskets supplied with header, make sure the O-rings are properly seated in your heater. Use the appropriate gaskets for all your the grooves.
PRESSURE RELIEF VALVE INSTALLATION INTERNAL AUTOMATIC BYPASS VALVE To conform to local building codes, it may be neces- In addition to the Unitherm Governor, a built-in auto- sary to install a pressure relief valve. A 3/4" pressure matic bypass valve is provided in the in/out header. relief valve, having a capacity equal to the BTUH out- While the Unitherm Governor responds to the changes put of the model to be installed, is recommended for...
PLUMBING—WATER CONNECTIONS Single Pool Heater Installation Multiple Pool Heater Installation The heater requires water flow and positive pressure to fire and operate properly. It must therefore be installed downstream of the discharge side of the filter pump. A typical installation is plumbed as follows: 1.
HEAT EXCHANGER REVERSAL PROCEDURE - STANDARD MODELS 1. Remove right and left side access panels (Figure 1). 2. Disconnect wires at high limit, AGS (automatic gas shut-off), and pressure switch on the in/out header (Figure 2). 3. Digital/AFT Models: Remove the thermostat tem- perature sensor by loosening the compression fit- ting nut (Figure 3).
ELECTRICAL WIRING CAUTION: Heater must be electrically grounded and NOTE: If it is necessary to replace any of the original bonded. Bonding lug is provided loose with the wiring, use 105°C wire or its equivalent, and/or 150°C heater. Install bonding lug on lower right or left side wire or its equivalent, like the original wiring.
TRANSFORMER WIRING 120 VAC WIRING For 120 VAC input power to the unit, connect the black wire to the “L1” or hot leg of the power supply. Connect the white wire to the “Ret” or neutral leg of the power supply. Attach the wire nut to the red wire. There should be no connection to the red wire for 120 VAC operation.
SECTION 4 - SERVICING INSTRUCTIONS GENERAL LOCATION OF CONTROLS ATMOSPHERIC Drain Plug (Located in rear header) Mounted On Top Of Header HL1 - High Limit HL2 - High Limit Pressure Switch Temp Sensor/Well Digital Thermostat Circuit Board Unitherm Governor Draw Plug Roll-Out Switch Transformer...
CONTROL PANEL REMOVAL CONTROL ADJUSTMENTS - MILLIVOLT MODELS The water temperature is controlled by the heater ther- 1. Remove screw from front door. Set aside door for mostat on the upper front panel of the heater. The serviceability. control center contains an On/Off switch and one ther- mostat.
THERMOSTAT OPERATION - DIGITAL BOARD Thermostat operation Your heater is equipped with a microprocessor-controlled thermostat that controls the pool or spa temperature by measuring the temperature of the water entering the heater. It monitors the water temperature and turns the heater on when it senses that the water temperature is below the set point.
Page 34
Program Button F/Cfff – Fahrenheit to Celsius 1) To access the program screen, press the Mode Refer to step one above to access the program button until the display reads OFF. Remove the screen. Press the Mode button until F/Cfff appears on four screws holding the control cover on.
NOTE: The LCD temperature display may not agree with the temperature reading of your pool or spa ther- mometer. The heater reads the water temperature at the inlet. Due to the circulation characteristics of any pool or spa, the water temperature at the inlet to the heater may differ from that observed at a given location in the pool or spa.
REMOTE CONTROL INSTALLATION AND OPERATION CAUTION: Before installing remote controls to the digital thermostat model heaters, read the following: The digital thermostat model is remote-ready in most cases. The digital liquid crystal display (LCD) shows the actual pool temperature, operating status, and service codes (See examples below). The touch pad on the con- trol panel allows you to select the desired pool or spa temperature.
Page 37
THERMOSTAT OPERATION - ADVANCED FLAME TECHNOLOGY (AFT) BOARD LCD Display Temp Buttons Mode Button Program button The pool heater touchpad, located on the upper front Service Menu and Fault History panel of the heater, allows the user to select either To access the Service Menu and fault history, press POOL or SPA operation, and to adjust the setpoint the MODE and UP arrow buttons simultaneously for 3...
Page 38
Set Factory Defaults Press the DOWN arrow button. The Fault History can Refer to step one above to access the program display up to ten faults in memory. The order of the screen. Set Factory Defaults should appear on the faults begins with “Fault Last,”...
NOTE: The LCD temperature display may not agree with the temperature reading of your pool or spa ther- mometer. The heater reads the water temperature at the inlet. Due to the circulation characteristics of any pool or spa, the water temperature at the inlet to the heater may differ from that observed at a given location in the pool or spa.
REMOTE CONTROL INSTALLATION AND OPERATION CAUTION: Before installing remote controls to the AFT thermostat model heaters, read the following: The digital thermostat model is remote-ready in most cases. The digital liquid crystal display (LCD) shows the actual pool temperature, operating status, and service codes (See examples below). The touch pad on the con- trol panel allows you to select the desired pool or spa temperature.
REMOTE CONTROL WIRING Important Installation Notes for Remote or External Wiring Configuration • Remote wiring must be run in a separate conduit. • Remote wiring must not be run parallel to high voltage lines. • For runs of under 30 feet, remote wiring should have stranded conductors with a minimum of 22 AWG, 600V, cable twisting 1.5 to 2.5 in.
4. Turn the heater ON. TIME CLOCK/FIREMAN’S SWITCH 5. Manually turn the pressure adjustment knob clock- To operate the heater with a time clock, connect the wise until the heater shuts off. (A flat screwdriver timer to the fireman’s switch connection in the heater’s may be necessary if knob is too tight.) wiring.
NOTE: An erratic high limit is often characteristic of an MAIN BURNER AND ORIFICE REMOVAL - internal heat exchanger problem, e.g. scale build-up, ATMOSPHERIC MODELS defective bypass. Refer to Troubleshooting section (on 1. Remove burner tray. pg. 47). 2. Remove screws and burner hold-down bracket. HIGH LIMIT REMOVAL NOTE: If the heat exchanger is sooted badly, the burner hold-down bracket and spacer can become dis-...
Extension Pieces (2) Auger with Carbide Tip Wire Brush 4. Remove heat exchanger from the heater and wash HEAT EXCHANGER REMOVAL with a garden hose, making sure soot is removed 1. Shut water, gas and electricity off, close valves from spaces between fins. and relieve pressure, then remove relief valve.
UNITHERM GOVERNOR (U.G.) REPLACEMENT 1. Shut water, gas and electricity off, close valves Retainer Plug and relieve pressure. 2. Drain heat exchanger. U.G. 3. Remove retainer plug located next to the outlet Spring pipe connection. 4. Unsnap old U.G. to remove from retainer plug. Gasket Snap in new U.G.
LO NOx HEATERS (CONTINUED) MAIN BURNER AND ORIFICE REMOVAL 1. Remove burner tray, following above procedure. BAFFLE MOUNTED COMBUSTION 2. Remove pilot. See pilot removal procedure. INLET SIDE AIR BLOWER 3. Remove (8) total screws from the burner hold- PILOT down brackets, front and rear of tray.
SECTION 5 - TROUBLESHOOTING MECHANICAL IMPORTANT NOTICE These instructions are intended for the use of qualified personnel who are specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed.
ELECTRICAL - STANDING PILOT MILLIVOLT POOL OR SPA HEATER ELECTRICAL CHECK WITH MILLIVOLT GAS VALVE CAUTION: For qualified service personnel only. 1. Filter must be on with adequate water flow through heater. 2. Gas valve must be in "ON" position. Thermostat set higher than pool water temperature. 3.
ELECTRICAL - ELECTRONIC IGNITION IID WARNING HIGH VOLTAGE For qualified technicians ONLY NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater. START TURN GAS SUPPLY OFF. NOTE: Before troubleshooting, familiarize yourself with the start-up and check-out TURN THERMOSTAT procedure.
DIGITAL/AFT CONTROL LOGIC - FLOW CHART Power On • Check On/Off switch (under lid on control panel) Is the water • Check for 120/240 volts to the transformer temperature displayed? (time clock, circuit breaker, wire connections) • Check for 24 volts to Circuit Board (P6 connector) REM and Water Temperature Push MODE displayed and flashing...
SECTION 6 - REPLACEMENT PARTS NOTE: To supply you with the correct part, it is impor- If determined defective by the Company and within warranty, a like part or equal substitution will be tant that you supply the heater model number, serial returned, freight collect.
Page 54
(OPTIONAL) 14-HM 16-HM 13-HM 15-HM 6-HM 5-HM 2-HM 12-HM 7-HM 4-HM 10-HM 11-HM 3-HM 8-HM 17-HM 9-HM HONEYWELL IID ATMOSPHERIC PILOT POLYMER IN/OUT HEADER AND ACCESSORIES HONEYWELL MILLIVOLT PILOT IID LO NOx PILOT...
Page 55
ATMOSPHERIC HEATERS CALL BURNER TRAY * ) l * ) l v i l v i l c i f * ) l c i f * ) l CONTROLS Thermostat Auto Reset 135 Deg Surface Mount 006725F 006725F 006725F 006725F AGS 135°...
Page 56
ATMOSPHERIC HEATERS CALL HEAT EXCHANGER - METAL Heat Exchange Assy.Cupro Nickel ASME CI 010360F 010361F 010362F 010363F & " 2 " 2 l l e l l e p i l & CONTROL BOX c t i MISCELLANEOUS COMPONENTS c t i Pressure Switch 11 PSI Special-See Water Pressure Switch Adj.
Page 57
ATMOSPHERIC HEATERS CALL SHEETMETAL Flue Collector (Units with Polymer Header) 010071F 010072F 010073F 010074F e l l s t i Door Assy. Access Panel Set (3 Pcs Units with Polymer Header) 010311F 010311F 010311F 010311F Access Panel Set (3 Pcs. Units with Metal Header) 010312F 010312F 010312F...